User Guide

26
MAIN MENU
EMR (Energy Management Recovery)
Default is On. With EMR selected On,
the heating or cooling system will start
early so the temperature in your home
is at the desired temperature at the
beginning of the program period. If set
to O, the system will not start until the
beginning of the program period.
Maximum Heat Setpoint Temp.
Default is 99°. Minimum Cool Setpoint
Temp. – Default is 45°. These settings
are the highest temperature limit in
Heat mode or the lowest temperature
limit in Cool mode. Select a setting of
99° to 45° for the maximum heating
temperature or 45° to 99° for the
minimum cooling temperature.
Main Menu
Comfort or Dehum – Default is O.
Selecting either Comfort or Dehum will
automatically reduce indoor humidity
with a call for cooling if humidity is 2%
above the humidity setpoint. If Comfort
is selected, the system will slow the fan
speed (variable speed blowers only) to
increase the dehumidication process
and cool based on the temperature
setpoint. If Dehum is selected, the system makes the dehumidication a
priority over temperature. This setting uses more energy and may over-cool
the space by up to to achieve the desired humidity level. If O is selected
the system will control temperature to the cooling setpoint.