Data Sheet

Regulator Tips
22
All regulators should be installed and used in accordance with federal, state, and local codes and regulations.
PRESSURE
•  Adequate  overpressure  protection  should  be  installed 
to protect the regulator from overpressure. Adequate
overpressure protection should also be installed to
protect all downstream equipment in the event of
regulator failure.
•  Downstream  pressures  significantly  higher  than  the 
regulator’s pressure setting may damage soft seats and
other internal parts.
•  When a regulator appears unable to pass the published
flow rate, be sure to check the inlet pressure measured
at the regulator body inlet connection. Piping up to
and away from regulators can cause significant flowing
pressure losses.
•  When adjusting setpoint, the regulator should be flowing 
at least five percent of the normal operating flow.
•  Droop is the reduction of outlet pressure experienced by 
pressure reducing regulators as the flow rate increases. It
is stated as a percent, in inches of water column (mbar)
or in pounds per square inch (bar) and indicates the
difference between the outlet pressure setting made
at low flow rates and the actual outlet pressure at the
published maximum flow rate. Droop is also called offset
or proportional band.
•  Downstream  pressure  always  changes  to  some  extent 
when inlet pressure changes.
•  A disk with a cookie cut appearance probably means you 
had an overpressure situation. Thus, investigate further.
SPEED OF RESPONSE AND ACCURACY
•  If two or more available springs have published pressure 
ranges that include the desired pressure setting, use the
spring with the lower range for better accuracy.
•  Direct-operated regulators generally have faster response 
to quick flow changes than pilot-operated regulators.
•  Speed of regulator response, in order: 
- Direct-operated
- Two-path pilot-operated
- Unloading pilot-operated
- Control valve
Note: Although direct-operated regulators give the fastest
response, all types provide quick response.
•  The  full  advertised  range  of  a  spring  can  be  utilized 
without sacrificing performance or spring life.
SIZING
•  The recommended selection for orifice diameters is the 
smallest orifice that will handle the flow.
•  Regulator body size should never be larger than the pipe 
size.  In many cases, the regulator body is one size smaller 
than the pipe size.
•  Do  not  oversize  regulators.  Pick  the  smallest  orifice 
size  or  regulator  that  will  work.  Keep  in  mind  when 
sizing  a  station  that  most  restricted  trims  that  do  not 
reduce the main port size do not help with improved low 
flow control.
•  Most  soft-seated  regulators  will  maintain  the  pressure 
within  reasonable  limits  down  to  zero  flow.  Therefore,
a  regulator  sized  for  a  high  flow  rate  will  usually  have 
a turndown ratio sufficient to handle pilot-light loads
during off cycles.
•  Do not undersize the monitor set. It is important to realize 
that the monitor regulator, even though it is wide-open,
will require pressure drop for flow. Using two identical
regulators in a monitor set will yield approximately
70 percent of the capacity of a single regulator.
TEMPERATURE
•  Most  regulators  shown  in  this  handbook  are  generally 
suitable for temperatures to 180°F / 82°C. With high
temperature Fluorocarbon (FKM) (if available), the
regulators can be used for temperatures to 300°F /
149°C. Check the temperature capabilities to determine
materials and temperature ranges available. Use stainless
steel diaphragms and seats for higher temperatures, such
as steam service.
•  For every 15 psid / 1.0 bar, differential pressure differential 
across the regulator, expect approximately one degree
drop in gas temperature due to the natural refrigeration
effect.  Freezing  is  often  a  problem  when  the  ambient 
temperature is between 30°F / -1°C and 45°F / 7°C.