Specifications
SAG582136600 System Application Guide
Issue W, January 12, 2015 Spec. No. 582136600 (Model 211
NGFB)
Page 56 of 109
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
AC Input Line Cord, 120/208/240VAC, P/N 548196
Features
♦ Provides one (1) 6’ long, 12/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input
receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with an IEC320 C20 plug.
Restrictions
For 120/208/240 VAC (rated for 20A at 120/208/240VAC).
For 208/240V use with List 1, 2, 5, and 6 and all Rectifier Modules.
For 120V use with List 1 and 5 and all Rectifier Modules.
For 120V use with List 2 and 6 with 500W Rectifier Module only.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Per UL 60950-1, 2nd Edition, when this cord is used with this power system, the following restrictions apply:
• The power system must be used “in a location having equipotential bonding (such as a
telecommunications centre, a dedicated computer room or a restricted access location).
• “The building installation shall provide a means for connection to protective earth; and
• “The equipment is to be connected to that means; and
• “A service person shall check whether or not the socket-outlet from which the equipment is to be powered
provides a connection to the building protective earth. If not, the service person shall arrange for the
installation of a protective earthing conductor from the separated protective earthing terminal to the
protective earth wire in the building.”
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.