Data Sheet

33
CommerCial/industrial direCt-operated HigH-pressure regulators
UL
®
Listed Type 627 Constructions
TYPE NUMBER
CAPACITIES
(1)
PROPANE ORIFICE SIZE
INLET AND
OUTLET
CONNECTIONS
OUTLET PRESSURE
RANGE
SETPOINT
MAXIMUM
OPERATING INLET
PRESSURE
BTU / hour SCMH Inch mm psig bar psig bar psig bar
627-5810 6,080,000 68.4
3/8 9.5
3/4-inch FNPT
5 to 20 0.34 to 1.4 10 0.69 250 17.2
627-5810V 6,080,000 68.4
627-6210 10,755,000 121
1/2 13
627-6210V 10,755,000 121
627-7710 10,773,000 121
1-inch FNPT
627-7710V 10,773,000 121
1. For UL listed Type 627 congurations, capacity based on inlet pressure of 30 psig / 1.4 bar Internal registration and 20% droop.
NOTE: Additional spring ranges and body styles available. Ask your LP-Gas Equipment Distributor for additional congurations and for more information.
Type 630 Regulator
TYPE NUMBER
CAPACITIES IN BTU PER
HOUR / SCMH PROPANE
(2)
ORIFICE SIZE
INLET AND
OUTLET
CONNECTIONS
OUTLET PRESSURE
RANGE
SETPOINT
MAXIMUM
OPERATING INLET
PRESSURE
BTU / hour SCMH Inch mm psig bar psig bar psig bar
630-104-78 14,000,000 158 1/2 13 2-inch FNPT 8 to 20 0.55 to 1.4 10 0.69 250 17.2
2. For Non-UL listed Types 627 and 630 congurations, capacity based on inlet pressure 20 psig / 1.4 bar greater than outlet pressure, Internal registration and 20% droop.
NOTE: Additional spring ranges and body styles available. Ask your LP-Gas Equipment Distributor for additional congurations and for more information.
Non-UL listed Type 627 Constructions
TYPE NUMBER
CAPACITIES
(2)
PROPANE ORIFICE SIZE
INLET AND
OUTLET
CONNECTIONS
OUTLET PRESSURE
RANGE
SETPOINT
MAXIMUM
OPERATING INLET
PRESSURE
BTU / hour SCMH Inch mm psig bar psig bar psig bar
627R-117
(3)
10,755,000 121
1/2 13
3/4-inch FNPT
5 to 20 0.34 to 1.4
10 0.69 200 13.8
627M-421
(4)
10,755,000 121 10 0.69 250 17.2
627R-197
(3)
10,773,000 121
1-inch FNPT
10 0.69 200 13.8
627M-471
(4)
10,773,000 121 10 0.69
250 17.2627-497 14,837,000 167
15 to 40 1.0 to 2.8
40 2.8
627-577 20,948,000 235 2-inch FNPT 40 2.8
2. For Non-UL listed Types 627 and 630 congurations, capacity based on inlet pressure 20 psig / 1.4 bar greater than outlet pressure, Internal registration and 20% droop.
3. “R” denotes token relief. Check with your LP-Gas Equipment Distributor on relief capacities.
4. For monitor applications. Standard with blocked throat and external sensing.
NOTE: Additional spring ranges and body styles available. Ask your LP-Gas Equipment Distributor for additional congurations and for more information.