Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Smart Pressure Transmitter for Nuclear Service www.rosemountnuclear.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Rosemount 3051N Smart Pressure Transmitter for Nuclear Service Rosemount 3051 HART Universal Revision 5 NOTICE Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product. Within the United States, contact Rosemount Nuclear Instruments, Inc. at 1-952-949-5210 for assistance.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Rosemount Nuclear Instruments, Inc. Warranty and Limitations of Remedy The warranty and limitations of remedy applicable to this Rosemount equipment are as stated on the reverse of the current Rosemount quotation and customer acknowledgment forms. RETURN OF MATERIAL Authorization for return is required from Rosemount Nuclear Instruments, Inc. prior to shipment. Contact Rosemount Nuclear Instruments, Inc.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Revision Status Changes from June 2006 to June 2008 Page (Old) Page (New) Cover, throughout TOC-1 Throughout 3-6 and 3-8 3-12 Cover, throughout Page i, back cover Page iii i to iv and TOC-1 to TOC-4 Throughout 3-6 and 3-8 3-12 5-7 5-8 TOC-1 to TOC-8 Changes Document revision date change from June 2006 to June 2008, rev from BA to CA CE mark added with Rosemount Nuclear Instruments, Inc.
Reference Manual Rosemount 3051N iv 00809-0100-4808, Rev CA June 2008
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Table of Contents SECTION 1 Introduction Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 SECTION 2 Transmitter Functions Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 Warnings . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Rosemount 3051N 00809-0100-4808, Rev CA June 2008 Zero Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17 Full Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18 Recall Factory Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19 Recall Factory Trim— Sensor Trim . . . . . . . . . . . . . . . . . . . . . . . 2-19 Recall Factory Trim— Analog Output. . . . . . . . . . . . .
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Temperature Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5 Span and Zero, Zero Elevation, and Suppression . . . . . . . . . . . . . 5-6 Humidity Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6 Volumetric Displacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6 Turn-on Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Rosemount 3051N 00809-0100-4808, Rev CA June 2008 Multifunction LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12 Touch Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12 Using the Soft Input Panel (SIP) keyboard. . . . . . . . . . . . . . . . . . A-13 Menus and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-13 HART Application Startup. . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Section 1 Introduction USING THIS MANUAL The sections in this manual provide information on installing, operating, and maintaining devices from the Rosemount 3051N Smart Pressure Transmitter Family. The sections are organized as follows: Section 2: Transmitter Functions Provides instruction on commissioning and operating Rosemount 3051N Pressure Transmitters.
Rosemount 3051N 1-2 Reference Manual 00809-0100-4808, Rev CA June 2008
Reference Manual 00809-0100-4808, Rev CA June 2008 Section 2 Rosemount 3051N Transmitter Functions Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 Failure Mode Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-2 Review Configuration Data . . . . . . . . . . . . . . . . . . . . . . . . page 2-7 Check Output . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Electrical shock can result in death or serious injury. • FAILURE MODE ALARM Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock. Rosemount 3051N transmitters automatically and continuously perform self-diagnostic routines. If the self-diagnostic routines detect a failure, the transmitter drives its output outside of the normal saturation values.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N 1. Security Jumper: prevents all writes to transmitter configuration. 2. Local Keys (Local Zero and Span) Software Lock Out: prevents changes to transmitter range points via local zero and span adjustment keys. With local keys security enabled, changes to configuration are possible via HART. 3.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FIGURE 2-1. Electronics Board. ELECTRONICS BOARD HI LO Alarm OFF ON Security FIGURE 2-2. Rosemount 3051N with Optional LCD Meter. NOTE Security jumper not installed = Not Write Protected. Alarm jumper not installed = High Alarm. COMMISSIONING THE ROSEMOUNT 3051N WITH A HART-BASED COMMUNICATOR 2-4 Commissioning consists of testing the transmitter and verifying transmitter configuration data.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N To commission on the bench, connect the transmitter and the communicator as shown in Figure 2-3. Make sure the instruments in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices before connecting a communicator in an explosive atmosphere. Connect the communicator leads at any termination point in the signal loop.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Wiring Diagrams (Field Hook-up) The following diagrams illustrate wiring loops for a field hook-up with a HART-based Communicator. FIGURE 2-4. Field Hook-up (4–20 mA Transmitters). RL ≥250Ω CAUTION Do not use inductive-based transient protectors. Power Supply Current Meter Signal point may be grounded at any point or left ungrounded.
Reference Manual 00809-0100-4808, Rev CA June 2008 REVIEW CONFIGURATION DATA HART Comm 1, 5 Rosemount 3051N NOTE Information and procedures in this section that make use of HART Communicator fast key sequences assume that the transmitter and communicator are connected, powered, and operating correctly. If you are not familiar with the HART Communicator or fast-key sequences, refer to Appendix A: HART Communicator.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N NOTE Regardless of the range points, the Rosemount 3051N will measure and report all readings within the digital limits of the sensor. For example, if the 4 and 20 mA points are set to 0 and 10 in H2O on a range code 1 Rosemount 3051N, and the transmitter detects a pressure of 25 inH2O, it digitally outputs the 25 inH2O reading and a 250% of span reading. However, there may be up to ±5.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FIGURE 2-5. Square Root Output Transition Point. Sq. Root Curve Transition Point Full Scale Output (mA dc) Full Scale Flow (%) Linear Section Sq. Root Curve Transition Point Slope=42 Slope=1 Rerange The Range Values command sets the 4 and 20 mA points (lower and upper range values). Setting the range values to the limits of expected readings maximizes transmitter performance.
Reference Manual Rosemount 3051N 00809-0100-4808, Rev CA June 2008 NOTE If the transmitter security jumper is in the ON position, you will not be able to make adjustments to the zero and span. Refer to Figure 2-1 for the appropriate placement of the transmitter security jumper. Rerange with a Pressure Input Source and a Communicator HART Comm. 1, 2, 3, 1, 2 Reranging using the communicator and a pressure source or process pressure is a way of reranging the transmitter with a pressure input.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N To rerange the transmitter using the span and zero buttons, perform the following procedure: 1. Loosen the screw holding the label on top of the transmitter housing, and rotate the label to expose the zero and span buttons (see Figure 2-6). 2. Using a pressure source with an accuracy three to ten times the desired calibrated accuracy, apply a pressure equivalent to the lower range value to the high side of the transmitter. 3.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Damping HART Comm. 1, 3, 6 LCD Meter Options HART Comm. 1, 4, 3, 4 The process variable (PV) Damp command changes the response time of the transmitter to smooth variations in output readings caused by rapid changes in input. Determine the appropriate damping setting based on the necessary response time, signal stability, and other requirements of the of loop dynamics of your system. The default damping value is 0.
Reference Manual 00809-0100-4808, Rev CA June 2008 Transmitter Test HART Comm. 1, 2, 1, 1 Loop Test HART Comm. 1, 2, 2 Rosemount 3051N The transmitter Self Test command initiates a more extensive diagnostics routine than that performed continuously by the transmitter. The transmitter test routine can quickly identify potential electronics problems. If the transmitter test detects a problem, messages to indicate the source of the problem are displayed on the communicator screen.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Smart transmitters operate differently than analog transmitters. A smart transmitter uses a microprocessor and sensor memory that contains information about the sensor’s specific characteristics in response to pressure and temperature inputs. A smart transmitter compensates for these sensor variations. The process of generating the sensor performance profile is called factory characterization.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Calibration Overview Complete calibration of the Rosemount 3051N Pressure Transmitter involves the following tasks: Configure the Analog Output Parameters • Set Process Variable Units (page 2-8) • Set Output Type – Linear or Square Root (page 2-8) • Set the Range Points (page 2-9) • Set Damping (page 2-12) Calibrate the Sensor • Full Trim (page 2-18) • Zero Trim (page 2-17) Calibrate the 4–20 mA Output (Digital-to-Analog [D/A]
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FIGURE 2-7. Transmitter Data Flow with Calibration Options. Transmitter Ranged 0 to 100 inH2O Transmitter Electronics Module Input Pressure Input Device 20.00 mA Analog Output Sensor HART Communicator Microprocessor Digital PV Sensor Signal Output Device 3051:PT-4001 Online 1 ➡ Device Setup 2 PV 100.00 inH2O 3 AO 20.00 mA 4 LRV 0.00 inH2O 5 URV 100.00 inH2O NOTE Value on PV line should equal the input pressure.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N When performing a zero trim, ensure that the equalizing valve is open and all wet legs are filled to the correct levels. NOTE Do not perform a zero trim on Rosemount 3051N Absolute pressure transmitters. A zero trim is zero-based, and absolute pressure transmitters reference absolute zero. To correct mounting position effects on a Rosemount 3051N Absolute Pressure Transmitter, perform a low trim within the full sensor trim function.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Full Trim HART Comm. 1, 2, 3, 3 To calibrate the sensor with a HART Communicator using the full trim function, perform the following procedure: 1. Assemble and power the entire calibration system including a transmitter, HART Communicator, power supply, pressure input source, and readout device (see Figure 2-9).
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Recall Factory Trim The Recall Factory Trim commands allow the restoration of the as-shipped factory settings of the sensor trim and analog output trim. Recall Factory Trim— Sensor Trim Resets the transmitter sensor trim to the as-shipped factory settings. The Recall Factory Trim—Sensor Trim command can be useful for recovering from an inadvertent zero trim of an absolute pressure unit. HART Comm.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N NOTE Use a precision resistor for optimum accuracy. If you add a resistor to the loop, ensure that the power supply is sufficient to power the transmitter to a 20 mA output with the additional loop resistance.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N HTc = URV + S (URV) Ps Where: HTc = Corrected High Trim Value URV = Upper Range Value S= –(Span shift per specification) Ps = Static Line Pressure URV = 1500 inH2O LRV = 500 inH2O In this example: Ps = 1200 psi S= -(-0.01/1000 psi) = 0.01/1000psi To calculate the corrected low trim (LTc) value: LTc = 500 in H20 + (0.
Reference Manual Rosemount 3051N 2-22 00809-0100-4808, Rev CA June 2008
Reference Manual 00809-0100-4808, Rev CA June 2008 Section 3 Rosemount 3051N Installation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-4 Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . page 3-4 Electrical Considerations . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Replacement equipment or spare parts not approved by Rosemount Nuclear Instruments, Inc. for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous or adversely impact its qualification status. • Use only components supplied with the Rosemount 3051N or sold by Rosemount Nuclear Instruments Inc. as spare parts for the Rosemount 3051N.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FIGURE 3-1. Typical Installation Flowchart.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N GENERAL CONSIDERATIONS Measurement accuracy depends upon proper installation of the transmitter and impulse piping. Mount the transmitter close to the process and use a minimum of piping to achieve best accuracy. Keep in mind the need for easy access, personnel safety, practical field calibration, and a suitable transmitter environment. Install the transmitter to minimize vibration, shock, and temperature fluctuation.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N NOTE For steam service, do not blow down impulse piping through the transmitter. Flush the lines with the blocking valves closed and refill the lines with water before resuming measurement. NOTE When the transmitter is mounted on its side, position the Coplanar process flange to ensure proper venting or draining. Keep drain/vent connections on the bottom for gas service and on the top for liquid service.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FIGURE 3-3. Rosemount 3051N Coplanar Flange Dimensional Drawing (Differential Pressure Transmitter Shown) 5 (127) 1 Meter Cover (optional) /2-14 NPT Conduit Connection (two places) 4.3 (110) Label 4.1 (105) 0.75 (20) Clearance for Cover Removal 0.75 (20) Clearance for Cover Removal Terminal Connections Transmitter circuitry 7.1 (181) Nameplate Housing Rotation Set Screw Drain/vent Valve 6.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FIGURE 3-4. Traditional Flange Mounting Configurations with Optional Brackets for Panel Mounting OPTION CODE B2: TRADITIONAL FLANGE PANEL MOUNTING BRACKET (PAINTED CARBON STEEL) OPTION CODE BS: TRADITIONAL FLANGE UNIVERSAL PANEL MOUNTING BRACKET (STAINLESS STEEL) 9.5 (241) 9.4 (239) 2.63 (66.8) 2.75 (69.9) Nameplate Nameplate 6.3 (181) 4.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FIGURE 3-5. Traditional Flange (Option Code H2) Dimensional Drawing 5 (127) 1 /2-14 NPT Conduit Connection (Two Places) 4.3 (110) 0.75 (20) Clearance for Cover Removal 0.75 (20) Clearance for Cover Removal Terminal connections Transmitter Circuitry Meter Cover (optional) Center of gravity (aluminum housing without meter) Nameplate 1.36 (35) 1.63 (41.4) 2.13 (54.1) 1 /4-18 NPT on Traditional Flange for Process Connection 1.
Reference Manual 00809-0100-4808, Rev CA June 2008 Mounting Rosemount 3051N The Rosemount 3051N Pressure Transmitter weighs approximately 6.0 lb (2,7 kg) without additional options. For complete weight information, including options, see “Physical Specifications” in Section 5. Optional mounting brackets available with the Rosemount 3051N allow mounting to a panel or wall. The B4 Bracket Option for use with the Coplanar flange is 316 SST and provided with 316 SST bolts.
Reference Manual Rosemount 3051N 00809-0100-4808, Rev CA June 2008 NOTE In steam or other elevated temperature services, it is important that temperatures at the coplanar process flanges not exceed 250 °F (121 °C). In vacuum service, these temperature limits are reduced to 220 °F (104 °C).
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FIGURE 3-6. Typical Installation Examples to Illustrate Transmitter and Impulse Piping Locations. GAS OR LIQUID SERVICE GAS SERVICE STEAM SERVICE Flow Flow Flow Impulse Piping The piping between the process and the transmitter must accurately transfer the pressure to obtain accurate measurements.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Process Connections Rosemount 3051N connections on the transmitter flange are 1/4–18 NPT. Use your plant-approved lubricant or sealant when making the connections. The end-user is responsible for the qualification of the threaded seal interface on the transmitter’s 1/4-18 NPT connections. Do not attempt to loosen or remove the flange bolts while the transmitter is in service.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FIGURE 3-7. Power Supply Load Limitations. Max. Loop Resistance = 43.5 (Power Supply Voltage – 10.5) ohms Load (ohms) 1935 1500 1000 Design Region 500 0 10.5 20 30 40 Voltage (V dc) 55 Communication requires a minimum loop resistance of 250 ohms. Wiring To make connections, perform the following procedure: 1. Remove the housing cover on the side marked “FIELD TERMINALS.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Grounding the Transmitter Case The transmitter case should always be grounded in accordance with national and local electrical codes. The most effective transmitter case grounding method is direct connection to earth ground with minimal impedance. Methods for grounding the transmitter case include: • Internal Ground Connection: The Internal Ground Connection screw is inside the FIELD TERMINALS side of the electronics housing.
Reference Manual 00809-0100-4808, Rev CA June 2008 Section 4 Rosemount 3051N Troubleshooting Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Returning Rosemount Products and Materials . . . . . . . .
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Table 4-1. Rosemount 3051N Troubleshooting Chart. Symptom Milliamp Reading Is Zero Transmitter Not Communicating with HART Communicator Milliamp Reading Is Low or High No Response to Changes in Applied Pressure Pressure Variable Reading Is Low or High Pressure Variable Reading Is Erratic Corrective Actions • • • • • • • • • • • • • • • • • • • • • Check if power polarity is reversed.
Reference Manual 00809-0100-4808, Rev CA June 2008 Section 5 Rosemount 3051N Specifications and Reference Data Nuclear Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1 Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . page 5-3 Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . page 5-5 Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-8 Materials of Construction . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Environmental Performance to normal operating limits as described in the “Performance Specifications” and “Functional Specifications” sections of this manual.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N PERFORMANCE SPECIFICATIONS Based upon zero-based calibrations, reference conditions, 4–20mA analog output, and digital trim values equal to the span setpoints Reference Accuracy Includes hysteresis, terminal-based linearity, and repeatability(1) Rosemount 3051ND Range Code 0 1 2–5 Reference Accuracy ± 0.10% calibrated span from 1:1 to 2:1 RDF ± 0.05% upper range limit from 2:1 to 30:1 RDF ± 0.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Overpressure Effect Maximum zero shift after overpressure equal to Maximum Working Pressure Rosemount 3051ND Range Code 0–3 4–5 Overpressure Effect ± 0.5% URL ± 3.0% URL Rosemount 3051NG Range Code 2–4 5 Overpressure Effect ± 0.25% URL ± 0.30% URL Rosemount 3051NA Range Code 0–4 Static Pressure Effect Overpressure Effect ± 0.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FUNCTIONAL SPECIFICATIONS Service Liquid, gas, or vapor Output 4–20 mA, user-selectable for linear or square root output; digital signal based on HART® protocol Power Supply Load Limitations Maximum loop resistance is determined by the voltage level of the external power supply, as described by: Max. Loop Resistance = 43.5 (Power Supply Voltage – 10.5) ohms Load (ohms) 1935 1500 1000 Design Region 500 0 10.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Span and Zero, Zero Elevation, and Suppression Zero and span values can be set anywhere within the range limits stated in Table 5-2 and Table 5-3, providing sensor limits are not exceeded. Span must be greater than or equal to the minimum span stated in Table 5-2 and Table 5-3. Table 5-2.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Figure 5-1. Typical Smart Transmitter Response Time Transmitter 4–20 mA Output vs. Time Pressure Released Td Tc Td = Dead Time Tc = Time Constant 20mA Response Time = Td +Tc 9.89mA 63.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N PHYSICAL SPECIFICATIONS MATERIALS OF CONSTRUCTION Isolating Diaphragms 316L SST Drain/Vent Valves 316 SST Process Flanges CF-8M (cast version of 316 SST) Process O-rings Glass-filled TFE, Ethylene propylene (optional) Fill Fluid Silicone oil Flange Bolts Plated carbon steel, per ASTM A449, Type 1 (austenitic 316 SST per ASTM F593 for Rosemount 3051N Range Code 0) Electronics Housing Low-copper aluminum with polyester-polyurethane paint, or
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Option Code J H2 M5 M6 B2 B4 BS PM Description Add: Stainless Steel Housing Traditional Flange LCD Meter for Aluminum Housing LCD Meter for SST Housing Carbon Steel Panel Mounting Bracket for Traditional Flange SST Mounting Bracket for Coplanar Flange Universal SST Panel Bracket for Traditional Flange 2 inch pipe mount assembly for Traditional Flange 3.1 lb (1.4 kg) 2.4 lb (1.1 kg) 0.5 lb (0.2 kg) 1.25 lb (0.6 kg) 2.3 lb (1.0 kg) 1.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N ORDERING INFORMATION Rosemount 3051N(1) Differential, Gage, and Absolute Pressure Transmitters — = Not Applicable • = Applicable (1) Rosemount Transmitter Type (Select One) 3051ND 3051NG 3051NA Differential Pressure Transmitter Gage Pressure Transmitter Absolute Pressure Transmitter ND • — — NG — • — NA — — • Pressure Ranges (RANGE/MIN.
Reference Manual 00809-0100-4808, Rev CA June 2008 Code A J Code H2 Code B2 B4 BS PM Code M5 M6 Rosemount 3051N Housing Material Conduit Entry Size Polyurethane-covered Aluminum SST ½–14 NPT ½–14 NPT • • • • • • • • • • • • • • • • • • • • • • • • • • • Alternate Flange Options (Requires Materials of Construction Code 0) Traditional Flange, 316 SST, SST Drain/Vent, SST Flange Adapter Mounting Bracket Options Traditional Flange Bracket for Panel Mounting, CS Bolts Coplanar Flange Bracket fo
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N ROSEMOUNT 3051N 4-20 MA/HART OUTPUT SMART PRESSURE TRANSMITTERS TYPICAL CONFIGURATION DATA WORKSHEET CONFIGURATION DATA SHEET Software Tag: |__|__|__|__|__|__|__|__| OUTPUT INFORMATION: (Software Selectable) 4 mA = ____________ 0★ 20 mA = ____________ Upper Range Limit ★ Pressure Units = inH2O★(2) psi★(3) Pa inHg bar kPa mbar Torr mmH2O Atm kg/cm2 mmHg Output = (4) Damping = Key to Symbols ★ = Typical Factory Def
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N HARDWARE SELECTABLE INFORMATION Alarm Option: High★ Low Transmitter Security: Off★ On SIGNAL SELECTION: (Software Selectable) 4–20 mA with simultaneous digital signal based on HART protocol★ Note: This is the only signal selection that has been evaluated for use in safety related applications.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Figure 5-2. Rosemount 3051N Exploded View (with Coplanar Process Flange).
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N 5-15
Reference Manual Rosemount 3051N 5-16 00809-0100-4808, Rev CA June 2008
Reference Manual 00809-0100-4808, Rev CA June 2008 Section 6 Rosemount 3051N Options Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-1 LCD Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-1 Mounting Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-7 Transient Protection Terminal Block (T1) . . . . . .
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N The meter features a two-line display with five digits for reporting the process variable on the top line and six characters for displaying engineering units on the bottom line. The LCD meter can also display flow and level scales. The meter uses both lines to display diagnostic messages.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N a. Select 5 CM xfer fnct. Enter the transmitter transfer function for the meter. Select sq root to display flow units. The custom meter transfer function is independent of the analog output transfer function. 8. Select SEND (F2) to upload the configuration to the transmitter. FIGURE 6-1. Exploded View of the Rosemount 3051N with Optional LCD Meter.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N 4. Insert the interconnection header in the ten-pin socket exposed by removal of the jumpers. 5. Remove the two captive screws from the electronics module. To do so, loosen the screws to release the module, then pull out the screws until they are stopped by the captive thread inside of the circuit board standoffs. Continue loosening the screws and remove them. 6.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FIGURE 6-2. Rosemount 3051N with Optional LCD Meter. Diagnostic Messages In addition to the output, the LCD meter displays abbreviated operation, error, and warning messages for troubleshooting the transmitter. Messages appear according to their priority, with normal operating messages appearing last. To determine the cause of a message, use a HART Communicator to further interrogate the transmitter.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Some non-volatile memory faults are user-addressable. Use a HART Communicator to diagnose the error and determine if it is repairable. Any error message that ends in “FACTORY” is not repairable. In cases of non user-addressable errors, you must replace the transmitter. Contact Rosemount Nuclear Instruments Inc. at (952) 949-5210 if you need assistance. FAIL ELECT The transmitter electronics board is malfunctioning due to an internal fault.
Reference Manual 00809-0100-4808, Rev CA June 2008 Operation Rosemount 3051N Normal operation messages appear on the LCD meter to confirm actions or inform you of transmitter status. Operation messages are displayed with other transmitter information, and warrant no action to correct or alter the transmitter settings. ZERO PASS The zero value, set with the local zero adjustment button, has been accepted by the transmitter, and the output should change to 4 mA.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Option PM is a SST pipe mount bracket assembly designed for use in pipe mounting the Traditional Flange (H2). It is the same bracket used on other RNII nuclear qualified transmitters, including the Rosemount 1154 Series H. When installing the transmitter to the optional mounting brackets, torque the bolts to 21 foot-pounds. See “Mounting” in Section 3 for additional mounting considerations.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FIGURE 6-4. Transient Protection Terminal Block (T1).
Reference Manual Rosemount 3051N 6-10 00809-0100-4808, Rev CA June 2008
Reference Manual 00809-0100-4808, Rev CA June 2008 Appendix A Rosemount 3051N HART Communicator Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-1 Connections and Hardware . . . . . . . . . . . . . . . . . . . . . . . . page A-5 Rosemount 275 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-7 Menus and Functions . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Warnings Explosions can result in death or serious injury. • Do not remove the transmitter covers in explosive environments when the circuit is alive. • Before connecting a communicator in an explosive atmosphere, make sure the instruments in the loop are installed according to intrinsically safe or nonincendive field wiring practices.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FIGURE A-1. HART Communicator Typical Abbreviated Menu Tree for Rosemount 3051.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Table A-1. Typical HART Fast Key Sequences for the Rosemount 3051 (partial listing).
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N CONNECTIONS AND HARDWARE The HART Communicator can interface with a transmitter from the control room, the instrument site, or any wiring termination point in the loop through the communicator connections as shown in Figure A-2 and Figure A-3. To communicate, connect the HART Communicator in parallel with the instrument or load resistor. The connections are non-polarized.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N FIGURE A-4. Bench Hook-up (4–20 mA Transmitters). 24 V dc Supply Current Meter FIGURE A-5. Field Hook-up (4–20 mA Transmitters). RL ≥ 250Ω CAUTION: Do not use inductive-based transient protectors. RL ≥ 250Ω Power Supply Current Meter Signal point may be grounded at any point or left ungrounded.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N ROSEMOUNT 275 Communicator Keys The keys of the Rosemount 275 HART Communicator include action, function, alphanumeric, and shift keys. FIGURE A-6. Rosemount 275 HART Communicator. Function Keys Action Keys Alphanumeric Keys Shift Keys Action Keys As shown in Figure A-6, the action keys are the six blue, white, and black keys located above the alphanumeric keys.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Hot Key Use this key to quickly access important, user-selectable options when connected to a HART-compatible device. Pressing the HOT KEY turns the HART Communicator on and displays the Hot Key Menu. See “Customizing the Hot Key Menu” in the Rosemount 275 HART Communicator manual for more information. Function Keys Use the four software-defined function keys, located below the LCD, to perform software functions.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Fast Key Sequences HART fast key sequences provide quick on-line access to most transmitter variables and functions. Instead of stepping your way through the menu structure using the action keys, you can press a HART fast key sequence to move from the ONLINE MENU to the desired variable or function. On-screen instructions guide you through the rest of the screens.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N NOTE Online communication with the transmitter automatically loads the current transmitter data to the HART Communicator. Changes in on-line data are made active by pressing SEND (F2). The transfer function is used only for off-line data retrieval and sending. • Frequency Device–The Frequency Device option displays the frequency output and corresponding pressure output of current-to-pressure transmitters.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N ROSEMOUNT 375 Communicator Keys FIGURE A-9. Rosemount 375 HART Communicator. The keys of the Rosemount 375 HART Communicator include navigation, function, alphanumeric, and tab keys. The keypad and touch screen have nearly total function redundancy.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Enter Key The enter ( ) key allows you to launch the focused item or to complete an editing action. It does not navigate you through a menu structure. For example, if you have the Cancel button in focus (highlighted) when you push the enter key, you will be choosing to cancel out of that particular window. Tab Key The tab ( Alphanumeric Keys ) key allows you to move between selectable controls.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N The touch screen should be contacted by blunt items only, preferably the stylus included with the Rosemount 375 Field Communicator. The use of sharp instruments, such as screwdrivers, can cause failure of the touch screen interface. Repair of the touch screen requires replacement of the entire Rosemount 375 Field Communicator display assembly, which is possible only at an authorized service center.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Fast Key Sequences The Fast Key sequence is a sequence of numerical button presses, corresponding to the menu options that lead you to a given task. Use Table A-1, an alphabetical listing of most on-line functions, to find the corresponding HART fast key sequences. These codes are applicable only to Rosemount 3051N transmitters and the HART Communicator.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Message Description Add item for ALL device types or only for this ONE device type. Asks the user whether the hot key item being added should be added for all device types or only for the type of device that is connected. Command Not Implemented The connected device does not support this function. Communication Error The communicator and the device are not communicating correctly.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N A-16 Message Description Looking for a device Polling for multidropped devices at addresses 1–15. Local buttons operator error ON Illegal pressure applied during zero or span operation. Repeat the process after verifying the correct pressures. Mark as read only variable on hotkey menu? Asks whether the user should be allowed to edit the variable from the hotkey menu if the item being added to the hotkey menu is a variable.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Message Description ROM checksum error ON Checksum of transmitter software has detected a fault. Return to Rosemount Nuclear Instruments, Inc. for repair. Save data from device to configuration memory Prompts user to press SAVE softkey to initiate a device-to-memory transfer. Saving data to configuration memory. Data is being transferred from a device to configuration memory. Sending data to device.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N A-18 Message Description Value out of range The user-entered value is either not within the range for the given type and size of variable or not within the min/max specified by the device.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Glossary Analog Output Trim Digital Trim operation that allows adjustment of the output electronics to conform to the plant standard. Three types of analog output trim are available: 4–20 mA Trim, 4–20 mA Other Scale, and Low Power. See “Analog Output Trim” in Section 2 . Low Power is not approved for use with the Rosemount 3051N.
Reference Manual Rosemount 3051N 00809-0100-4808, Rev CA June 2008 Lower Range Value (LRV) Lowest value of the measured variable that the analog output of the transmitter is currently configured to measure. Multidropping The connection of several transmitters to a single communications transmission line. Communication between the host and the transmitters takes place digitally with the analog output of the transmitters deactivated.
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N Index A Access Requirements . . . . Alarm and Security Jumper Configuration Procedure . . Alarm Level Verification . . Analog Output Trim . . . . . L E . . 3-14 . . . 2-3 . . . 2-2 . . 2-19 B Basic Setup . . . . . . . . . . . . . . 2-8 Bolts Flange . . . . . . . . . . . . . . 5-8 C Calibration . . . . . . . . . . . . . . 2-13 Overview . . . . . . . . . . . 2-15 Procedure to Use . . . . . 2-16 Sensor Trim . . . . . . . . . .
Reference Manual Rosemount 3051N S Security . . . . . . . . . . . . . . . . 2-2 Local Zero and Span Physical Removal . . . . . . 2-3 Local Zero and Span Software Lock Out . . . . . . 2-3 Write Protect . . . . . . . . . . 2-3 Security and Alarm Jumper Configuration Procedure . . . . . 2-3 Sensor Temperature . . . . . . . 2-8 Sensor Trim . . . . . . . . . . . . 2-16 Setup . . . . . . . . . . . . . . . . . . 2-8 Basic . . . . . . . . . . . . . . . 2-8 Detailed . . . . . . . . . . . .
Reference Manual 00809-0100-4808, Rev CA June 2008 Rosemount 3051N The Emerson logo is a trade mark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. PlantWeb is a mark of one of the Emerson Process Management companies. HART is a registered trademark of the HART Communications Foundation. All other marks are the property of their respective owners.