Data Sheet
Bulletin 74.3:ACE97
2
Pad Specications
NPS 1/2, 1, and 2 / DN 15, 25, and 50
(1)
200 psig / 13.8 bar
(1)
200 psig 13.8 bar
(1)
See Table 1
(1)
25 psig / 1.7 bar
200 psig / 13.8 bar
(1)
20 psig / 1.4 bar
(110% of rated C
v
)
C
v
= 0.2 use C
v
= 0.22 C
v
= 7.5 use C
v
= 8.25
C
v
= 0.4 use C
v
= 0.44 C
v
= 10 use C
v
= 11
C
v
= 1 use C
v
= 1.1 C
v
= 20 use C
v
= 22
C
v
= 2 use C
v
= 2.2 C
v
= 45 use C
v
= 50
C
v
= 4 use C
v
= 4.4 C
v
= 60 use C
v
= 66
Depad Specications
NPS 1, 2, 3, and 4 / DN 25, 50, 80, and 100
(1)
See Table 1
C
v
= 3, C
v
= 12, or C
v
= 17
C
v
= 20, C
v
= 35, or C
v
= 70
C
v
= 6, C
v
= 90, C
v
= 115, or C
v
= 140
C
v
= 150, C
v
= 200, or C
v
= 280
General Type ACE97 Specications
External
-20 to 180°F / -29 to 82°C
0 to 212°F / -18 to 100°C
-20 to 212°F / -29 to 100°C
-20 to 212°F / -29 to 100°C
NPS 1/2 and 1 / DN 15 and 25; C
v
= 0.2 and C
v
= 0.4:
316L Stainless steel
NPS 1 and 2 / DN 25 and 50; C
v
= 1 to 4 and C
v
= 5 to 10:
316 Stainless steel
NPS 2 / DN 50; C
v
= 20 to 60:
CF3M/CF8M Stainless steel
316 Stainless steel
316 Stainless steel
316 Stainless steel
stainless steel
Nitrile (NBR), Fluorocarbon (FKM),
Peruoroelastomer (FFKM), or
Ethylenepropylene (EPDM - FDA)
Nitrile (NBR), Fluorocarbon (FKM), or
Ethylenepropylene (EPDM - FDA)
70 pounds / 32 kg
105 pounds / 48 kg
175 pounds / 79 kg
1. The pressure/temperature limits in this Bulletin or any applicable standard limitation should not be exceeded.
The Type ACE97 Pad-Depad valve is a self-contained, pilot-
operated valve that maintains a blanket of inert gas on top of a
stored product to protect it from atmospheric contamination. It
reduces combustibility, decreases vaporization, controls vapor
space pressure during pump-in and pump-out operations, and helps
prevent the tank from entering a vacuum condition and collapsing
upon itself. The Type ACE97 valve provides excellent and accurate
pressure control of the vapor space in the tank. Blanketing pressure
is kept to a minimum in order to conserve the use of blanketing gas.
Pad (Tank Blanketing) – ensures a minimum pressure is maintained
in the tank vapor space during normal operation.
Depad (Vapor Recovery) – limits tank pressure to a maximum value
during normal operation.
Tank and vapor recovery connections are available to meet most
customer requirements. A Single Array Manifold (SAM) provides
a single tank and sensing connection and is required for tanks
having a single nozzle. Accessories include gauges, purge meters,
pressure switches, and check valves.
Type ACE97 valves (NPS 1 / DN 25 and larger)
are pilot-operated for a higher degree of accuracy and control.
A fully balanced valve eliminates setpoint changes
caused by variations in inlet pressure.
Displays pressure of blanketing gas supply
to the blanketing valve.
Low-pressure gauge measures
tank pressure.
Allows for the installation of an alarm system to
indicate either low or high-pressure on the tank.
Provides a visual indication of blanketing gas ow.
Prevents corrosive gases and vapors from
owing back into the blanketing system.
Allows analysis of valve operation in the eld,
simplifying service and reliability. (Only available on NPS 1 and 2 /
DN 25 and 50 pad valve.)