AC Power For Business-Critical Continuity™ Liebert® PSI XR™ User Manual–1000/1500/2200/3000, 120VAC
TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 2.0 WHAT’S INCLUDED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.0 COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 6.1 DB-9 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 6.2 Remote Shutdown Via the DB-9 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 6.2.1 6.2.2 Any Mode Shutdown Via Pins 5 & 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the UPS. • Intended for installation in a temperature-controlled, indoor area free of conductive contaminants. • Maximum ambient temperature 104°F (40°C). Read this manual thoroughly before attempting to install or operate this UPS. The equipment can be installed and operated by individuals without previous training.
CONDITIONS OF USE—The input supply outlet must be within 6 ft. (1.8m) of the UPS and be easily accessed. This UPS provides conditioned power to connected equipment. It is not intended for use with life-support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. If uncertain, consult your local dealer, local Emerson Network Power representative or Channel Support Applications.
GLOSSARY OF SYMBOLS Risk of electrical shock ! Indicates caution followed by important instructions Indicates the unit contains a valve-regulated, lead-acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON/Alarm Silence/Manual Self-Diagnostic Test OFF Status Change Button 3
Introduction 1.0 INTRODUCTION The Liebert PSI™ XR is a 2U, line-interactive UPS that may be installed in a rack or used as a tower UPS. Status indicators on the front of the Liebert PSI XR display load level, battery level, buck/boost, sitewiring fault, overload, battery status and UPS operation. Controls include a combination On/Alarm Silence/Manual Self-Diagnostic Test button, an Off button and a Status Change button. The Liebert PSI XR has USB, DB-9 (contact closure) and Liebert IntelliSlot® ports.
Introduction Figure 3 2200—rear view 15A Output Circuit Breaker for Receptacles #3 & #4 Power Cord; 5-20P (not shown for clarity) DB-9 Port (Contact Closure) Liebert IntelliSlot Port Receptacles #3 and #4 NEMA 5-15R Receptacles #1 and #2; NEMA 5-20R T-Slot 30A Input Circuit Breaker Receptacles #5 and #6 NEMA 5-15R INPUT EPO FUNCTION VOLTAGE=110V VOLTAGE=120V VOLTAGE=127V 2 1 OUTPUT DC 48V EPO External Battery Cabinet Connector USB Port Voltage Configuration DIP Switch Figure 4 Network Surg
What’s Included 2.0 WHAT’S INCLUDED The Liebert PSI XR is shipped with the following items: • • • • • • • • • • Figure 5 Multi-Language User Manual on CD Liebert MultiLink Software and User Manual, downloadable at multilink.liebert.com Contact Closure (ML9P9S) Cable USB Cable Tower Stands Mounting Hardware Rack-Mount Handles Fixed Mounting Rails EPO Connector Battery-UPS Tab Accessories Tower Stands Contact Closure (ML9P9S) Cable 6 ft (1.8m) USB cable 6 ft (1.
Installation 3.0 INSTALLATION 3.1 Preparation ! CAUTION The UPS and battery cabinets are heavy (see Table 6 and Table 7). Take proper precautions when lifting or moving either the UPS or battery cabinets. The Liebert PSI XR may be installed in either a tower or rack configuration. Determine the method that suits the application and proceed. Decide where to install the Liebert PSI XR. The UPS must be installed indoors in a controlled environment.
Installation 3.2 Tower UPS Installation See Figure 7 when using the Liebert PSI XR in a tower configuration.
Installation 3.3 Rack-Mount UPS Conversion and Installation See Figure 8 when installing the Liebert PSI XR in a rack. External battery cabinets are installed in same manner. Figure 8 Convert the Liebert PSI XR for rack installation Step 1 Step 2 Load Level Battery Level Load Level Battery Level Step 4 Step 3 Load Level Battery Level Step 5 Load Level Battery Level ! WARNING Placing heavy equipment near the top of a rack may increase the risk of tipping.
Installation 3.4 Orient Display for Installation The Liebert PSI XR features a rotating display that may be oriented for either tower or rack installations. To set the display for your installation, pull out on the display and rotate it until it is oriented correctly, then press it into the UPS until it is seated. Figure 9 3.
Installation 3.7 Connect Network Surge protection Connect a 10 base-T/100 network cable to the network surge protection IN jack on the rear of the UPS. Connect from the OUT jack with network cabling to network equipment (see Figure 11). Figure 11 Connect network surge protection Network Equipment INPUT OUTPUT EPO FUNCTION 2 1 VOLTAGE=110V VOLTAGE=120V VOLTAGE=127V DC 24V Network surge protection OUT jack 3.
Installation 3.9 Set Up Liebert MultiLink software To start using Liebert MultiLink (software and user manual available at multilink.liebert.com): • Install the software. See the Liebert MultiLink quick-start guide or user manual for installation instructions. • Connect one end of the USB cable (supplied) to the USB port on the rear of the UPS. Connect the other end to a USB port on the computer. See the Liebert MultiLink user manual for operating instructions.
Installation 3.11 External Battery Cabinet Installation Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS. The batteries have a maximum run time of three hours at full load. 1. Install the external battery cabinet in tower- or rack-configuration (see Figure 14 or 3.3 - RackMount UPS Conversion and Installation). 2.
Installation Figure 15 Connect battery cabinets to UPS INPUT OUTPUT EPO FUNCTION VOLTAGE=110V VOLTAGE=120V VOLTAGE=127V 2 1 DC 24V See Table 8 for approximate battery run times.
Controls and Indicators 4.0 CONTROLS AND INDICATORS Buttons on the front panel display control the Liebert PSI XR. Eight LEDs indicate the UPS’s status. Refer to Figure 16 and Table 2.
Controls and Indicators 4.1 Control Buttons 4.1.1 On/Alarm Silence/Manual Self-Diagnostic Test This button controls output power to connected load(s). It has three functions: • On • Alarm Silence • Manual Self-Diagnostic Test ON—Start the UPS by pressing this button for more than 3 seconds, then releasing the button (an alarm will sound briefly). If the ON button is pressed and utility is outside input parameters, the UPS will start on battery (dark start).
Controls and Indicators 4.2.3 Battery Level Indicator The five LEDs illuminate with a steady glow to indicate battery capacity. Battery capacity is shown for five seconds after the Status Change button is pressed. The LEDs show the battery capacity as a range, ± 5% The LEDs’ battery level meanings and colors are: 4.2.
Operational Modes 5.0 OPERATIONAL MODES 5.1 Normal Mode When the UPS is in Normal Mode, the Normal Mode Indicator illuminates green. 5.2 Buck/Boost Mode The Automatic Voltage Regulator (AVR) circuitry compensates for fluctuations in utility power, such as voltage surges and sags. When the Liebert PSI XR detects an abnormality, it raises the undervoltage (boost) or lowers the overvoltage (buck) as needed.
Communication 6.0 COMMUNICATION 6.1 DB-9 Connector The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a computer running Liebert MultiLink software in contact closure mode. The connection provides On Battery and Low Battery notification. When power is interrupted and battery power is low, Liebert MultiLink software can signal the host computer to gracefully shut down the operating system.
Communication 6.4 UPS Communications The Liebert PSI XR is equipped with a Liebert IntelliSlot port to provide advanced communication and monitoring options. Liebert MultiLink software continually monitors the UPS and can shut down your computer or server via USB, contact closure and SNMP (via IS-WEBRT3 card) in the event of an extended power failure. The Liebert IS-WEBRT3 provides SNMP and Web-based monitoring and control of the UPS across the network.
Battery Maintenance 7.0 BATTERY MAINTENANCE 7.1 Battery Charging, Storage The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design life. The Liebert PSI XR continuously charges the batteries when connected to the utility supply, even while the UPS is switched Off. If the Liebert PSI XR will be stored for an extended period, Emerson recommends connecting the UPS to input power for at least 8 hours every four to six months to keep the batteries charged.
Specifications 8.0 Table 6 SPECIFICATIONS Liebert PSI XR specifications PS1000RT3-120XR PS1500RT3-120XR PS2200RT3-120XR PS3000RT3-120XR PS1000RT3120XRW PS1500RT3120XRW PS2200RT3120XRW PS3000RT3120XRW 3000VA/2700W Power Rating, VA/W 1000VA/900W 1500VA/1350W 1920VA/1920W* Dimensions, W x D x H, in (mm) Unit 17.3 x 19.3 x 3.5 (440 x 490.5 x 88) 17.3 x 27.6 x 3.5 (440 x 700.5 x 88) Shipping 22 x 24.1 x 9 (560 x 612 x 228) 22 x 34.8 x 9.
Specifications Table 7 Battery cabinet specifications Model Number PSRT3-24VBXR PSRT3-48VBXR Used w/UPS Model PS1000RT3-120XR PS1000RT3120XRW PS1500RT3-120XR PS1500RT3120XRW PS2200RT3-120XR PS2200RT3120XRW PS3000RT3-120XR PS3000RT3120XRW Dimensions, W x D x H, in (mm) Unit 17.3 x 19.3 x 3.5 (440 x 490.5 x 88) Shipping 22 x 26.6 x 9 (560 x 675 x 228) Weight, lb (kg) Unit 64 (29) Shipping 73 (33) Batteries Type Quantity x Voltage x Ah Valve-regulated, nonspillable, lead acid 8 x 12 x 7.
Specifications Table 8 Liebert PSI XR battery run times Number of Batteries Internal Battery Internal battery + 1 External Battery Cabinets Internal battery + 2 External Battery Cabinets Internal battery + 3 External Battery Cabinets Load % 1000 1500 2200 3000 10 83 82 76 75 20 52 48 48 47 30 31 28 28 28 40 18 17 17 17 50 15 13 14 13 60 12 11 11 11 70 11 9 9 9 80 9 7 8 7 90 7 6 7 6 100 6 5 5 5 10 263 222 161 143 20 165 131 101 83 30 12
Specifications Table 8 Liebert PSI XR battery run times (continued) Number of Batteries Internal battery + 4 External Battery Cabinets Internal battery + 5 External Battery Cabinets Internal battery + 6 External Battery Cabinets Load % 1000 1500 2200 3000 10 790 627 483 330 20 494 371 303 204 30 360 264 221 148 40 283 204 174 116 50 233 167 143 95 60 198 141 122 76 70 172 122 106 66 80 152 108 94 59 90 137 96 79 52 100 124 82 72 48 10 965 762 5
Troubleshooting 9.0 TROUBLESHOOTING The information below indicates various symptoms a user may encounter if the Liebert PSI XR experiences a problem. See Table 9 for suggested solutions. 1. An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for low battery, overload warning and fault. 2.
Ensuring The High Availability Of Mission-Critical Data And Applications. Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity.