2 --- 1 0Settings
Engine Exerciser Settings
Unless otherwise specified on the order, the controller engine exerciser settings
are set at the factory to the default values. If a setting must be changed, follow the
procedure on the next page. Some settings may require a password (if the
controllerissetupforone).
Any indiscriminate change in these settings may affect the normal
operation of the Automatic Transfer Switch. This change could allow
the load circuits to remain connected to an inadequate source
Parameter Default Setting Adjustment Range
Display Screen
(see next page)
month JAN
JAN, FEB, MAR,
APR, MAY, JUN, JUL,
AUG, SEP, OCT,
NO V, DEC
PRESENT DATE/TIME
Date
day 1 1to31
PRESENT DATE/TIME
Date
year * 1 00 to 99
PRESENT DATE/TIME
Date
hour 1 0to23
PRESENT DATE/TIME
Time
minute 1 0to59
PRESENT DATE/TIME
Time
engine exerciser enable
(P1 to P7)
no yes or no
P1 ENGINE EXERCISER
Enable
engine exerciser t ransfer load
(P1 to P7)
no yes or no
P1 ENGINE EXERCISER
wLoad
engine exerciser start hour
(P1 to P7)
0 0to23
P1 ENGINE EXERCISER
Start h
engine exerciser start minute
(P1 to P7)
0 0to59
P1 ENGINE EXERCISER
Start min
engine exerciser run week
(P1 to P7)
all
all, alternate,
first, second, third,
fourth, or fifth
engine exerciser run day
(P1 to P7)
SUN
SUN, MON, TUE,
WED, THU, FRI, SAT
engine exerciser duration hours
(P1 to P7)
0 0to23
P1 ENGINE EXERCISER
Run TIme h
engine exerciser duration minutes
(P1 to P7)
0 0to59
P1 ENGINE EXERCISER
Run TI me min
* For the year 2000, enter 00.