Specifications

7
To function correctly and read temperature accurately, the thermostat must have constant 24-volt pow-
er. If the thermostat temperature is steadily dropping, reading low, or reads 08° when a remote sensor is
installed, it can be traced to one of the three following conditions.
Condition Test Comments
1. Loss of 24-volt
power.
On models with batteries, remove
the batteries and re-install ther-
mostat. If the display is blank,
check heating and cooling system
to determine why 24-volt power is
absent.
For the sensor to read correctly, the
24-volt system power must be present.
Some systems may require an isolation
relay to provide constant power to the
thermostat. Limit or safety devices in
the equipment can also cause a power
interruption.
2. A broken wire on
S1, S2 and S3 or
(+, SA, -) from the
thermostat to the
remote.
Disconnect sensor wires at ther-
mostat. Attach a short piece (2')
of three-wire shielded cable to
S1, S2 and S3 or (+, SA, -) on the
subbase. Bring the remote sensor
to the thermostat location and
attach S1, S2 and S3 or (+, S, -)
respectively. Reattach thermostat.
If the temperature begins to climb
(slowly), it is reading correctly. If it
reads correctly with the 2' length
but improperly when attached to
the wire run, it indicates a fault in
the wire run.
Repair or replace the 3 wire shielded
cable. Be sure the remote wire run is
not parallel to line voltage wires that
carry heavy inductive loads, or across
uorescent light ballasts that may
cause an inductance to be transmitted
to the thermostat.
3. A shorted or
damaged remote
sensor.
Because it is an electronic sensor,
there are no Ohm values to test. If
correct conditions as listed in 1 & 2
above and the temperature stays at
or near 08°, it indicates a shorted or
damaged remote sensor.
Replace remote sensor.
Note: Digital thermostats and remote sensors acclimate very slowly to temperature change. It may take
an hour or more for the temperature to acclimate to the room temperature from a low temperature
reading as outlined above. To expedite the room temperature display use the reset instructions listed in
the installation instructions for the thermostat model you are working with. When reset, the thermostat
will default to a room temperature of 70° and begin sensing room temperature. Be sure to recongure
the installer menu for a remote sensor because the reset function may cancel remote sensing.
TROUBLESHOOTING