Rosemount 3051S FOUNDATION fieldbus Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series Pressure Transmitter Family with FOUNDATION™ fieldbus Protocol www.rosemount.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Rosemount 3051S Series Pressure Transmitter with FOUNDATION fieldbus Protocol NOTICE Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product. Within the United States, Rosemount Inc.
Reference Manual 00809-0200-4801, Rev BA July 2010 Rosemount 3051S Table of Contents SECTION 1 Introduction Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Service Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Device Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4801, Rev BA July 2010 Rosemount 3051S Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8 Configure the AI block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8 Configuration Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11 Pressure transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11 Pressure transmitter used to measure level in an open tank . . .
Reference Manual 00809-0200-4801, Rev BA July 2010 Rosemount 3051S SECTION 6 Advanced Pressure Diagnostics for FOUNDATION fieldbus Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 Statistical Process Monitoring Technology . . . . . . . . . . . . . . . . . . . . . 6-2 SPM Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4 SPM Configuration and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4801, Rev BA July 2010 Rosemount 3051S Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Range and Sensor Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Minimum Span Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overpressure Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Static Pressure Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Section 1 Introduction OVERVIEW This manual is for the 3051S Series Pressure Transmitter with FOUNDATION fieldbus communications. This transmitter’s scalable architecture allows putting a FOUNDATION fieldbus output board with any performance class 3051S supermodule and any of its process connections.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Service Support To expedite the return process outside of the United States, contact the nearest Emerson Process Management representative. Within the United States, call the Rosemount National Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assist you with any needed information or materials.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure 1-1. Commissioning Tag COMMISSIONING LABEL Device ID Device Tag to denote physical location DEVICE ID: 00115113051032003161928-030016245 PD TAG: 007138842 REVISION: 7.2 REVISION: 7.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Analog Input Block The Analog Input (AI) Function Block processes the measurements from the sensor and makes them available to other function blocks. The output value from the AI block is in engineering units and contains a status indicating the quality of the measurement. The AI block is widely used for scaling functionality.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Output Splitter Block The Output Splitter Function Block provides the capability to drive two control outputs from a single input. It takes the output of one PID or other control block to control two valves or other actuators. Multiple Analog Input Block The Multiple Analog Input Block allows for up to 8 variables to be published in one macro cycle.
Reference Manual Rosemount 3051S 1-6 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Section 2 Rosemount 3051S Series Installation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-2 Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-4 Wiring . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series Electrical shock can result in death or serious injury. • Avoid contact with the leads and terminals. Process leaks could result in death or serious injury. • Install and tighten all four flange bolts before applying pressure. • Do not attempt to loosen or remove flange bolts while the transmitter is in service. Replacement equipment or spare parts not approved by Rosemount Inc.
Reference Manual 00809-0200-4801, Rev CA July 2010 Draft Range Rosemount 3051S Series Installation For the 3051S_CD0 draft range pressure transmitter, it is best to mount the transmitter with the isolators parallel to the ground. Installing the transmitter in this way reduces oil mounting effect and provides for optimal temperature performance. Be sure the transmitter is securely mounted. Tilting of the transmitter may cause a zero shift in the transmitter output.
Reference Manual Rosemount 3051S Series INSTALLATION PROCEDURES 00809-0200-4801, Rev CA July 2010 For dimensional drawing information refer to Appendix B: Specifications and Reference Data on page B-15. Process Flange Orientation Mount the process flanges with sufficient clearance for process connections. For safety reasons, place the drain/vent valves so the process fluid is directed away from possible human contact when the vents are used.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series Figure 2-1. Cover Jam Screw PlantWeb® Housing Junction Box Housing Cover Jam Screw 2X Cover Jam Screw (1 per side) Mount the Transmitter Mounting Brackets Facilitate mounting transmitter to a 2-in. pipe, or to a panel. The B4 Bracket (SST) option is standard for use with the Coplanar and In-Line process connections.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series Bolt Installation Only use bolts supplied with the Rosemount 3051S or sold by Emerson Process Management as spare parts. When installing the transmitter to one of the optional mounting brackets, torque the bolts to 125 in-lb. (0,9 N-m). Use the following bolt installation procedure: 1. Finger-tighten the bolts. 2. Torque the bolts to the initial torque value using a crossing pattern. 3.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series GAGE/ABSOLUTE TRANSMITTER DIFFERENTIAL TRANSMITTER Drain/Vent Plug Drain/Vent Drain/Vent 1.75 (44) x 4 1.75 (44) x 4 1.50 (38) x 4 1.50 (38) x 2 NOTE Dimensions are in inches (millimeters). Transmitter with Flange Adapters and Flange/ Adapter Bolts Transmitter with Flange Bolts 1.75 (44) x 4 2.
Reference Manual Rosemount 3051S Series 00809-0200-4801, Rev CA July 2010 Impulse Piping The piping between the process and the transmitter must accurately transfer the pressure to obtain accurate measurements. There are five possible sources of error: pressure transfer, leaks, friction loss (particularly if purging is used), trapped gas in a liquid line, liquid in a gas line, density variations between the legs, and plugged impulse piping.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series Mounting Requirements Impulse piping configurations depend on specific measurement conditions. Refer to Figure 2-2 for examples of the following mounting configurations: Liquid Flow Measurement • Place taps to the side of the line to prevent sediment deposits on the process isolators. • Mount the transmitter beside or below the taps so gases vent into the process line. • Mount drain/vent valve upward to allow gases to vent.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series Figure 2-3. In-Line Installation Examples Process Connections GAS SERVICE GAS OR LIQUID SERVICE LIQUID OR STEAM SERVICE 3051S transmitter flange process connection size is 1/4–18 NPT. Flange adapters with 1/2–14 NPT connections are available as the D2 option. Use your plant-approved lubricant or sealant when making the process connections.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series Failure to install proper flange adapter O-rings can cause process leaks, which can result in death or serious injury. The two flange adapters are distinguished by unique O-ring grooves. Only use the O-ring that is designed for its specific flange adapter, as shown below.
Reference Manual Rosemount 3051S Series 00809-0200-4801, Rev CA July 2010 1. Loosen the housing rotation set screw. 2. First rotate the housing clockwise to the desired location. If the desired location cannot be achieved due to thread limit, rotate the housing counter clockwise to the desired location (up to 360° from thread limit). 3. Retighten the housing rotation set screw.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series NOTE It is important to know that Simulate is enabled only when the hardware senses the switch changing from DISABLE to ENABLE. If the power is removed with the switch in ENABLE, Simulate is not enabled. You must move the switch from ENABLE to DISABLE and then back to ENABLE to be able to use the Simulate software. WIRING Transmitter Wiring Wiring and power supply requirements can be dependent upon the approval certification.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series Transmitter Grounding Always ground the transmitter case in accordance with national and local electrical codes. A ground can be connected to the 3051S Transmitter either by an external ground lug or the internal ground lug. Both options can be seen in Figure 2-6. Figure 2-6.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series Figure 2-7. Optional LCD Display LCD Display Meter Cover Setting Units Units for both the Sensor Transducer Block and the AI Block are set in the AI Block. To change units: • Set the AI Block to OOS mode • Select XD_Scale.units_index • Select only one of the engineering units listed on page 3-10 • Return AI Block to Auto mode ZEROING TRANSMITTER Before operating the transmitter, perform a Zero Trim and set the Damping.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series Figure 2-8. Integral Manifold Designs CONVENTIONAL Rosemount 305 Integral Manifold Installation Procedure COPLANAR TRADITIONAL IN-LINE To install a 305 Integral Manifold to a 3051S transmitter: 1. Inspect the PTFE SuperModule O-rings. If the O-rings are undamaged, reusing them is recommended. If the O-rings are damaged (if they have nicks or cuts, for example), replace them with new O-rings.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series NOTE If using thread tape, be sure the thread tape does not strip when the manifold assembly is started. 5. Wrench tighten manifold into process connection. (Note: Minimum torque value is 425 in-lbs) 6. Count how many threads are still showing. (Note: Minimum engagement is 3 revolutions) 7. Subtract the number of threads showing (after tightening) from the total threads to calculate the revolutions engaged.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series Manifold Operation Three-valve configuration shown. In normal operation the two block valves between the process and instrument ports will be open and the equalizing valve(s) will be closed. L H Drain/ Vent Valve Drain/ Vent Valve Equalize (closed) Isolate (open) Isolate (open) Process To zero the 3051S, close the block valve to the low pressure (downstream side) of the transmitter first.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Series The manifold valves are now in the proper configuration for zeroing the transmitter. To return the transmitter to service, close the equalizing valve(s) first. L H Drain/ Vent Valve Drain/ Vent Valve Equalize (closed) Isolate (open) Isolate (closed) Process Next, open the block valve on the low pressure side of the transmitter.
Reference Manual Rosemount 3051S Series 2-20 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Section 3 Rosemount 3051S Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Device Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-2 General Block Information . . . . . . . . . . . . . . . . . . . . . . . . . page 3-3 Resource Block . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S DEVICE CAPABILITIES Link Active Scheduler The Rosemount 3051S can be designated to act as the backup Link Active Scheduler (LAS) in the event that the LAS is disconnected from the segment. As the backup LAS, the 3051S will take over the management of communications until the host is restored. The host system may provide a configuration tool specifically designed to designate a particular device as a backup LAS.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S GENERAL BLOCK INFORMATION Modes The Resource, Transducer, and all function blocks in the device have modes of operation. These modes govern the operation of the block. Every block supports both automatic (AUTO) and out of service (OOS) modes. Other modes may also be supported. Changing Modes To change the operating mode, set the MODE_BLK.TARGET to the desired mode. After a short delay, the parameter MODE_BLOCK.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Block Instantiation The Rosemount 3051S supports the use of Function Block Instantiation. When a device supports block instantiation, the number of blocks and block types can be defined to match specific application needs.The number of blocks that can be instantiated is only limited by the amount of memory within the device and the block types that are supported by the device.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S SOFT W LOCK and HARD W LOCK Inputs to the security and write lock functions include the hardware security switch, the hardware and software write lock bits of the FEATURE_SEL parameter, the WRITE_LOCK parameter, and the DEFINE_WRITE_LOCK parameter. The WRITE_LOCK parameter prevents modification of parameters within the device except to clear the WRITE_LOCK parameter.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S PlantWeb™ Alarms The alarms and recommended actions should be used in conjunction with Section 2: Troubleshooting. The Resource Block will act as a coordinator for PlantWeb alarms. There will be three alarm parameters (FAILED_ALARM, MAINT_ALARM, and ADVISE_ALARM) which will contain information regarding some of the device errors which are detected by the transmitter software.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S MAINT_ALARMS A maintenance alarm indicates the device or some part of the device needs maintenance soon. If the condition is ignored, the device will eventually fail. There are five parameters associated with MAINT_ALARMS, they are described below. MAINT_ENABLED The MAINT_ENABLED parameter contains a list of conditions indicating the device or some part of the device needs maintenance soon.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S 1. Process Anomaly Detected (SPM) 2. LOI Failure 3. PWA Simulate Active 4. Defer NV Memory Write Detected 5. Mass Flow Transducer Block Reverse Flow 6. Mass Flow Transducer Block Sensor Out of Range 7. Mass Flow Transducer Block Out of Range 8. Process Anomaly Detected (SPM) ADVISE_MASK The ADVISE_MASK parameter will mask any of the failed conditions listed in ADVISE_ENABLED.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S CHANNEL Select the channel that corresponds to the desired sensor measurement. The 3051S measures both pressure (channel 1) and sensor temperature (channel 2). Table 3-1. I/O Channel Definitions Channel Number Channel Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 differential pressure in AI.XD_SCALE units sensor temperature in AI.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S XD_SCALE and OUT_SCALE The XD_SCALE and OUT_SCALE each include three parameters: 0%, 100%, and, engineering units. Set these based on the L_TYPE: L_TYPE is Direct When the desired output is the measured variable, set the XD_SCALE to the “Primary_Value_Range”. This is found in the Sensor Transducer Block. Set OUT_SCALE to match XD_SCALE.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Configuration Examples Pressure transmitter Situation #1 A pressure transmitter with a range of 0 – 100 psi. Solution Table 3-2 lists the appropriate configuration settings. Table 3-2. Analog Input function block configuration for a typical pressure transmitter. .
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Solution to Situation #2 Table 3-3 lists the appropriate configuration settings. Table 3-3. Analog Input function block configuration for a pressure transmitter used in level measurement (situation #1).
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Solution to situation #3 Table 3-4 lists the appropriate configuration settings. Table 3-4. Analog Input function block configuration for a pressure transmitter used in level measurement (Situation #3).
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Filtering The filtering feature changes the response time of the device to smooth variations in output readings caused by rapid changes in input. Adjust the filter time constant (in seconds) using the PV_FTIME parameter. Set the filter time constant to zero to disable the filter feature. Figure 3-3. Analog Input PV_FTIME filtering Diagram.
Reference Manual 00809-0200-4801, Rev CA July 2010 Process Alarms Rosemount 3051S Process Alarm detection is based on the OUT value. Configure the alarm limits of the following standard alarms: • High (HI_LIM) • High high (HI_HI_LIM) • Low (LO_LIM) • Low low (LO_LO_LIM) In order to avoid alarm chattering when the variable is oscillating around the alarm limit, an alarm hysteresis in percent of the PV span can be set using the ALARM_HYS parameter.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Advanced Features The AI Function Block provides added capability through the addition of the following parameters: ALARM_TYPE ALARM_TYPE allows one or more of the process alarm conditions detected by the AI function block to be used in setting its OUT_D parameter. OUT_D OUT_D is the discrete output of the AI function block based on the detection of process alarm condition(s).
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Modes The MAI Function Block supports three modes of operation as defined by the MODE_BLK parameter: Manual (Man) The block output (OUT) may be set manually Automatic (Auto) OUT_1 to OUT_8 reflects the analog input measurement or the simulated value when simulation is enabled. Out of Service (OOS) The block is not processed. Values are not updated and the OUT status is set to Bad: Out of Service.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Display Parameter 1 Block Type #1 AI Block Block Tag #1 FFAI_RMT3 Param Index #1 OUT Custome Tag #1 Units Type #1 Auto Custom Units #1 DISPLAY_PARAM_SEL The DISPLAY_PARAM_SEL parameter specifies how many process variables will be displayed. Select up to four display parameters. BLK_TAG_#(1) Enter the Block Tag of the function block that contains the parameter to be displayed.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Displaying a variable from another device on the segment (Example) Input Selector Any Function block on Segment IN_5 IN_6 Parameter X IN_7 IN_8 Any variable from a device on the network can be displayed on the 3051S LDC but the variable must be on a regularly scheduled communications cycle and the variable must be linked to a block within the 3051S.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S MASS FLOW The Mass Flow Function Block is a licensable block. It will be licensed on a new transmitter if the H01 option is ordered or it can be licensed in the field via a licensing code. Please contract your local sales person on how to acquire a license. The Mass Flow Function Block has two distinct parts to its configuration. The first part is downloading the formula the block uses to calculate mass flow.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Establish Communications with the 3051S FOUNDATION fieldbus Transmitter using 3095 EA for FOUNDATION fieldbus 1. Connect the 9-pin communications cable into the PCMCIA card port located in the computer. 2. Connect communication wiring to the cable connectors labeled “D+” and “D-”. 3. Open the transmitter cover on the side marked “Field Terminals”.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Create and Send a Mass Flow Configuration using 3051S EA for FOUNDATION fieldbus A mass flow configuration file can be created in either OFFLINE or ONLINE mode. 1. Select the device tag name requiring a new or updated mass flow configuration file. The selected device tag will become highlighted. Information about the selected device will appear on the Device Status portion of the screen. 2. Select the EA Wizard.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure 3-8. EA Wizard View EA Wizard 4. Upon completing a mass flow configuration using the EA Wizard, the file can be saved to disk. The file must be saved for review or to edit the mass flow configuration file in the future. FOUNDATION fieldbus mass flow configuration files cannot be uploaded from the Mass Flow Transducer Block. If the file is not saved, it cannot be retrieved. 5.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure 3-9. Download Mass Flow Configuration File Selected Device (Highlighted) Send Mass Flow Configuration File to Selected Device Status Confirms Mass Flow Configuration File Installations Table 3-7.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure 3-10. Field Communicator Menu Tree Home Overview Configure Service Tools Advanced Overview Status Primary Purpose Variable Shortcuts Status Active Alerts Return all to Service Put all Out of Service Active Alerts "Alert 1 Name" Primary Purpose Variable Pressure Value XX.XXX UOM Status: GOOD Temperature Value XX.
Reference Manual Rosemount 3051S 3-26 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Section 4 Rosemount 3051S Operation and Maintenance Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-2 Licensing Optional Blocks . . . . . . . . . . . . . . . . . . . . . . . . . page 4-2 Calibration . . . . . . . . . . .
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Electrical shock can result in death or serious injury. • Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock. Performing a 'Restart with defaults' will set all function block information in the device to factory defaults.
Reference Manual 00809-0200-4801, Rev CA July 2010 Master Reset Method Rosemount 3051S Resource Block To perform a master reset, run the Master Reset Method. If your system does not support methods, manually configure the Resource Block parameters listed below. 1.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S CALIBRATION Sensor Calibration, Upper and Lower Trim Methods Sensor Transducer In order to calibrate the transmitter, run the Upper and Lower Trim Methods. If your system does not support methods, manually configure the Transducer Block parameters listed below. 1. Set MODE_BLK.TARGET to OOS 2. Set CAL_UNIT to supported engineering units in the Transducer Block 3.
Reference Manual 00809-0200-4801, Rev CA July 2010 Factory Trim Recall Method Rosemount 3051S Sensor Transducer Block To perform a factory trim on the transmitter, run the Factory Trim Method. If your system does not support methods, manually configure the Transducer Block parameters listed below. 1. Set MODE_BLK.TARGET to OOS 2. Set FACTORY_CAL_RECALL to Recall 3. Set SENSOR_CAL_DATE to the current date. 4. Set SENSOR_CAL_WHO to the person responsible for the calibration. 5.
Reference Manual Rosemount 3051S 4-6 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Section 5 Rosemount 3051S Troubleshooting Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1 Troubleshooting Guides . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-2 Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-5 Sensor Transducer Block . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S TROUBLESHOOTING GUIDES Figure 5-1. Rosemount 3051S troubleshooting flowchart PROBLEMS WITH COMMUNICATIONS Device does not appear on segment. Device does not stay on segment. 1. Check wiring to device. 2. Recycle power to device. 3. Electronic failure. Refer to “Device does not show up on segment” in Table 5-1 for more information.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure 5-2. Problems with communications flowchart COMMUNICATIONS ESTABLISHED BUT HAVE “BLOCK_ERR” OR AN “ALARM” CONDITION. See "PlantWeb Alerts" on page 5-10 Problem Identified? Perform Recommended Action, see Table 2-1. Yes No Read the following parameters in the Resource Block to determine the recommended action.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table 5-1. Troubleshooting guide Symptom(1) Cause Recommended Actions Device does not show up on segment Unknown No power to device Recycle power to device 1. Ensure the device is connected to the segment. 2. Check voltage at terminals. There should be 9–32Vdc. 3. Check to ensure the device is drawing current. There should be approximately 17 mA.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S RESOURCE BLOCK This section describes error conditions found in the Resource block. Read Table 5-2 through Table 5-4 to determine the appropriate corrective action. Table 5-2. Resource Block BLOCK_ERR messages Block Errors Table 5-2 lists conditions reported in the BLOCK_ERR parameter. Condition Name and Description Other Simulate Active: This indicates that the simulation switch is in place.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S SENSOR TRANSDUCER BLOCK Table 5-5. Sensor Transducer Block BLOCK_ERR messages This section describes error conditions found in the Sensor Transducer Block. Read Table 5-5 through Table 5-7 to determine the appropriate corrective action. Condition Name and Description Other Out of Service: The actual mode is out of service. Table 5-6.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S ANALOG INPUT (AI) FUNCTION BLOCK This section describes error conditions that are supported by the AI Block. Read Table 5-9 to determine the appropriate corrective action. Table 5-8. AI BLOCK_ERR Conditions.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S LCD TRANSDUCER BLOCK This section describes error conditions found in the LCD Transducer Block. Read Table 5-10 and to determine the appropriate corrective action. Self Test Procedure for the LCD The SELF_TEST parameter in the Resource block will test LCD segments. When running, the segments of the display should light up for about five seconds.
Reference Manual 00809-0200-4801, Rev CA July 2010 ADVANCED DIAGNOSTICS TRANSDUCER BLOCK (ADB) Table 5-11. Advanced Diagnostic Block BLOCK_ERR messages Rosemount 3051S This section describes error conditions found in the Advanced Diagnostics Transducer Block. Read Table 5-11 to determine the appropriate corrective action. Refer to Section 6 for complete information on Advanced Diagnostics. Condition Name and Description Other Out of Service: The actual mode is out of service.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S PLANTWEB ALERTS Table 5-12. Failure Alerts Failed Alert What is this Alert Detecting? What is the effect Recommended Help on the instrument? Action Primary Value Failure Pressure updates from the sensor module stopped. PV holds last good value with a BAD status. Device remains in Auto. Secondary Value Failure Sensor Module temperature updates have stopped. SV holds last good value with a BAD status.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table 5-13. Maintenance Alerts Maintenance What is this Alert Alert Detecting? What is the effect on the instrument? Primary Value Degraded The PV is outside the operating range of the transmitter. PV status will go UNCERTAIN. The Instrument Pressure may be too High or too Low. Confirm that it is within the Operating Range of the Transmitter.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table 5-14. Advisory Alerts Advisory Alert What is this Alert Detecting? What is the effect Recommended Help on the instrument? Action Process Anomaly Detected (SPM) The statistical process monitor in the device diagnostics has reported that a user defined limit was exceeded. Alert Only LOI Failure Communications failure with LCD.
Reference Manual 00809-0200-4801, Rev CA July 2010 Section 6 Rosemount 3051S Advanced Pressure Diagnostics for FOUNDATION fieldbus Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-1 Statistical Process Monitoring Technology . . . . . . . . . . . page 6-2 SPM Configuration and Operation . . . . . . . . . . . . . . . . . . page 6-6 Plugged Impulse Line Detection Technology . . . . . . . . . page 6-17 Configuration of Plugged Impulse Line Detection . . . . .
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Statistical Process Monitoring (SPM) The Advanced Diagnostics Suite features SPM technology to detect changes in the process, process equipment or installation conditions of the transmitter. This is done by modeling the process noise signature (using the statistical values of mean and standard deviation) under normal conditions and then comparing the baseline values to current values over time.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S The sensing of the unique signature begins with the combination of a high speed sensing device, such as the Rosemount 3051S Pressure Transmitter, with software resident in a FOUNDATION fieldbus Feature Board to compute statistical parameters that characterize and quantify the noise or variation. These statistical parameters are the mean and standard deviation of the input pressure.
Reference Manual Rosemount 3051S SPM Functionality 00809-0200-4801, Rev CA July 2010 A block diagram of the Statistical Process Monitoring (SPM) diagnostic is shown in Figure 6-3. Note from Figure 6-1 that the 3051S FF has four Statistical Process Monitoring blocks (SPM1-SPM4). Figure 6-3 illustrates just one of the SPM blocks.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure 6-4. Flow Chart of 3051S FF Statistical Process Monitoring Further detail of the operation of the SPM diagnostic is shown in the Figure 6-4 flowchart. This is a simplified version showing operation using the default values. After configuration, SPM calculates mean and standard deviation, used in both the learning and the monitoring modes. Once enabled, SPM enters the learning/verification mode.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S NOTE: The Statistical Process Monitoring diagnostic capability in the Rosemount 3051S FOUNDATION fieldbus Pressure Transmitter calculates and detects significant changes in statistical parameters derived from the input process variable. These statistical parameters relate to the variability of and the noise signals present in the process variable.
Reference Manual 00809-0200-4801, Rev CA July 2010 SPM Configuration for Monitoring Other Process Variables Rosemount 3051S Advanced users may wish use SPM to monitor other Fieldbus parameters available within the pressure transmitter. Examples of such parameters would include module sensor temperature, PID control output, valve position, or a process measurement from another device on the same Fieldbus segment.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure 6-5. Effect of the SPM Monitoring Cycle on the Statistical Values SPM#_User_Command Select “Learn” after all the parameters have been configured to begin the Learning Phase. The monitoring phase will start automatically after the learning process is complete. Select “Quit” to stop the SPM. “Detect” may be selected to return to the monitoring phase.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S SPM#_Low_Dynamics_Lim Lower limit on standard deviation for detecting a Low Dynamics condition (must be specified as a negative number) All of these limits are specified as a percent change in the statistical value from its baseline. If a limit is set to 0 (the default setting) then the corresponding diagnostic is disabled. For example, if SPM#_High_Variation_Limit is 0, then SPM# does not detect an increase in standard deviation.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S SPM#_StDev Current Standard Deviation of the process variable SPM#_StDev_Change Percent change between the Baseline Standard Deviation and the Current Standard Deviation SPM#_Timestamp Timestamp of the last values and status for the SPM SPM#_Status Current state of the SPM Block.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table 6-1. Valid SPM Channels for the AI Block Channel 12 13 14 15 16 17 18 19 SPM Variable SPM1 mean SPM1 standard deviation SPM2 mean SPM2 standard deviation SPM3 mean SPM3 standard deviation SPM4 mean SPM4 standard deviation See Table 3-1 for a complete listing of valid Channels for the AI Block.
Reference Manual Rosemount 3051S 00809-0200-4801, Rev CA July 2010 Figure 6-7. SPM Configuration Wizard - Selecting the SPM to Configure The Wizard will then take you through the process of setting the parameters corresponding to the Block Tag, Block Parameter, Monitoring Cycle, and Bypass Verification. On Fieldbus hosts that support Device-Dashboard functionality (e.g. AMS Device Manager 10.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure 6-9. Example of PID Control within a Pressure Transmitter Using SPM, it is possible to detect problems in the control loop. For example, an increase in the cycling or oscillation of the control loop could be indicated by an increase in the standard deviation. If SPM has already been enabled, it must first be disabled, before any additional SPM blocks can be configured.
Reference Manual Rosemount 3051S EDDL Trending of Mean and Standard Deviation 00809-0200-4801, Rev CA July 2010 Once the SPM has been enabled, the EDDL user interface allows for easy viewing and trending of mean and standard deviation.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure 6-12. Example AI Function Block for Trending Standard Deviation in DeltaV Set the units and scaling for the function block as follows: XD_SCALE = 0 to 1 in H2O (68 °F) OUT_SCALE = 0 to 1 in H2O (68 °F) L_TYPE = Indirect Note that the range set in the OUT_SCALE parameter will be the range that is shown by default when the variable is trended in the DeltaV Process History View.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Follow through the “Add History Collection” dialog (Figure 6-14), to add the parameter to the DeltaV Historian with the desired sampling period, compression, etc. By default the sampling period is 60 seconds, as shown in a. of Figure 6-14. However, there are many diagnostics applications where one may want to look at changes in the standard deviation much faster than this.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure 6-15. Trend of Standard Deviation in DeltaV Process History View Finally, when the SPM data is trended in DeltaV, it is possible to configure HI and/or LO alarms on the mean or standard deviation via the AI Block. This can be done by right-clicking on the AI Function Block in Control Studio, and selecting the option “Assign Alarm”. The Block Alarm configuration window will let you set up desired alarm limits.
Reference Manual Rosemount 3051S 00809-0200-4801, Rev CA July 2010 Figure 6-16. Basics of Plugged Impulse Line Testing at Emerson Process Management and other sites indicates that Statistical Process Monitoring technology can detect plugged impulse lines. Plugging effectively disconnects the transmitter from the process, changing the noise pattern received by the transmitter.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S The case of the Differential Pressure measurement in a flow application with a single line plugged is more complicated, and the behavior of the transmitter may vary depending on a number of factors. First the basics: a differential pressure transmitter in a flow application is equipped with two impulse lines, one on the high pressure side (HP) and one on the low pressure side (LP) of the primary element.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S However, there is a combination of factors that may affect the output of the DP transmitter under single plugged line conditions. If the impulse line is filled with an incompressible fluid, no air is present in the impulse line or the transmitter body, and the plug is formed by rigid material, the noise or fluctuation will decrease.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S DP Flow and Low GP/AP vs. High GP/AP Measurements This is best described as a noise to signal ratio issue and is primarily an issue for detection of plugged lines for high GP/AP measurements. Regardless of the line pressure, flow generated noise tends to be about the same level. This is particularly true for liquid flows.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S L is the impulse line length in meters r is the radius of the impulse line. The “C” formula shows the strong influence of air trapped in a liquid filled impulse line, or an impulse line with air only. Both potential issues indicate the value of short impulse lines. One installation best practice for DP flow measurements is the use of the Rosemount 405 series of integrated compact orifice meters with the 3051S Pressure transmitter.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure 6-19. Overview of Plugged Impulse Line Diagnostics PIL also includes some additional features to make it especially suitable for detecting plugging in pressure measurement impulse lines.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S 4. Steady Process? At the end of the 5-minute verification phase, the PIL compares the last mean and standard deviation against the previous mean and standard deviation to determine if the process is at a steady state. If the process is at a steady-state, then the PIL moves into Detection phase. If not, then PIL repeats the Verification Phase 5.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure 6-20. Flow Chart for Plugged Impulse Line Diagnostics CONFIGURATION OF PLUGGED IMPULSE LINE DETECTION This section describes the configuration of the plugged impulse line diagnostic. Basic Configuration For some impulse line plugging applications there will be a very significant (> 80%) decrease in standard deviation.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S By default, the value of PLINE_Affect_PV_Status is “False”, meaning that the quality of the pressure measurement will not be changed if PIL detects a plugged impulse line. Setting this parameter to “True” will cause the status quality to change to “Uncertain” when a plugged impulse line is detected. Depending upon the DCS configuration, the “Uncertain” quality could be visible to the Operator, or it could affect the control logic.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Detection sensitivities are specified as a percent change in the standard deviation from the baseline value. Note from Figure 6-21 that a higher detection limit (% change) actually corresponds to a lower sensitivity, because a greater change in the process dynamics is required to trigger a plugged impulse line alert. Likewise, a lower detection limit corresponds to a higher sensitivity.
Reference Manual Rosemount 3051S 00809-0200-4801, Rev CA July 2010 First SPM needs to be configured to monitor the pressure as described in “SPM Configuration for Monitoring Pressure” on page 6-6. After SPM has been configured, the standard deviation needs to be trended, either in an EDDL-supported host (such as AMS Device Manager, shown in Figure 6-22), or in the DCS as described in “Trending Statistical Values in Control System” on page 6-10. Figure 6-22.
Reference Manual Rosemount 3051S Advanced PIL Configuration 00809-0200-4801, Rev CA July 2010 PIL provides the ability for advanced users to fine-tune some of the algorithm settings PLINE_Relearn_Threshold This adjusts the limit at which the PIL will automatically relearn new baseline values if the process mean changes.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S PLINE_Learn_Sensitivity The PLINE_Learn_Sensitivity parameters provide very specific adjustments to the sensitivity during the learning phase. Most of the time, it is sufficient to use the default values • Insufficient Dynamics Check: Ignores the insufficient dynamic check if not selected. Use only when there is very low process noise. This could result in a plugged impulse line not being detected. • 10%, 20%, and 30% Stdev.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Plugged Impulse Line Configuration in EDDL Host systems that support Electronic Device Description Language (EDDL) may use labels for the PIL configuration parameters that are slightly different from the Fieldbus parameter names described previously in this section. Table 6-2 below shows the correspondence between the fieldbus parameter names used in this document, and the labels used in EDDL hosts, such as AMS Device Manager.
Reference Manual Rosemount 3051S 6-32 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Appendix A Rosemount 3051S FOUNDATION fieldbus Block Information Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-1 Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-1 Sensor Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . page A-7 Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . page A-9 LCD Display Transducer Block . . . . . . .
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index DEV_REV Valid Range Initial Value Units Other Description 12 23 N/A Read Only DD_REV 13 3 N/A Read Only GRANT_DENY 14 HARD_TYPES 15 RESTART 16 Manufacturer revision number associated with the resource used by an interface device to locate the DD file for the resource. Revision of the DD associated with the resource - used by the interface device to locate the DD file for the resource.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index Valid Range MAX_NOTIFY 31 7 LIM_NOTIFY 32 0 to MAX_NOTIFY CONFIRM_ TIME 33 WRITE_LOCK 34 UPDATE_EVT BLOCK_ALM 35 36 N/A N/A ALARM_SUM 37 N/A ACK_OPTION 38 WRITE_PRI WRITE_ALM ITK_VER 39 40 41 DISTRIBUTOR 1: Unlocked 2: Locked Initial Value Units Other Description N/A Read Only Maximum number of unconfirmed notify messages possible.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index HARDWARE_ REV OUTPUT_ BOARD_SN FINAL_ASSY_ NUM DETAILED_ STATUS SUMMARY_ STATUS 52 MESSAGE_ DATE MESSAGE_ TEXT SELF_TEST DEFINE_WRITE _LOCK 60 SAVE_CONFIG_ NOW 61 SAVE_CONFIG_ BLOCKS 62 START_WITH_ DEFAULTS 63 SIMULATE_IO 64 SECURITY_IO 65 SIMULATE_ STATE 66 A-4 Valid Range Initial Value Units Other Description 3 N/A Read Only Read Only Read Only Read Only Read Only Hardware revision of that hardw
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index Valid Range Initial Value Units DOWNLOAD_ MODE 67 0-2 1 E RECOMMENDE D_ACTION FAILED_PRI FAILED_ENABLE 68 0 E 69 70 0 - 15 0 0 N/A E FAILED_MASK 71 See Table 25 0 E FAILED_ACTIVE 72 0 E FAILED_ALM 73 MAINT_PRI MAINT_ENABLE 74 75 0 - 15 MAINT_MASK 76 See Table 26 MAINT_ACTIVE 77 MAINT_ALM 78 ADVISE_PRI ADVISE_ ENABLE 79 80 0 - 15 ADVISE_MASK 81 See Table 27 ADVISE_ACTIVE 82 Othe
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index ADVISE_ALM 83 HEALTH_INDEX 84 PWA_SIMULATE A-6 85 Valid Range Initial Value Units Other N/A 1-100 Off/On (0-1) 100 Off None None Read Only Description Alarm indicating advisory alarms. These conditions do not have a direct impact on the process or device integrity. Parameter representing the overall health of the device, 100 being perfect and 1 being non-functioning.
Reference Manual 00809-0200-4801, Rev CA July 2010 SENSOR TRANSDUCER BLOCK Rosemount 3051S The transducer block contains the actual measurement data, including a pressure and temperature reading. The transducer block includes information about sensor type, engineering units, linearization, reranging, temperature compensation, and diagnostics. Table A-2.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index Initial Value Units SENSOR_CAL_ LOC SENSOR_CAL_ DATE 24 NULL N/A 25 0 N/A SENSOR_CAL_ WHO SENSOR_ ISOLATOR_MTL SENSOR_FILL_ FLUID SECONDARY_ VALUE SECONDARY_ VALUE_ UNIT TB_DETAILED_ STATUS 26 N/A 27 E 28 E 29 SVU FACTORY_CAL_ RECALL 32 MODULE_TYPE 33 SENSOR_CAL_ TYPE FLANGE_TYPE 34 30 Valid Range See Table 19 and footnote4 Read Only Read Only Read Only E 31 N/A Description The location of th
Reference Manual 00809-0200-4801, Rev CA July 2010 ANALOG INPUT (AI) FUNCTION BLOCK Rosemount 3051S The Analog Input (AI) function block processes field device measurements and makes them available to other function blocks. The output value from the AI block is in engineering units and contains a status indicating the quality of the measurement. The measuring device may have several measurements or derived values available in different channels.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S AI Parameter Table Table A-3. Definitions of Analog Input Function Block System Parameters. Parameter Index No. ACK_OPTION 23 ALARM_HYS Available Values Units Default Read/Write Description None 0 all Disabled Read and Write Used to set auto acknowledgment of alarms. 24 0 = Auto Ack Disabled 1 = Auto Ack Enabled 0 – 50 Percent 0.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index No.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index No. Available Values Units Default Read/Write Description TAG_DESC 02 32 text characters None none Read and Write UPDATE_EVT 20 Not applicable None Not applicable Read only The user description of the intended application of the block. This alert is generated by any change to the static data. In all Rosemount devices the units of the transducer block is forced to match the unit code.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S LCD DISPLAY TRANSDUCER BLOCK Table A-4.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index Valid Range UNITS_TYPE_2 24 1: Auto 2: Custom 3: None CUSTOM_UNITS _2 BLK_TYPE_3 BLK_TAG_3 PARAM_INDEX_ 3 CUSTOM_TAG _3 UNITS_TYPE_3 25 CUSTOM_UNITS _3 BLK_TYPE_4 BLK_TAG_4 PARAM_INDEX_ 4 CUSTOM_TAG _4 UNITS_TYPE_4 31 CUSTOM_UNITS _4 37 A-14 26 27 28 See Table 33 29 30 32 33 34 See Table 33 Units Other Description E This parameter determines where the units for the display parameter come from.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S ADVANCED DIAGNOSTICS TRANSDUCER BLOCK (ADB) Table A-5.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index Valid Range Initial Value Units SPM_BYPASS_ VERIFICATION SPM1_BLOCK_ TYPE 17 No N/A 0 N/A Enables/Disables Bypass of Process Stability Checks during Learning The function block type for the SPM1 variable SPM1_BLOCK_ TAG 19 NULL N/A Block tag for the SPM1 process variable SPM1_PARAM_ INDEX 20 0 N/A OD Parameter index for the SPM1 Block Tag that is entered.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index Valid Range Initial Value Units SPM1_LOW_ DYNAMICS_LIM SPM2_BLOCK_ TYPE 32 0.0f 0.0f % % Decrease in dynamics for SPM1 allowed by user 33 0 N/A The function block type for the SPM2 variable SPM2_BLOCK_ TAG 34 NULL N/A Block tag for the SPM2 process variable SPM2_PARAM_ INDEX 35 0 N/A OD Parameter index for the SPM2 Block Tag that is entered.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index Valid Range Initial Value Units SPM3_BLOCK_ TYPE 48 0 N/A The function block type for the SPM3 variable SPM3_BLOCK_ TAG 49 NULL N/A Block tag for the SPM3 process variable SPM3_PARAM_ INDEX 50 0 N/A OD Parameter index for the SPM3 Block Tag that is entered.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index Valid Range Initial Value Units SPM4_BLOCK_ TAG 64 NULL N/A Block tag for the SPM4 process variable SPM4_PARAM_ INDEX 65 0 N/A OD Parameter index for the SPM4 Block Tag that is entered.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Parameter Index Valid Range Initial Value Units Other Description PLINE_STATUS 78 Inactive Read Only Last Impulse line status PLINE_ TIMESTAMP PLINE_ON 79 Read Only Last Timestamp for PLINE_STATUS PLINE_ RELEARN PLINE_ SENSITIVITY 81 PLINE_AFFECT_ PV_STATUS 83 1.Inactive 2.Learning 3.Verifying 4.All Lines Plugged 5.OK 6.Insufficient Dynamics 7.BAD PV Status 8.Not Licensed All Times and Dates 0 = FALSE 0xff = TRUE 1.
Reference Manual 00809-0200-4801, Rev CA July 2010 Appendix B Rosemount 3051S Specifications and Reference Data Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . page B-1 Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . page B-10 Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . page B-18 Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . page B-23 Accessories . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Reference Accuracy Stated reference accuracy equations include terminal based linearity, hysteresis, and repeatability. For FOUNDATION fieldbus and wireless devices, use calibrated range in place of span. Transmitter with Coplanar Sensor Module (Single Variable) Differential Pressure (3051S_CD) Gage Pressure (3051S_CG) Ultra Classic Ultra for Flow(1) Ranges 2 - 4 ±0.025% of span; For spans less than 10:1, ±[0.005 + 0.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Transmitter with In-Line Sensor Module Absolute Pressure (3051S_TA) Gage Pressure (3051S_TG) Ranges 1 - 4 Range 5 Ultra ±0.025% of span For spans less than 10:1, ±[0.004(URL / Span)]% of span ±0.04% of span Classic ±0.055% of span For spans less than 10:1, ±[0.0065(URL / Span)]% of span ±0.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S MultiVariable Flow Performance(1) Mass, Energy, Actual Volumetric, and Totalized Flow Reference Accuracy Models Ultra for Flow Classic MV ±0.65% of Flow Rate over a 14:1 flow range (200:1 DP range) ±0.70% of Flow Rate over 8:1 flow range (64:1 DP range) Not Available ±0.90% of Flow Rate over 8:1 flow range (64:1 DP range) ±0.85% of flow rate at 8:1 flow turndown ±0.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Uncompensated Flow Performance Flow performance specifications assume the device only uses DP readings without pressure and temperature compensation. Models Ultra Classic Ultra for Flow ±0.9% of flow rate at 8:1 flow turndown ±0.80% of flow rate at 14:1 flow turndown Annubar Flowmeter (3051SFA) Ranges 2-3 ±0.85% of flow rate at 8:1 flow turndown Compact Conditioning Orifice Flowmeter (3051SFC_C) Ranges 2-3 = 0.4 ±0.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Warranty(1) Models All 3051S Products Ultra and Ultra for Flow (1) Classic and Classic MV (2) 1-year limited warranty(3) 12-year limited warranty (1) Warranty details can be found in Emerson Process Management Terms & Conditions of Sale, Document 63445, Rev G (10/06). (2) Rosemount Ultra and Ultra for Flow transmitters have a limited warranty of twelve (12) years from date of shipment.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Ambient Temperature Effect Transmitter with Coplanar Sensor Module (Single Variable) Differential Pressure: (3051S_CD, 3051SMV_ _3 or 4) Gage Pressure: (3051S_CG) Ultra per 50 °F (28 °C) Ranges 2 - 5(2) ±(0.009% URL + 0.025% span) from 1:1 to 10:1; ±(0.018% URL + 0.08% span) from >10:1 to 200:1 Range 0 ±(0.025% URL + 0.05% span) from 1:1 to 30:1 Range 1 ±(0.1% URL + 0.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Transmitter with MultiVariable Sensor Module Differential Pressure and Static Pressure (3051SMV_ _1 or 2) Models DP Ranges 2-3 DP Range 1 Classic MV Per 50 °F (28 °C) Ultra for Flow -40 to 185 °F (-40 to 85 °C) ±(0.0125% URL + 0.0625% span) from 1:1 to 5:1; ±(0.025% URL + 0.125% span) for >5:1 ±0.13 reading up to 8:1 DP turndown from URL; ±[0.13 + 0.0187(URL/Reading)]% reading to 100:1 DP turndown from URL Not available ±(0.
Reference Manual 00809-0200-4801, Rev CA July 2010 Models 3051SMV_ _ 1 or 2 3051SF_1, 2, 5, or 6 Rosemount 3051S Ultra, Ultra for Flow, Classic and Classic MV DP Sensor: GP/AP Sensor: 3051S_L Vibration Effect Zero shifts up to ±1.25 inH2O (3,11 mbar), which can be zeroed Span: no effect Zero shifts to ±2.5 inH2O (6,22 mbar), which can be zeroed Span: no effect With liquid level diaphragm in vertical plane, zero shift of up to ±1 inH2O (2,5 mbar).
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S FUNCTIONAL SPECIFICATIONS Range and Sensor Limits Transmitter with Coplanar Sensor Module (Single Variable) DP Sensor(1) (3051S_CD, 3051SMV_ _3, 4, or D 3051SF_3, 4, or 7, 3051S_LD) GP Sensor (3051S_CG, 3051S_LG) AP Sensor (3051S_CA, 3051S_LA) Range Lower (LRL)(2) Upper (URL) Lower (LRL)(3) Upper (URL) Lower (LRL) Upper (URL) 0 -3 inH2O (-7,5 mbar) -25 inH2O (-62,3 mbar) -250 inH2O (-0,62 bar) -1000 inH2O (-2,49 bar) -300 psi (-2
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Process Temperature RTD Interface (3051SMV_ _1 or 3, 3051SF_1, 3, 5 or 7)(1) Lower (LRL) Upper (URL) -328 °F (-200 °C) 1562 °F (850 °C) (1) Transmitter is compatible with any Pt 100 RTD sensor. Examples of compatible RTDs include Rosemount Series 68 and 78 RTD Temperature Sensors.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Process Temperature RTD Interface (3051SMV_ _1 or 3, 3051SF_1, 3, 5 or 7) Minimum Span = 50 °F (28 °C) Service 3051S, 3051SMV_P, and 3051SF_5, 6, 7, or D (Direct Process Variable Output): Liquid, gas, and vapor applications 3051SMV_M and 3051SF_1, 2, 3, or 4 (Mass and Energy Flow Output): Some fluid types are only supported by certain measurement types Fluid Compatibility with Pressure and Temperature Compensation Ordering Code 1 2 3 4 Me
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S 3051SMV and 3051SF_1-7 3051S and 3051SF_D with HART Diagnostics (option code DA1) Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 12.0) Load (Ohms) 1322 1000 500 Operating Region 0 12.0 20 30 Voltage (Vdc) 42.4 The HART communicator requires a minimum loop resistance of 250 for communication.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Backup Link Active Scheduler (LAS) The transmitter can function as a Link Active Scheduler if the current link master device fails or is removed from the segment. Software Upgrade in the Field Software for the 3051S with FOUNDATION fieldbus is easy to upgrade in the field using the FOUNDATION fieldbus Common Device Software Download procedure.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S ASP Diagnostics Suite for FOUNDATION fieldbus (Option Code D01) The 3051S ASP Diagnostics Suite for FOUNDATION fieldbus provides Abnormal Situation Prevention indication and enhanced EDDL graphic displays for easy visual analysis. The integral Statistical Process Monitoring (SPM) technology calculates the mean and standard deviation of the process variable 22 times per second and makes them available to the user.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Coplanar MultiVariable Sensor Module (3051SMV_ _1 or 2, 3051SF_1, 2, 5, or 6) Differential Pressure Static Pressure Range 1 Range 2 Range 3 Range 3 GP/AP Range 4 GP/AP 1600 psi (110,3 bar) 2000 psi (137,9 bar) 1600 psi (110,3 bar) 3626 psi (250 bar) 1600 psi (110,3 bar) 3626 psi (250 bar) Liquid Level Transmitter (3051S_L) Overpressure limit is dependent on the flange rating or sensor rating (whichever is lower).
Reference Manual 00809-0200-4801, Rev CA July 2010 Temperature Limits Rosemount 3051S Ambient -40 to 185 °F (-40 to 85 °C) With LCD display(1): -40 to 175 °F (-40 to 80 °C) With option code P0: -20 to 185 °F (-29 to 85 °C) (1) LCD display may not be readable and LCD updates will be slower at temperatures below -4 °F (-20 °C).
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Humidity Limits 0–100% relative humidity Turn-On Time(1) When power is applied to the transmitter during startup, performance will be within specifications per the time period described below: Transmitter Turn-On Time (Typical) 3051S, 3051SF_D, 3051S_L Diagnostics 3051SMV, 3051SF_1-7 2 seconds 5 seconds 5 seconds (1) Does not apply to wireless option code X. Volumetric Displacement Less than 0.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Process Connections Coplanar Sensor Module (3051S_C, 3051SMV, 3051SF) Standard Process Adapters (D2 Option) 1 /4-18 NPT on 2 1/8-in. centers /2-14 NPT and RC 1/2 on 2-in. (50.8 mm), 2 1/8-in. (54.0 mm), or 2 1/4-in. (57.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Drain/Vent Valves 316 SST, Alloy C-276, or Alloy 400/K-500(1) material (Drain vent seat: Alloy 400, Drain vent stem: Alloy K-500) (1) Alloy 400/K-500 is not available with 3051S_L.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Shipping Weights Sensor Module Weights Coplanar Sensor Module(1) 3.1 lb (1,4 kg) In-Line Sensor Module 1.4 lb (0,6 kg) (1) Flange and bolts not included. Transmitter Weights(1) Transmitter with Coplanar Sensor Module (3051S_C, 3051SMV, 3051SAM_ _G or A) Junction Box Housing, SST Flange 6.3 lb (2,8 kg) PlantWeb Housing, SST Flange 6.7 lb (3,1 kg) Wireless PlantWeb Housing, SST Flange 7.
Reference Manual Rosemount 3051S 3051S_L Weights Without SuperModule Platform, Housing, or Transmitter Options Flush 2-in. Ext. 4-in. Ext. Flange lb. (kg) lb (kg) lb (kg) 2-in., 150 9.5 (4,3) — — 3-in., 150 15.7 (7,1) 16.4 (7,4) 17.6 (8,0) 4-in., 150 21.2 (9,6) 20.9 (9,5) 22.1 (10,0) 2-in., 300 11.3 (5,1) — — 3-in., 300 19.6 (8,9) 20.3 (9,2) 21.5 (9,8) 4-in., 300 30.4 (13.8) 30.3 (13,7) 31.5 (14,3) 2-in., 600 12.8 (5,8) — — 3-in., 600 22.1 (10,0) 22.8 (10,3) 24.0 (10,9) DN 50 / PN 40 11.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S DIMENSIONAL DRAWINGS Figure B-1. Transmitter with Coplanar Sensor Module and Flange PlantWeb Housing Junction Box Housing Wireless Housing Front View Front View Front View 4.20 (107) Extended Range Antenna 4.20 (107) 8.53 (217) 8.53 (217) 9.63 (245) Side View 4.55 (116) Long Range Antenna 6.93 (176) 90° 10.91 (277) 4.20 (107) 9.63 (245) Side View Side View 3.45 (88) 3.46 (87.8) 6.72 (171) 6.06 (155) 7.70 (196) 8.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure B-2. Transmitter with Coplanar Sensor Module and Traditional Flange PlantWeb Housing Junction Box Housing Wireless Housing Front View Front View Front View Extended Range Antenna Long Range Antenna 6.93 (176) 9.26 (235) 9.26 (235) 3.40 (86) 1.10 (28) Side View 90° 10.91 (277) 4.20 (107) 3.40 (86) 1.10 (28) 3.40 (86) Side View 1.10 (28) Side View 3.45 (88) 3.46 (87.8) 6.72 (171) 6.06 (155) 7.70 (196) 9.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure B-3. Transmitter with In-Line Sensor Module PlantWeb Housing Junction Box Housing Wireless Housing Front View Front View Front View Extended Range Antenna 4.20 (107) 4.20 (107) Long 90° Range Antenna 6.93 (176) 3.46 (87.8) 4.20 (107 8.22 (209) 8.22 (209) Side View 10.91 (277) Side View Side View 5.21 (132) 4.55 (116) 3.45 (88) 6.93 (176) 6.72 (171) 6.06 (155) 8.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure B-4. Coplanar Mounting Configurations (B4 Bracket) Pipe Mount Front View Panel Mount Front View Front View 4.55 (116) 2.58 (66) 6.15 (156) 2.81 (71) 4.70 (120) 3.54 (90) 6.25 (159) Dimensions are in inches (millimeters) Figure B-5. Traditional Mounting Configurations Pipe Mount Pipe Mount (Flat Bracket) Panel Mount 10.70 (272) 8.18 (208) 2.62 (67) 7.7 (196) 13.03 (331) 0.93 (24) 5.32 (135) 2.62 (67) 3.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure B-6. In-Line Mounting Configurations (B4 Bracket) Pipe Mount Front View Panel Mount Side View 2.58 (66) 4.55 (116) 6.15 (156) 6.15 2.81 (71) 6.25 (159) 3.08 (78) 4.72 (120) 6.90 (175) Dimensions are in inches (millimeters) Figure B-7. Remote Display Mounting Configurations (B4 Bracket) Pipe Mount Front View Panel Mount Side View 2.33 (59) 5.19 (132) 1.82 (46) 4.48 (114 2.66 (68) 2.66 (68) 6.90 (175) 6.15 (156) 4.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure B-8. Rosemount 3051SFA Annubar Flowmeter Rosemount 3051SFA Annubar Flowmeter(1) Front View Side View Top View D C B A Dimensions are in inches (millimeters) (1) The Pak-Lok Annubar model is available up to 600# ANSI (1440 psig at 100 °F (99 bar at 38 °C)). Table 1. 3051CFA Annubar Flowmeter Dimensional Data B-28 Sensor Size A (Max) 1 2 3 7.50 (190.5) 9.25 (235.0) 12.00 (304.8) B (Max) C (Max) 16.03 (407.2) 9.00 (228.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure B-9. Rosemount 3051SFC Compact Orifice Flowmeter Rosemount 3051SFC Compact Orifice Flowmeter Orifice Plate Front View Orifice Plate Side View Orifice Plate Top View Compact Orifice Plate (Primary Element Type code P) E D B C A F 1.13 (28.7) (Primary Element Type code C) Conditioning Orifice Plate E D B A C F 1.13 (28.7) Dimensions are in inches (millimeters) Table 2.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure B-10. Rosemount 3051SFP Integral Orifice Flowmeter Rosemount 3051SFP Integral Orifice Flowmeter Front View Bottom View Side View 11.9 (302.3) 8.8 (223.46) 7.7 (195.6) Flow 5.3 (134.14) B.D.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Figure B-11. 3051S_L Liquid Side View Flush Flanged Configuration Front View Extended Flanged Configuration 5.21 (132) 4.20 (107) 4.20 (107) 4.55 (116) 7.09 9.65 (180) 8.53 (245) (217) E D A A H B C H Extension 2, 4, or 6 (51, 102, or 152) Dimensions are in inches (millimeters) Level Transmitter Class ASME B16.5 (ANSI) 150 ASME B16.5 (ANSI) 300 ASME B16.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Engineering Assistant Software Packages Code Product Description EA Code Engineering Assistant Software Program Software Media 2 3 Code EA Rev. 5 (Compatible with 3095, 3051S FOUNDATION fieldbus, and 333) EA Rev.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S ORDERING INFORMATION Table B-1. 3051S Series Coplanar Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time. Model Transmitter Type 3051S Scalable Pressure Transmitter Performance Class Standard 1 Ultra: 0.
Reference Manual Rosemount 3051S 00809-0200-4801, Rev CA July 2010 Table B-1. 3051S Series Coplanar Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table B-1. 3051S Series Coplanar Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Rosemount 3051S 00809-0200-4801, Rev CA July 2010 Table B-1. 3051S Series Coplanar Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table B-1. 3051S Series Coplanar Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Rosemount 3051S (1) (2) (3) (4) 00809-0200-4801, Rev CA July 2010 This option is only available with range codes 2A and 3A, 316L SST or Alloy C-276 isolating diaphragm and silicone fill fluid. Performance Class code 3 is available with Measurement Type code D only. 3051S_CD0 is only available with traditional flange, 316L SST diaphragm material, and Bolting option L4.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table B-2. 3051S Series In-Line Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time. Model Transmitter Type 3051S Scalable Pressure Transmitter Performance Class Standard 1 Ultra: 0.025 percent span accuracy, 200:1 rangedown, 10-yr stability, 12-yr limited warranty 2 Classic: 0.
Reference Manual Rosemount 3051S 00809-0200-4801, Rev CA July 2010 Table B-2. 3051S Series In-Line Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table B-2. 3051S Series In-Line Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Rosemount 3051S 00809-0200-4801, Rev CA July 2010 Table B-2. 3051S Series In-Line Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table B-3. Rosemount 3051S Scalable Liquid Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time. Model Transmitter Type Standard 3051S Scalable Liquid Level Transmitter Standard ★ Performance Class Standard 1 2 Standard ★ ★ Ultra: 0.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table B-3. Rosemount 3051S Scalable Liquid Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table B-3. Rosemount 3051S Scalable Liquid Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Rosemount 3051S 00809-0200-4801, Rev CA July 2010 Table B-3. Rosemount 3051S Scalable Liquid Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table B-3. Rosemount 3051S Scalable Liquid Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table B-3. Rosemount 3051S Scalable Liquid Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Table B-4.
Reference Manual Rosemount 3051S 00809-0200-4801, Rev CA July 2010 KA ATEX and CSA Flameproof, Intrinsically Safe, Division 2 (combination of E1, E6, I1, and I6) Note: Only available on Housing Style codes IA, IJ, 2A, 2J, 2E, 2M, 3A, or 3J. KB FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5, E6, I5, and I6) Note: Only available on Housing Style codes IA, IJ, 2A, 2J, 2E, 2M, 3A, or 3J.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S EXPLODED VIEW DIAGRAM The following drawing shows the name and location for commonly ordered spare parts.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S SPARE PARTS See Rosemount 3051S_C, 3051S_T & 3051S_L ordering tables in Appendix B (B-33, B-39, and B-43 respectively) for ordering spare sensor modules.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Covers Aluminum Electronics Cover; Cover and O-ring 03151-9030-0001 316L SST Electronics Cover; Cover and O-ring 03151-9030-0002 Housing Miscellaneous External Ground Screw Assembly (Option D4): Screw, clamp, washer 03151-9060-0001 Housing V-Seal for both PlantWeb and Junction Box housings 03151-9061-0001 Flanges Part Number Differential Coplanar Flange Nickel-plated Carbon Steel 03151-9200-0025 316 SST 03151-9200-0022 Alloy C
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Flange Adapter Union Part Number Nickel-plated Carbon Steel 03151-9259-0005 316 SST 03151-9259-0002 Alloy C-276 03151-9259-0003 Alloy 400 03151-9259-0004 Drain/Vent Valve Kits (each kit contains parts for one transmitter) Part Number Differential Drain/Vent Kits 316 SST Valve Stem and Seat Kit 03151-9268-0022 Alloy C-276 Valve Stem and Seat Kit 03151-9268-0023 Alloy 400 Valve Stem and Seat Kit 03151-9268-0024 316 SST Ceram
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Flange/Adapter Bolt Kit {73 mm (2.88 in.)} Carbon Steel (set of 4) 03151-9281-0001 316 SST (set of 4) 03151-9281-0002 ANSI/ASTM-A-193-B7M (set of 4) 03151-9281-0003 Alloy 400 (set of 4) Manifold/Flange Kit {57 mm (2.25 in.
Reference Manual Rosemount 3051S B-56 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Appendix C Rosemount 3051S Product Certifications Approved Manufacturing Locations . . . . . . . . . . . . . . . . . page C-1 Ordinary Location Certification for FM . . . . . . . . . . . . . . . page C-1 European Directive Information . . . . . . . . . . . . . . . . . . . . page C-1 Hazardous Locations Certifications . . . . . . . . . . . . . . . . . page C-2 Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S HAZARDOUS LOCATIONS CERTIFICATIONS North American Certifications FM Approvals E5 Explosion-proof for Class I, Division 1, Groups B, C, and D, T5 (Ta = 85 °C); Dust Ignition-proof for Class II and Class III, Division 1, Groups E, F, and G, T5 (Ta = 85 °C); hazardous locations; enclosure Type 4X, conduit seal not required when installed according to Rosemount drawing 03151-1003.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Special conditions for safe use (x) 1. The apparatus, excluding the Types 3051 S-T and 3051 S-C (In-line and Coplanar SuperModule Platforms respectively), is not capable of withstanding the 500V test as defined in Clause 6.3.12 of EN 60079-11. This must be considered during installation. 2. The terminal pins of the Types 3051 S-T and 3051 S-C must be protected to IP20 minimum. N1 ATEX Type n Certificate No.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Japanese Certifications E4 TIIS Flameproof Ex d IIC T6 Certificate Description TC15682 TC15683 TC15684 Coplanar with Junction Box Housing Coplanar with PlantWeb Housing Coplanar with PlantWeb Housing and LCD Display In-Line SST with Junction Box Housing In-Line Alloy C-276 with Junction Box Housing In-Line SST with PlantWeb Housing In-Line Alloy C-276 with PlantWeb Housing In-Line SST with PlantWeb Housing and LCD Display In-Line Alloy
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S E3 China Flameproof, Dust Ignition-proof Certificate No. (manufactured in Chanhassen, MN): GYJ091035 Certificate No. (manufactured in Beijing, China): GYJ06366 Certificate No. (manufactured in Singapore): GYJ06364 Certificate No. (3051SFx RTC, BMMC, SMMC): GYJ071086 Ex d IIB+H2 T3~T5 DIP A21 TA T3~T5 IP66 NOTE Refer to Appendix B of the 3051S Reference Manual (document number 00809-0100-4801) for Special Conditions for Safe Use.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Special conditions for safe use (x) 1. Appropriate ex d blanking plugs, cable glands, and wiring needs to be suitable for a temperature of 90 °C. 2. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Input Parameters Loop / Power Groups Ui = 30 V HART / FOUNDATION fieldbus/ Remote Display / Quick Connect / HART Diagnostics Ui = 17.5 V FISCO Ii = 300 mA HART / FOUNDATION fieldbus/ Remote Display / Quick Connect / HART Diagnostics Ii = 380 mA FISCO Pi = 1.0 W HART / Remote Display / Quick Connect / HART Diagnostics Pi = 1.3 W FOUNDATION fieldbus Pi = 5.32 W FISCO Ci = 30 nF SuperModule Platform Ci = 11.
Reference Manual Rosemount 3051S INSTALLATION DRAWINGS Factory Mutual (FM) C-8 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-9
Reference Manual Rosemount 3051S C-10 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-11
Reference Manual Rosemount 3051S C-12 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-13
Reference Manual Rosemount 3051S C-14 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-15
Reference Manual Rosemount 3051S C-16 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-17
Reference Manual Rosemount 3051S C-18 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-19
Reference Manual Rosemount 3051S C-20 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-21
Reference Manual Rosemount 3051S C-22 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-23
Reference Manual Rosemount 3051S C-24 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Canadian Standards Association (CSA) C-25
Reference Manual Rosemount 3051S C-26 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-27
Reference Manual Rosemount 3051S C-28 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-29
Reference Manual Rosemount 3051S C-30 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-31
Reference Manual Rosemount 3051S C-32 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-33
Reference Manual Rosemount 3051S C-34 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-35
Reference Manual Rosemount 3051S C-36 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-37
Reference Manual Rosemount 3051S KEMA C-38 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S C-39
Reference Manual Rosemount 3051S C-40 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S EUROPEAN ATEX DIRECTIVE INFORMATION CENELEC/BASEEFA Rosemount 3051S pressure transmitters that have the following label attached, have been certified to comply with Directive 94/9/EC of the European Parliament and the Council as published in the Official Journal of the European Communities No. L 100/1 on 19–April–1994.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Type n housing label • Marking for type n protection: II 3 G Ex nAnL IIC T4 (-40 °C Tamb 70 °C) Ui = 45 Vdc MAX BASEEFA ATEX certificate number: BAS01ATEX3304X Dust housing label • C-42 Marking for dust protection: II 1 D -20 °C Tamb 85 °C T105°C IP66 V = 42.
Reference Manual 00809-0200-4801, Rev CA July 2010 CENELEC/KEMA FLAMEPROOF Rosemount 3051S The Rosemount 3051S and 300S pressure transmitters that have the following label attached, have been certified to comply with Directive 94/9/EC of the European Parliament and the Council as published in the Official Journal of the European Communities No. L 100/1 on 19–April–1994.
Reference Manual Rosemount 3051S C-44 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Appendix D Rosemount 3051S 3051S FOUNDATION fieldbus Revision 23 Release New Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page D-1 New Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page D-2 NEW FUNCTION BLOCKS Compensated Mass Flow Transducer Block This block has all the functionality of the 3095 MultiVariable Mass Flow transmitter with its fully compensated real-time mass flow calculation.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S NEW FUNCTIONALITY PID with Auto Tuner This block has now been improved to include an auto-tune function. Advanced Diagnostic Block The Statistical Process Monitoring with continuous update of mean and standard deviation at sensor update rate – Previous to Revision 23, SPM values, Mean and Standard Deviation, could be viewed but not connected to a control strategy.
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S Revised function blocks (comply w/ most recent ITK) The Arithmetic, Characterizer and Integrator blocks had small changes made to them to bring them in compliance to ITK 5.0 (One of the first devices to pass this level). Sensor status remains Uncertain when reading is beyond the sensor limits (increased robustness) Previous to this release when a pressure went beyond the sensor limits the pressure status would go to BAD.
Reference Manual Rosemount 3051S D-4 00809-0200-4801, Rev CA July 2010
Reference Manual 00809-0200-4801, Rev BA July 2010 Rosemount 3051S Index A Analog Input (AI) Function Block 1-4, Address . . . . . . . . . . . . . . . . 1-2 Temporary Node . . . . . . . 1-2 Advanced Diagnostics Transducer Block (ADB) . . . . 1-3, 5-9, A-15 Block Error . . . . . . . . . . . 5-9 Parameters . . . . . . . . . . A-15 Troubleshooting . . . . . . . 5-9 Advanced Features . . . . . . . 3-16 ADVISE_ACTIVE . . . . . . . . . . 3-8 ADVISE_ALM . . . . . . . . . . . . 3-8 ADVISE_ENABLED . . . . . . .
Reference Manual 00809-0200-4801, Rev BA July 2010 Rosemount 3051S FAILED_ALM . . . . . . . . . . . . 3-6 FAILED_ENABLED alarms . . . 3-6 FAILED_MASK alarms . . . . . . 3-6 FAILED_PRI alarms . . . . . . . . 3-6 Features Advanced . . . . . . . . . . . 3-16 FEATURES, FEATURES_SEL 3-4 Reports . . . . . . . . . . . . . 3-4 Soft W Lock, Hard W Lock 3-5 Unicode . . . . . . . . . . . . . 3-4 Filtering . . . . . . . . . . . . . . . 3-14 AI block . . . . . . . . . . . .
Reference Manual 00809-0200-4801, Rev BA July 2010 Parameter Advanced Diagnostics Transducer Block (ADB) . . . A-15 ADVISE_ACTIVE . . . . . . 3-8 ADVISE_ALM . . . . . . . . . 3-8 ADVISE_ENABLED . . . . . 3-7 ADVISE_PRI . . . . . . . . . 3-8 ALARM_TYPE . . . . . . . 3-16 Analog Input (AI) Function Block A-10 BLK_TAG_# . . . . . . . . . 3-18 BLK_TYPE_# . . . . . . . . 3-18 BLOCK_ERR . . . . . 5-5, 5-7 CHANNEL . . . . . . . . . . . 3-9 CUSTOM_TAG_# . . . . . 3-18 CUSTOM_UNITS_# . . . 3-18 DEFINE_WRITE_LOCK .
Reference Manual Rosemount 3051S Index-4 00809-0200-4801, Rev BA July 2010
Reference Manual 00809-0200-4801, Rev CA July 2010 Rosemount 3051S The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. SuperModule and Coplanar trademarks of Rosemount Inc. PlantWeb is a mark of one of the Emerson Process Management companies. HART is a registered trademark of the HART Communications Foundation. Syltherm and D.C. are registered trademarks of Dow Corning Co.