Installation Manual Par t Number 3-9000-765Revision H June 2015 DanielTM 3812 Liquid Ultrasonic Flow Meter for Direct or Remote Mount Meter Electronics
Daniel customer service Location Telephone number Fax number North America/Latin America +1.713.467.6000 +1.713.827.4805 Daniel Customer Service +1.713.827.6314 +1.713.827.6312 USA (toll free) +1.888.356.9001 +1.713.827.3380 Asia Pacific (Republic of Singapore) +65.6777.8211 +65.6777.0947.0743 Europe (Stirling Scotland, UK) +44 (0)1786.433400 +44 (0)1786.433401 Middle East Africa (Dubai, UAE) +971 4 8118100 +971 4 8865465 Email • Customer Service: tech.service@emersonprocess.
Signal words and symbols Pay special attention to the following signal words, safety alert symbols and statements: Safety alert symbol This is a safety alert symbol. It is used to alert you to potential physical injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death. Danger indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Important safety instructions Daniel Measurement and Control, Inc. (Daniel) designs, manufactures and tests products to function within specific conditions. Because these products are sophisticated technical instruments, it is important that the owner and operation personnel strictly adhere both to the information printed on the product and to all instructions provided in this manual prior to installation, operation, and maintenance.
Product Operation Personnel: • To prevent personal injury, personnel must follow all instructions of this manual prior to and during operation of the product. • Follow all warnings, cautions, and notices marked on, and supplied with, this product. • Verify that this is the correct instruction manual for your Daniel product. If this is not the correct documentation, contact Daniel at 1-713-827-6314. You may also download the correct manual from: http://www.daniel.
Notice THE CONTENTS OF THIS PUBLICATION ARE PRESENTED FOR INFORMATIONAL PURPOSES ONLY, AND WHILE EVERY EFFORT HAS BEEN MADE TO ENSURE THEIR ACCURACY, THEY ARE NOT TO BE CONSTRUED AS WARRANTIES OR GUARANTEES, EXPRESSED OR IMPLIED, REGARDING THE PRODUCTS OR SERVICES DESCRIBED HEREIN OR THEIR USE OR APPLICABILITY. ALL SALES ARE GOVERNED BY DANIEL'S TERMS AND CONDITIONS, WHICH ARE AVAILABLE UPON REQUEST. WE RESERVE THE RIGHT TO MODIFY OR IMPROVE THE DESIGNS OR SPECIFICATIONS OF SUCH PRODUCTS AT ANY TIME.
Warranty and Limitations 1. LIMITED WARRANTY: Subject to the limitations contained in Section 2 herein, Daniel Measurement & Control, Inc.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H Table of Contents June 2015 Contents Daniel customer service ................................................................................... 3 • Signal words and symbols .............................................................................. 4 • Important safety instructions ......................................................................... 5 • Notice ............................................................
Table of Contents Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual June 2015 3-9000-765 Rev H 3.6 I/O connections ......................................................................................... 55 3.6.1 Frequency/Digital outputs ...........................................................................56 3.6.2 Analog input settings ...................................................................................60 3.6.3 Analog output settings ...............................
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H List of Tables June 2015 List of Tables Table 1-1 Acronyms, abbreviations and definitions ........................................................................... 3 Table 1-2 Meter specifications......................................................................................................... 13 Table 2-1 3812 Ultrasonic Meter shrouds options per ANSI pressure rating .....................................
List of Tables June 2015 ii Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H List of Tables
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H List of Figures June 2015 List of Figures Figure 1-1 Daniel MeterLink download and registration ................................................................ 5 Figure 1-2 Direct mount electronics assembly with split shroud .................................................... 6 Figure 1-3 Direct mount electronics with latched single band shrouds and remote display............
List of Figures June 2015 iv Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Installation Manual 3-9000-765 Rev H Figure 3-14 Split shroud security seals ........................................................................................... 68 Figure 3-15 Latched band shroud assembly ................................................................................... 69 Figure 3-16 Shroud latch holes for security wire seals............................................................
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 1: Introduction 3-9000-765 Rev H May 2015 Section 1: Introduction Daniel 3812 Liquid Ultrasonic Flow Meters have direct mount or remote mount electronic options and various configurations that meet a broad range of customer requirements. Each meter comes fully assembled from Daniel Measurement and Control, Inc. and all parts and assemblies are tested prior to shipment.
Section 1: Introduction Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 1.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 1: Introduction 3-9000-765 Rev H 1.
Section 1: Introduction Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Table 1-1 Acronyms, abbreviations and definitions Acronym or abbreviation m3/h cubic meters per hour (volumetric flow rate) m3/s mA MAC Address cubic meters per second (volumetric flow rate) microinch (μinch) microinch (10-6 in) micron micrometer (10-6 m) Memory Management Unit MMU MPa N/A Nm3/h NOVRAM Pa Pa⋅s PC PFC P/N PS psi psia psig R rad RAM Remote Mount Option RTS RTU MODBUS s SD
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 1: Introduction 3-9000-765 Rev H 1.4 May 2015 Daniel MeterLink software Daniel MeterLink software has robust features for setting communications parameters, calibrating your meter, collecting logs and reports and monitoring the meter health and alarm statuses. Daniel MeterLink may be downloaded at no charge from: http://www2.emersonprocess.com/en-US/brands/daniel/Flow/ultrasonics/Pages/MeterLink.
Section 1: Introduction Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 1.5 3-9000-765 Rev H Daniel 3812 Liquid Ultrasonic Flow meter design TheDaniel 3812 Liquid Ultrasonic Flow Meter designs include a direct or remote mount electronics option and depending on the meter’s outside diameter, have a shroud cover protecting the transducers and cable assemblies. See Table 2-1 and the list below for meter body shroud types.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 1: Introduction 3-9000-765 Rev H May 2015 Figure 1-3 Direct mount electronics with latched single band shrouds and remote display A. B. C. A. Explosion-proof transmitter enclosure (CPU Module, Power Supply, I.S. Barrier Board, Backplane board, and optional LCD Board with glass endcap) B. Intrinsically-safe base enclosure includes Acquisition Module C.
Section 1: Introduction May 2015 Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H Figure 1-4 Direct mount electronics with bolted single band shrouds and local display A. B. C. A. Explosion-proof transmitter enclosure (CPU Module, Power Supply, I.S. Barrier Board, Backplane board, and optional LCD Board with glass endcap) B. Intrinsically-safe base enclosure includes Acquisition Module C.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 1: Introduction 3-9000-765 Rev H May 2015 Figure 1-5 Direct mount electronics assembly with clamped band shrouds A. B. C. A. Explosion-proof transmitter enclosure (CPU Module, Power Supply, I.S. Barrier Board, Backplane board, optional LCD Board with glass endcap) B. Intrinsically-safe base enclosure includes Acquisition Module C.
Section 1: Introduction Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Figure 1-6 Remote mount electronics assembly with clamped band shrouds A. B. C. A. Explosion-proof transmitter enclosure (CPU Module, Power Supply, I.S. Barrier Board, Backplane board, and optional LCD Board with glass endcap) B. Intrinsically-safe base enclosure includes Acquisition Module C.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 1: Introduction 3-9000-765 Rev H May 2015 Figure 1-7 Remote mount electronics assembly with split shrouds A. B. C. D. E. A. Explosion-proof transmitter enclosure (CPU Module, Power Supply, I.S. Barrier Board Backplane board, optional LCD Board with glass endcap) B. Intrinsically-safe base enclosure includes Acquisition Module C. Acquisition cable conduit D. Junction box E.
Section 1: Introduction Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Figure 1-8 Optional local display and glass endcap The Daniel 3812 Liquid Ultrasonic Flow Meter is a two-path (four transducers) in-line meter designed to measure the difference in signal transit time with and against the flow across one or more measurement path(s). A signal transmitted in the flow direction travels faster than one transmitted against the flow direction.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 1: Introduction 3-9000-765 Rev H 1.6 May 2015 Meter specifications ESCAPING FLUIDS HAZARD The purchaser of the meter is responsible for the selection of Daniel components/seals and materials compatible with the chemical properties of the measurement fluid. Failure to select suitable meter components/seals may cause escaping fluids, resulting in injury or equipment damage.
Section 1: Introduction Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Table 1-2 Meter specifications Meter Performance (continued) Flange types ANSI classes - 150, 300, 600 and 900 Raised face or RTJ 0.35 to 1.50 Accuracy limits typically are: • ± 2% without a flow calibration, ± 0.3% with flow calibration • Specific Gravity Accuracy Limits Minimum operating pressure • • 0 psig 0 barg Electronic specifications Power Meter • 10.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 1: Introduction 3-9000-765 Rev H May 2015 Table 1-2 Meter specifications Communications specifications Connectivity protocols One serial RS-232/RS-485 port (115 kbps baud rate) (Modbus RTU/ASCII) (1) Serial Port A (RS-232/RS-485 Full Duplex/RS-485 Half Duplex) One Ethernet Port (TCP/IP) 100 BaseT • Modbus TCP FloBoss 103, FloBoss S600 flow computer, ROC 107 • Device compatibility Digital, analog, and frequency inputs Digital Input(
Section 1: Introduction Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Table 1-2 Meter specifications Digital, analog, and frequency outputs Frequency/Digital Output(s) The meter has user-configurable selections for either a frequency output or Digital status (FODO) (Also see Section 3.6.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 1: Introduction 3-9000-765 Rev H 1.7 1.8 May 2015 Pre-installation considerations • Pipeline equipment code compliance, ANSI, ASME, etc. • Proper Inlet/outlet meter tube piping for reasonable stable flow to the settling chamber (first meter tube spool upstream of the meter). • Electrical safety compliance; UL, CSA, ATEX, IECEx etc.
Section 1: Introduction Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Daniel 3810 Series Liquid Ultrasonic Meters are INMETRO certified. Refer to the 3810 Series Liquid Ultrasonic Flow Meter Tag, INMETRO Certification drawing DMC - 006173. Certificate number: NCC 11.0163 X Marking: --Ex d ia IIB T4 Gb IP66 W Electrical parameters: Refer to Section 1.6, Table 1-2.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 1: Introduction 3-9000-765 Rev H 1.9 May 2015 Daniel 3812 Certifications and Approvals Daniel 3810 Series Liquid Ultrasonic Flow Meters have electrical, metrology, intrinsic safety and Pressure Equipment Directive certifications, approvals and lab testing and calibration certifications by the agencies listed below.
Section 1: Introduction May 2015 20 Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H FCC compliance
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 2: Mechanical installation 3-9000-765 Rev H May 2015 Section 2: Mechanical installation 2.1 Meter piping, lifting and mounting Refer to the following sections for piping recommendations, lifting with hoist rings and slings, mounting in heated or cooled pipelines and safety warnings and precautions. SURFACE TEMPERATURE HAZARD The meter body and piping may be extremely hot or cold.
Section 2: Mechanical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H CRUSHING HAZARD Do not remove flange stabilizers. Attempting to do so may allow the meter to roll, resulting in serious injury or equipment damage. A. A. Flange stabilizers ESCAPING FLUIDS HAZARD The purchaser of the meter is responsible for the selection of Daniel components/seals and materials compatible with the chemical properties of the measurement fluid.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 2: Mechanical installation 3-9000-765 Rev H May 2015 Meter components FLUID CONTENTS MAY BE UNDER PRESSURE When the meter is under pressure, DO NOT attempt to remove or adjust the transducer housing. Attempting to do so may release pressurized fluid, resulting in serious injury or equipment damage. FLUID CONTENTS MAY BE HAZARDOUS The meter must be fully depressurized and drained before attempting to remove the transducer housing.
Section 2: Mechanical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Daniel Liquid Ultrasonic Flow Meters are assembled, configured, and tested at the factory. The meter components include the transmitter electronics enclosure, the base electronics enclosure, the meter body with shroud covers for the transducers and cable assemblies and a direct or remote mount option. Figure 2-1 Direct mount meter electronics assembly with split shroud A. B. C.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 2: Mechanical installation 3-9000-765 Rev H May 2015 Figure 2-2 Remote mount meter electronics assembly with split shroud A. B. C. D. E. A. Remote mount explosion-proof transmitter enclosure (CPU Module, Power Supply, I.S. I.S. Barrier Board, Backplane Board and optional LCD Display Board) B. Intrinsically-safe base enclosure includes Acquisition Module C. Acquisition cable conduit D.
Section 2: Mechanical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Figure 2-3 Direct mount meter electronics with bolted band shrouds A. B. C. A. Explosion-proof transmitter enclosure (CPU Module, Power Supply, I.S. Barrier Board, Backplane Board and optional LCD Board with glass endcap) B. Intrinsically-safe base enclosure includes Acquisition Module C.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 2: Mechanical installation 3-9000-765 Rev H May 2015 Figure 2-4 Direct mount meter electronics assembly with clamped band shrouds A. B. C. A. Explosion-proof transmitter enclosure (CPU Module, Power Supply, I.S. Barrier Board and Backplane Board) B. Intrinsically-safe base enclosure includes Acquisition Module C.
Section 2: Mechanical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 2.2 3-9000-765 Rev H Piping recommendations BURST HAZARD Before pipeline cleaning and maintenance (“pigging operations”), remove straightening vanes or flow conditioners. Failure to do so may cause excessive pressure in the meter system, resulting in serious injury/ death or equipment damage.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 2: Mechanical installation 3-9000-765 Rev H May 2015 Sunshields, provided by the customer, may be required to prevent exceeding the process fluid temperature when the meter is mounted in a location with extremely hot climates. SUNSHIELD PROTECTION Install a sunshield to prevent prolonged exposure to direct sunlight in extreme climates.
Section 2: Mechanical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Figure 2-6 Piping recommendations bidirectional flow All pipe lengths are minimum: • D = Nominal pipe size in inches (i.e. 6" pipe size; 10 D = 60 in) • P = Pressure measurement location • T = Temperature measurement location Refer to the ultrasonic meter product data sheet for piping information.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 2: Mechanical installation 3-9000-765 Rev H May 2015 Meter tube dimensions with tube bundle or profiler plate for uni-directional and bi-directional flow, the minimum straight pipe length is as follows: Table 2-2 Piping recommendation for uni-directional or bi-directional flow UniDirectional Flow BiDirectional Flow 8D up stream (with a flow conditioner) 8D up stream (with a flow conditioner) 8D up stream (no flow conditioner) 8D u
Section 2: Mechanical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 2.3 3-9000-765 Rev H Meter safety for hoist rings and lifting slings A Daniel Ultrasonic Meter can be safely lifted and maneuvered into and out of a meter run for installation or service by obeying the following instructions.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 2: Mechanical installation 3-9000-765 Rev H May 2015 When lifting a Daniel Ultrasonic Meter by itself, Daniel recommends two methods. These methods are: • Using appropriately rated Safety Engineered Swivel Hoist Rings installed in the Daniel Ultrasonic Meter end flanges. • Using appropriately rated lifting slings positioned at designated areas of the Daniel Ultrasonic Meter.
Section 2: Mechanical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Figure 2-8 Safety approved hoist ring and non-compliant eye bolt Safety engineered swivel hoist ring Eye bolt Safety precautions using safety engineered swivel hoist rings Read and follow the Safety Precautions listed below: 34 1. Meters must only be lifted by personnel properly trained in the safe practices of rigging and lifting. 2.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H Section 2: Mechanical installation May 2015 8. Always use separate slings for each hoist ring. NEVER reeve one sling through both hoist rings. The slings must be of equal length. Each sling must have a load rating that equals or exceeds the hoist ring load rating. The angle between the two slings going to the hoist rings must never exceed 90 degrees or the load rating of the hoist rings will be exceeded.
Section 2: Mechanical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H 9. Direct mount option: NEVER allow the slings to contact the electronics enclosure. Damage to the enclosure may occur. Use a spreader bar with the slings to prevent contact with the electronics enclosure and the base enclosure (see Figure 2-11).
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 2: Mechanical installation 3-9000-765 Rev H May 2015 10. Remote mount option: Always use separate slings for each hoist ring. NEVER reeve one sling through both hoist rings. The slings must be of equal length. Each sling must have a load rating that equals or exceeds the hoist ring load rating. The angle between the two slings going to the hoist rings must never exceed 90 degrees or the load rating of the hoist rings will be exceeded.
Section 2: Mechanical installation May 2015 38 Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H 11. NEVER apply shock loads to the meter. Always lift the meter gradually. If shock loading ever occurs, the hoist ring must be inspected per manufacturer's recommendations prior to be placed in any further service. If a proper inspection cannot be performed, discard the hoist ring. 12.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 2: Mechanical installation 3-9000-765 Rev H May 2015 How to obtain safety engineered swivel hoist rings A list of approved manufacturers of safety engineered hoist rings is below: • American Drill Bushing Company(www.americandrillbushing.com) • Carr Lane Manufacturing Company (www.carrlane.com) Select an approved supplier from the list below. These vendors can supply the safetyengineered hoist rings.
Section 2: Mechanical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 2.3.2 3-9000-765 Rev H Appropriately rated lifting slings The following instructions are intended to provide general guidelines for proper lifting slings of the Daniel 3812 Ultrasonic meter by itself. These instructions are intended to be followed in addition to your company's standards or the DOE-STD-1090-2004 Hoisting and Rigging standard if such company standards do not exist.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H Section 2: Mechanical installation May 2015 3. NEVER attempt to lift the meter using only one sling around the meter. Always use two slings wrapped around each end of the body as shown below. A choker style sling is recommended using a spreader bar. Figure 2-11 Correct sling attachment 4. Visually inspect the slings prior to use for any signs of abrasion or other damage.
Section 2: Mechanical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H 6. NEVER allow the slings to contact the electronics enclosure or the transducer shrouds. Damage to the meter may occur. If the slings do come in contact with the electronics or the shroud, temporarily remove the head from the meter during the lifting operation (remove the four bolts holding the enclosure to its base and unplug the cable from the Acquisition Module.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 2: Mechanical installation 3-9000-765 Rev H 2.4 May 2015 Mounting requirements in heated or cooled pipelines The ambient operating temperature of the 3812 Liquid Allocation electronics (i.e. Flameproof enclosure and Intrinsically safe base enclosure) is -40 oC to +60 oC (-40 oF to +140 oF).
Section 2: Mechanical installation May 2015 44 Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H Mounting requirements in heated or cooled pipelines
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 3: Electrical installation 3-9000-765 Rev H May 2015 Section 3: Electrical installation 3.1 Cable length TTL mode The maximum cable length is 2000 feet when the “TTL” mode is selected. 3.2 Cable length Open Collector mode For the “open collector” mode, the maximum cable length depends on the cable parameters, pull-up resistance used, the maximum frequency to output, and frequency input parameters being driven.
Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3.3 3-9000-765 Rev H Grounding meter electronics housing Daniel 3812 Liquid Ultrasonic Flow Meter electronics should be internally grounded for intrinsically safe operations. Connect a wire to the chassis ground lug installed inside the Transmitter Electronics Enclosure as the primary ground. A secondary ground is located outside of the Transmitter Electronics Enclosure (see Figure 3-2).
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 3: Electrical installation 3-9000-765 Rev H May 2015 Figure 3-2 External ground lug A. A. External ground lug 3.4 Conduit seals Daniel 3812 Liquid Ultrasonic Flow Meters require conduit seals for installations in hazardous environments. Adhere to safety instructions to protect personnel and equipment. HAZARDOUS VOLTAGE INSIDE Do not open the Transmitter Electronics Enclosure when an explosive gas atmosphere is present.
Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3.4.1 3-9000-765 Rev H Startup for systems using explosion-proof conduit 1. Assemble flexible conduit (recommended by Daniel) to the Transmitter Electronics Enclosure. A conduit seal fitting is required within 18 inches (457 mm) of the enclosure. 2. Check to make certain that all power to field wiring is turned OFF.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 3: Electrical installation 3-9000-765 Rev H 3.4.2 May 2015 Startup for systems that use flame-proof cable HAZARDOUS VOLTAGE INSIDE Do not open the Transmitter Electronics Enclosure when an explosive gas atmosphere is present. Disconnect equipment from supply circuit before opening. Failure to remove power may result in serious injury or death. 1. Check to make certain that all field wiring power is turned OFF. 2.
Section 3: Electrical installation May 2015 3.5 Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H Wiring and I/O Daniel MeterLink uses the TCP/IP protocol to communicate with the 960-24™ MSTS electronics instead of Modbus ASCII or RTU. The TCP/IP protocol only works across either Ethernet, RS-485 full duplex (i.e., 4-wire), or RS-232. Daniel MeterLink can communicate with multiple meters if they are multi-dropped using 4-wire full duplex RS-485 mode.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 3: Electrical installation 3-9000-765 Rev H 3.5.1 May 2015 CPU Module labeling and LED indicators The meter’s metrology mode and the status of the data transfer from the Acquisition Module to the CPU Module is indicated via light-emitting diode (LED) status indicators. The Write PROT. switch protects the meter’s configuration, Figure 3-3 CPU Module labeling and LED indicators G. F. C. D. E. B. A. A.
Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Table 3-2 CPU Module labeling and LED functions CPU Module switch Function WRITE PROT. • • DHCP • • • PORT A • • • • MEAS Write-protect mode - with switch in the ON position (default setting) protects configuration and firmware overwrites.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 3: Electrical installation 3-9000-765 Rev H May 2015 Ethernet communications The Ethernet port IP address, subnet mask, and gateway address are software-configurable. In addition, a meter can be configured to act as a DHCP (Dynamic Host Configuration Protocol) server to assign an IP address to a PC or laptop running Daniel MeterLink. The DHCP server facility is not intended to act as a general purpose DHCP server for a wider network.
Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Serial connections Use serial cable (Daniel P/N 3-2500-401) to connect to a PC running Daniel MeterLink. The cable is designed for RS-232 communications which is the serial Port A default configuration (see Appendix A field wiring diagram, Daniel Drawing DMC - 005558). The DB-9 end of the cable plugs directly into the PC running Daniel MeterLink.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 3: Electrical installation 3-9000-765 Rev H May 2015 Figure 3-4 PC to meter serial connection wiring DB-9 Connector Female RX TX COM 3.6 I/O connections The meter provides the I/O connections on the CPU Module. Figure 3-5 CPU Module I/O connections A. B. C. D. A. Frequency/Digital Output 2 B. Frequency/Digital Output 3 C. Analog Output 2, 4-20mA output D.
Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3.6.1 3-9000-765 Rev H Frequency/Digital outputs The meter has three user-configurable selections for configuring either a Frequency output or Digital output (FODO).
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 3: Electrical installation 3-9000-765 Rev H May 2015 Frequency or Digital Outputs (FODO 3) source • FO1A, DO1A, FO1B, DO1B, FO2A, DO2A, FO2B, DO2B • FO1A, DO1A, FO1B, DO1B, FO2A, DO2A, FO2B, DO2B • Frequency output 1A is based on frequency content (Actual - Uncorrected Flow Rate) • Frequency output 1B is based on frequency content and Frequency 1B Phase • Frequency output 2A is based on frequency content (Actual - Uncorrected
Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Maximum frequency for the frequency outputs • 1000Hz • 5000Hz Table 3-5 Frequency/Digital Outputs possible configurations Frequency/Digital output Frequency /Digital Output 11 Frequency /Digital Output 22 or Frequency /Digital Output 32 Source configuration • • • • Frequency output 1A Frequency output 1B Digital output 1A Digital output 1B • • • • • • • • Frequency output 1A
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 3: Electrical installation 3-9000-765 Rev H May 2015 Output for FODO1 and Digital Output1 (Group 1 on the CPU Module) share a common ground and have 50V isolation. FODO2 and FODO3 (Group 2 on the CPU Module) share a common ground and have 50V isolation. This allows an output to be connected to a different flow computer. The outputs are opto-isolated from the CPU Module and have a withstand voltage of at least 500V rms dielectric.
Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3.6.2 3-9000-765 Rev H Analog input settings The 960-24™ MSTS has the capability to sample analog temperature (Analog Input 1) and pressure (Analog Input 2) with 4-20 mA signals. These analog input signals are configured to sink. The two independent analog input circuits are configured for conventional 4-20 mA service.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 3: Electrical installation 3-9000-765 Rev H 3.6.6 May 2015 Configuration protect switch settings The meter’s configuration parameters and firmware can be protected against changes via CPU Module Write PROT. switch as follows: Table 3-7 Configuration protect switch settings CPU Module switch Configuration protected Configuration unprotected WRITE PROT.
Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3.7 3-9000-765 Rev H Security seal installation Security seals protect the integrity of the meter metrology and prevent tampering with transducer assemblies. The following sections detail how to properly seal the Daniel 3812 Liquid Ultrasonic Flow Meter after commissioning. The security seal wires are commercially available. CUTTING HAZARD Sharp edges may be present on the band shrouds.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 3: Electrical installation 3-9000-765 Rev H May 2015 Procedure 1. Rotate the end cap clockwise fully closing and compressing the end cap seal. Install the Security latch using a 3mm Allen wrench. 2. Install the security seal wire into and through one of the two holes in the end cap. Choose holes that minimize counterclockwise rotation of the end cap when the security wire is taut (maximum wire diameter .078 inch; 2.0mm).
Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3.7.2 3-9000-765 Rev H Base Enclosure Security Seals Use the following instructions to install the security seal wire on the Base Enclosure. Procedure 1. Install security wire seal into and through two of the four the holes in the socket head screws on the Base Enclosure cover (maximum wire diameter .078 inch; 2.0mm). Figure 3-10 Base Enclosure security seals A. B. A. Base Enclosure B.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 3: Electrical installation 3-9000-765 Rev H 3.7.3 May 2015 Seal the Junction Box remote mount electronics option Use the following instructions to install the security seal wire on the junction box, if required. Procedure 1. Install security wire seal into and through two of the four the holes in the socket head screws on the Junction Box cover (maximum wire diameter .078 inch; 2.0 mm).
Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3.7.4 3-9000-765 Rev H Bolted band shroud security seals If required, use the following instructions to install bolted band shrouds security wire seals. Figure 3-12 Bolted band shroud security seals - bottom view A. B. C. A. Band shroud B. Left front shroud bolt 1/4”- 20 C. Left back shroud bolt 1/4”- 20 D. Right back shroud bolt 1/4”- 20 E. Right front shroud bolt 1/4”- 20 66 D. E.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 3: Electrical installation 3-9000-765 Rev H May 2015 Procedure 3.7.5 1. Beneath the meter, install the security wires into and through the left front bolt (Item B) and feed through the holes in the right back bolt (Item D). 2. Repeat wire installation through the right front bolt (Item E) to the left rear bolt (Item C) as shown in Figure 3-12. The maximum wire diameter .078 inch; 2.0 mm. 3.
Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3.7.6 3-9000-765 Rev H Split shroud security seals Use the following instructions to install the security seal wires on the split shroud covering the meter body and transducer assemblies. Figure 3-14 Split shroud security seals A. B C. D A. B. C. D. Upper split shroud Split shroud clamp Security wire seals Lower split shroud Procedure 68 1.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H 3.7.7 Section 3: Electrical installation May 2015 Latched band shroud security seals Use the following instructions to install the security seal wires on the latched band shrouds covering the meter body and transducer assemblies. Figure 3-15 Latched band shroud assembly A. B. C. D. E. F. A. Band shroud B. Stainless steel strike C. Transducer cable D. Meter body recess for pop rivet allowance E. Meter body shoulder F.
Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Procedure 1. Install the security seal wire into and through the holes in one of the shroud latches (maximum wire diameter .078 inch; 2.0 mm). Figure 3-16 Shroud latch holes for security wire seals A. B. A. Left shroud latch holes for security wire seals B. Right shroud holes for security wires 70 2. Remove all slack and seal. 3. Cut wire ends to remove excess wire. 4.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H 3.7.8 Section 3: Electrical installation May 2015 Seal conduit ports The unit should be properly sealed with a sealing compound after electrical connections have been tested according to the customer's Best Practices schedule. Some areas require a witnessed Acceptance Test for the installed system and require that the meter run for a predetermined length of time (approximately one to two weeks) before the unit is sealed.
Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H 72 Seal conduit ports
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 4: Configuration 3-9000-765 Rev H May 2015 Section 4: Configuration After the mechanical and electrical installation is complete and connectivity is established, use the Daniel MeterLink Software for Gas and Liquid Ultrasonic Meters Quick Start Manual (P/N 3-9000-763) to setup initial communications with the meter. 4.1 Daniel MeterLink setup 1. Review the software operating system, hardware and peripheral requirements. 2.
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 4.2 3-9000-765 Rev H Field Setup Wizard 1. Use the Field Setup Wizard-Startup Page and select the checkboxes that allow proper configuration for your meter (Temperature, Pressure, Meter Corrections, and Meter Outputs). Selections on this page will affect other configuration selections. Select Next to continue to General setup. 2. On General setup page configure the meter’s system units (U.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 4: Configuration 3-9000-765 Rev H May 2015 Display Items The valid labels, descriptions and units for the shown below: Table 4-1 Local display labels, descriptions and valid units Local Display labels, descriptions and units QFLOW — Uncorrected volume flow rate • BBL – Barrels • GAL – Gallons • L – Liters • CM – Cubic Meters • MCM – Thousand Cubic Meters TDYVL — Current day’s forward uncorrected volume • +BBL – Barrels • +GAL – Gallon
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Table 4-1 Local display labels, descriptions and valid units Local Display labels, descriptions and units VEL — Average flow velocity • Ft/S – Feet per second • M/S – Meters per second SOS — Average sound velocity • Ft/S – Feet per second • M/S – Meters per second TEMP — Flow-condition temperature • DEGF – Degrees Fahrenheit • DEGC – Degrees Celsius PRESS — Flow-condition pressure • PSI – Poun
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 4: Configuration 3-9000-765 Rev H May 2015 Display units The Meter volume units displayed are either U.S. Customary or Metric. To modify the Display Units, configure the Meter units system in the Field Setup Wizard — General Page. • • U.S.
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 4.3 3-9000-765 Rev H Using AMS Device Manager to configure the meter This procedure assumes you have AMS Device Manager installed on the host computer and have downloaded the latest Daniel Liquid Ultrasonic Meter Device Description (DD). If not installed, click the link below to download the AMS device installation tool kit. http://www2.emersonprocess.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H Section 4: Configuration May 2015 10. Click the Daniel Industries Liquid 3810 Series Rev 1 hyperlink. The file download dialog displays. Click the Save button to save the files to your host system. You may use the default download location or change the directory. 11. AMS file download options 12. Click the Save button to complete the file download. Figure 4-2 AMS file download complete 13.
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H 17. Click the Configure tab, and then select Guided Setup, Manual Setup or Alert Setup.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H Section 4: Configuration May 2015 AMS Device Manager - Guided Setup The Guided setup wizard provides configuration parameter settings for the meter. The Guided Setup is a subset of the Manual Setup parameters. Figure 4-5 AMS Device Manager - Guided Setup Note: Before writing configuration changes to your meter, make sure you have saved the Configuration file and Maintenance log. Procedure 1.
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H 4. After all of the data shown below is entered, click Apply to write the parameters to the meter. a. b. c. 5. Click Setup HART to configure the HART parameters (tag, date, descriptor, message text, Final Assembly number, Poll address and number of response preambles are displayed). After all of the data is entered click Apply to write the parameters to the meter. 6.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 4: Configuration 3-9000-765 Rev H May 2015 d. Click the All Variables tab to view a graphical display of the Primary, Secondary, Third and Fourth Variables. Figure 4-6 AMS Device Manager - Service Tools All Variables status indicators 8. Click OK to return to the Overview page. 9. Enable the Write Protect switch on the CPU Module to protect the meter’s configuration. 10. From the Overview window, click Display Meter K-Factors.
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H AMS Device Manager - Manual Setup Use the Manual Setup wizard to configure the meter’s parameters. See Figure 4-3 and Figure 4-4 and from the AMS Device Manager Configure menu click Manual Setup. Figure 4-8 AMS Device Manager - Configure Manual Setup Procedure 84 1. If installed, remove security wires from the endcap and the Bracket/Cover hex head bolts that secures the Base Enclosure. 1.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 4: Configuration 3-9000-765 Rev H May 2015 page. Navigate back to the Manual Setup for the changes to be reflected in other Manual Setup pages). Click Apply, after you enter the data to write the parameters to the meter. 7. Click the Frequency and Digital Output 1 tab. Follow the configuration instructions in the AMS Device Manager - Guided Setup, Step 3b. Click Apply, after you enter the data to write the parameters to the meter. 8.
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H b.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 4: Configuration 3-9000-765 Rev H May 2015 – State gated, active low Figure 4-12 Gating configuration parameter State gated, active low High Low Calibration Start 12. Calibration Stop Click the Alert Setup tab (from the main Configuration page).
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H 13. Click the Flow Analysis tab to select Configure Reverse Flow Detection, if desired. The default setting is Disabled. Click the Disabled button to send the feature command to the meter. Check for a response error. If no error response is received, click the Enable button. a. b. c.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H Section 4: Configuration May 2015 14. Click the Service Tools tab to access the device alerts, variables, trends and maintenance statuses or to edit the configuration parameters. a. Click the Service Tools|Alerts tab. If an alert condition exists, the alert type and description displays. Recommended actions are listed to assist you in a resolution.
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H c. Click the Service Tools|Variables tab. The Variables page displays tabs for the device’s Flow Data, Path Information, Flow Totals, and All Variables). Figure 4-16 AMS Device Manager - Service Tools d. e. f. 90 The Service Tools|Flow Data page includes charts for flow and sound velocities.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H Section 4: Configuration May 2015 g. Click Service Tools|Variables|All Variables tab to view Primary, Secondary, Third and Fourth Variable parameter status. Figure 4-17 AMS Device Manager - Service Tools All Variables Gauges display each variable’s status as good or bad. If a status is bad refer to the Service Tools Alerts page for recommended actions to resolve the alert condition.
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H h. Click the Service Tools|Trends tab to display the device variables (uncorrected volume flow rate, pressure and temperature) trends. Figure 4-18 AMS Device Manager - Service Tools Trends Primary and Secondary variables display real-time uncorrected volume flow rate trends. The third and fourth variables charts displays trends for temperature and pressure. 15.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 4: Configuration 3-9000-765 Rev H 4.4 May 2015 Using a Field Communicator to configure the meter important Follow all guidelines and precautions described in the Field Communicator User Manual and in the 3812 Liquid Ultrasonic Flow Meter documentation when working in a hazardous area.
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Procedure 1. Remove electrical power to the meter. If installed, remove the endcap security latches and seals and then, remove the endcap. 2. Refer to the Field Communicator Users Manual wiring diagrams and commissioning instructions provided with your handheld device. Register the product to activate the end user license. 3. Fully charge the Field Communicator battery prior to use.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 4: Configuration 3-9000-765 Rev H May 2015 5. Wire Analog Input 1 (AI1) and Analog Output 1 (AO1) as shown in Figure 4-20 and Appendix A, drawing DMC-004936. Figure 4-20 Field Communicator wiring diagram for the 3810 Series electronics 6. Use the leads provided with the Field Communicator to connect to your device. 7. Press and hold the Power button on the Field Communicator until the green light blinks. 8.
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 4.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Engineering drawings 3-9000-765 Rev H May 2015 Appendix A: Engineering drawings Appendix A A.
Engineering drawings May 2015 98 Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H Daniel 3812 Liquid Ultrasonic Flow Meter drawings
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Open source licenses 3-9000-765 Rev H May 2015 Appendix B: Open source licenses A Source code for executable files or libraries included in this product is provided per the indicated license in the table below. Hyperlinks to the controlling organization's websites are included in Section B.1 through Section B.4. Table B-1 Open source licences Package File specification License Summary base_libs-1.
Open source licenses Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H Package File specification License Summary strace-4.5.14-1 strace BSD trace system calls associated with a running pro sysconfig-1.2-1 sysconfig GPL System configuration package sysfsutils-2.1.0-1 sysfsutils GPL/LGPL sysfs utilities tcpdump-3.8.3-1 tcpdump BSD A network traffic monitoring tool termcap-1.2-1 termcap BSD minimal /etc/termcap needed by minicom etc u-boot-1.3.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H Open source licenses May 2015 The GNU General Public License (GPL) Version 2, June 1991 Copyright (C) 1989, 1991 Free Software Foundation, Inc. 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA Everyone is permitted to copy and distribute verbatim copies of this license document, but changing it is not allowed. Preamble The licenses for most software are designed to take away your freedom to share and change it.
Open source licenses Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H For example, if you distribute copies of such a program, whether gratis or for a fee, you must give the recipients all the rights that you have. You must make sure that they, too, receive or can get the source code. And you must show them these terms so they know their rights.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Open source licenses 3-9000-765 Rev H May 2015 TERMS AND CONDITIONS FOR COPYING, DISTRIBUTION AND MODIFICATION 0. This License applies to any program or other work which contains a notice placed by the copyright holder saying it may be distributed under the terms of this General Public License.
Open source licenses Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H 2. You may modify your copy or copies of the Program or any portion of it, thus forming a work based on the Program, and copy and distribute such modifications or work under the terms of Section 1 above, provided that you also meet all of these conditions: a) You must cause the modified files to carry prominent notices stating that you changed the files and the date of any change.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Open source licenses 3-9000-765 Rev H May 2015 In addition, mere aggregation of another work not based on the Program with the Program (or with a work based on the Program) on a volume of a storage or distribution medium does not bring the other work under the scope of this License. 3.
Open source licenses May 2015 Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H If distribution of executable or object code is made by offering access to copy from a designated place, then offering equivalent access to copy the source code from the same place counts as distribution of the source code, even though third parties are not compelled to copy the source along with the object code. 4.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual 3-9000-765 Rev H Open source licenses May 2015 Program by all those who receive copies directly or indirectly through you, then the only way you could satisfy both it and this License would be to refrain entirely from distribution of the Program.
Open source licenses Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H conditions either of that version or of any later version published by the Free Software Foundation. If the Program does not specify a version number of this License, you may choose any version ever published by the Free Software Foundation. 10.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Open source licenses 3-9000-765 Rev H May 2015 How to Apply These Terms to Your New Programs If you develop a new program, and you want it to be of the greatest possible use to the public, the best way to achieve this is to make it free software which everyone can redistribute and change under these terms. To do so, attach the following notices to the program.
Open source licenses Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H The hypothetical commands `show w' and `show c' should show the appropriate parts of the General Public License. Of course, the commands you use may be called something other than `show w' and `show c'; they could even be mouse-clicks or menu items--whatever suits your program.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Open source licenses 3-9000-765 Rev H B.2 May 2015 GNU Lesser General Public License GNU LESSER GENERAL PUBLIC LICENSE Version 3, 29 June 2007 Copyright © 2007 Free Software Foundation, Inc. Everyone is permitted to copy and distribute verbatim copies of this license document, but changing it is not allowed.
Open source licenses Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H The "Corresponding Application Code" for a Combined Work means the object code and/or source code for the Application, including any data and utility programs needed for reproducing the Combined Work from the Application, but excluding the System Libraries of the Combined Work. 1. Exception to Section 3 of the GNU GPL.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Open source licenses 3-9000-765 Rev H May 2015 4. Combined Works.
Open source licenses Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 3-9000-765 Rev H 5. Combined Libraries.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Open source licenses 3-9000-765 Rev H B.3 May 2015 BSD Open Source License For more details about the Open SourceTM BSD license or the Open Source Initiative, follow the link below: http://www.opensource.org/licenses/bsd-license.php Copyright (c) , All rights reserved.
Open source licenses Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 B.4 3-9000-765 Rev H M.I.T License For more details about the Open SourceTM MIT license or the Open Source Initiative follow the link below: http://www.opensource.org/licenses/mit-license.
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Index 3-9000-765 Rev H Appendix C Index C.1 Manual Index A Acronyms, abbreviations and definitions .........................3 AMS Device Manager - Manual Setup ..............................84 AMS™ Suite Device Manager ................................................3 Analog input switch settings .....................................................60 output switch settings ..................................................
Index Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual May 2015 incorrect sling attachment42 safety precautions using swivel hoist rings34 Split shroud security seals68, 69 swivel hoist rings33 90 degree angle between slings35 Meter specifications13 analog Input(s)15 analog output(s)16 connectivity15 Digital Input(s)15 frequency output/digital outputs16 power14 temperature14 transducers14 Meter tube considerations bi-directional flow30 piping unidirectional flow29 MMU4 Mounting in heated or c
P/N 3-9000-765 Rev H 2015 Daniel Measurement and Control, Inc. 11100 Brittmoore Park Drive Houston, TX 77041 USA T+1 713-467-6000 F+1 713-827-4805 USA Toll Free 1 888-356-9001 Daniel Measurement Services, Inc. T +1 713-827-6314 www.Daniel.com Europe: Stirling, Scotland, UK T + 44-1786-433400 Middle East: Africa: Dubai, UAE T +971-4-811-8100 Asia Pacific: Singapore T +65-677-8211 This product is a core component of the PlantWeb digital plant architecture. © 2015 Daniel Measurement and Control, Inc.