Specifications
SAG582136600 System Application Guide
Issue W, January 12, 2015 Spec. No. 582136600 (Model 211
NGFB)
Page 18 of 109
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
List 60: Five (5) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions
Features
♦ Provides 12’ long, 16 AWG, load and load return leads that are terminated
on one end with the appropriate mating connector to plug into the system’s
10A GMT fuse connector on a List BC, LC, NC, BA, LA, or NA Distribution
Unit, and are left un-terminated at the remaining end for connection into
customer loads.
Restrictions
For use with List BC, LC, NC, BA, LA, and NA Distribution units only.
Ordering Notes
1) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA Distribution Unit.
Each List 60 provides five (5) GMT fuse load lead assemblies, P/N 535206.
List 61: Eight (8) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse
Positions
Features
♦ Provides 12’ long, 16 AWG, load and load return leads that are terminated on
one end with the appropriate mating connector to plug into the system’s 10A
GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left un-
terminated at the remaining end for connection into customer loads.
Restrictions
For use with List BF, LF, and NF Distribution units only.
Ordering Notes
1) Order one (1) List 61 for each List BF, LF, or NF Distribution Unit.
Each List 61 provides eight (8) GMT fuse load lead assemblies, P/N 535206.
List 62: Five (5) Load Lead Assemblies (P/N 540988) for 15A GMT Fuse Positions
Features
♦ Provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the
appropriate mating connector to plug into the system’s 15A GMT fuse connector
on a List BF, LF, or NF Distribution Unit, and are left un-terminated at the
remaining end for connection into customer loads.
Restrictions
For use with List BF, LF, and NF Distribution units only.
Ordering Notes
1) Order one (1) List 62 for each List BF, LF, or NF Distribution Unit.
Each List 62 provides five (5) GMT fuse load lead assemblies, P/N 540988.
List 65: Shelf Side Battery Cables, P/N 540814
Features
♦ Provides two (2) 3’ long, 2 AWG, battery cables terminated in a 2-position Red
SB120 Anderson connector (mates with the Anderson connector on List 66).
Remaining end terminated in lugs for connection to shelf.
Restrictions
For use with List BF, LF, NF, BC, LC, and NC Distribution units only.
Ordering Notes
1) Order as required. Each shelf provides landings for up to three (3) battery strings.