Water/Glycol Systems—Capacities and Dimensions
Liebert
®
Mini-Mate2
16
7.0 WATER/GLYCOL SYSTEMS—CAPACITIES AND DIMENSIONS
Table 5 Water/Glycol data, 60Hz
Evaporator Model (Self-Contained)
MMD14W MMD20W
Condensing Unit Fluid
Water-Cooled Glycol-Cooled Water-Cooled Glycol-Cooled
DX Evaporator- Net Capacity Data - kW (Btu/hr) @ High Speed CFM
80°F DB, 62.8°F WB (26.7°C DB,
17.1°C WB) 38% RH
Total 4.05 (13,800) 3.50 (11,900) 6.40 (21,800) 5.20 (17,800)
Sensible 3.85 (13,100) 3.45 (11,800) 5.80 (19,800) 5.10 (17,400)
75°F DB, 61°F WB (23.9°C DB,
16.1°C WB) 45% RH
Total 3.85 (13,100) 3.30 (11,300) 6.15 (21,000) 5.00 (17,000)
Sensible 3.45 (11,800) 3.10 (10,600) 5.20 (17,700) 4.55 (15,600)
72°F DB, 60°F WB (22.2°C DB,
15.5°C WB) 50% RH
Total 3.80 (12,900) 3.20 (11,000) 6.00 (20,500) 4.85 (16,600)
Sensible 3.15 (10,800) 2.90 (9,800) 4.80 (16,400) 4.10 (14,000)
Fan Data - Evaporator
CFM (CMH) - High Speed 600 (1019) 750 (1274)
CFM (CMH) - Low Speed 480 (816) 600 (1019)
Fan Motor hp (W) 0.2 (149) 0.2 (149)
External Static Pressure, in. (mm) water gauge 0.3 (8) 0.3 (8)
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area ft.
2
(m
2
) 2.44 (0.23) 2.44 (0.23)
Coil Rows 2 3
Max Face Velocity-fpm (m/s) 232 (1.2) 291 (1.5)
Unit Refrigerant Charge, oz. (kg) 27 (0.77) 34 (0.96)
Unit Operating Weight 260 (118) 295 (134)
Electric & SCR Reheat Capacities (Includes Fan Motor)-kW (Btu/hr)
Input Voltage 208-1-60 3.6 (12160) 3.6 (12160)
Input Voltage 230-1-60 4.4 (14875) 4.4 (14875)
Input Voltage 277-1-60 4.8 (16285) 4.8 (16285)
Hot Gas Reheat Capacities - kW (Btu/hr) *
Based on 103°F (39.4°C) return gas temperature 4.7 (16050) 4.7 (16050)
Humidifier Data - Steam Generator Type
Steam capacity - lb./hr (kg/hr) 2.5 (1.14) 2.5 (1.14)
Electrical Input Power - kW 0.88 0.88
Unit Connection Sizes
Water/Glycol Condenser Connection Sizes, in. (mm) OD 1/2 (12.7) 1/2 (12.7)
Humidifier Supply 1/4" OD Cu Compression Fitting 1/4" OD Cu Compression Fitting
Evaporator/Condensate Drain 3/4" NPT-Female 3/4" NPT-Female
MERV 8 Filter, Supply/Return Grille, qty. (1),
Nom. Size - in. (mm)
1x20x20 (25x508x508) 1x20x20 (25x508x508)
MERV 8 Filter, Return Air Filter Box, qty. (1),
Nom. Size - in. (mm)
1x16x20 (25x406x508) 1x16x20 (25x406x508)
Condenser Fluid Requirements
85°F (29.4°C)
EWT
110°F (43.3°C)
EGT - 40% PG
85°F (29.4°C)
EWT
110°F (43.3°C)
EGT - 40% PG
THR - kW (Btu/hr) @ 75°F/45% RH 5.15 (17,500) 4.80 (16,400) 7.85 (26,700) 7.35 (25,000)
Flow Rate - GPM (l/m) 1.5 (5.7) 2.6 (9.9) 3.3 (12.5) 4.6 (17.4)
Pressure Drop - ft. of H
2
0 (kPa) 1.9 (5.7) 5.3 (15.8) 7.0 (20.9) 14.1 (42.2)
Water-Cooled Condensing Temperature 105°F (40.6°C) NA 105°F (40.6°C) NA
Water/Glycol Condenser Loop Volume - gal (l) 0.5 (1.9) 0.5 (1.9)
Free-Cooling Coil Option Net Capacity Data - kW (Btu/hr) using 45°F EWT
80°F DB, 62.8°F WB (26.7°C DB,
17.1°C WB) 38% RH
Total 3.70 (12,600) 2.80 (9,600) 4.25 (14,500) 3.55 (12,100)
Sensible 3.70 (12,600) 2.80 (9,600) 4.25 (14,500) 3.55 (12,100)
75°F DB, 61°F WB (23.9°C DB,
16.1°C WB) 45% RH
Total 3.15 (10,800) 2.35 (8,100) 3.60 (12,300) 3.00 (10,200)
Sensible 3.10 (10,600) 2.35 (8,100) 3.60 (12,300) 3.00 (10,200)
72°F DB, 60°F WB (22.2°C DB,
15.5°C WB) 50% RH
Total 2.85 (9,700) 2.10 (7,200) 3.25 (11,100) 2.65 (9,100)
Sensible 2.75 (9,300) 2.10 (7,200) 3.15 (10,800) 2.65 (9,100)
Flow Rate - GPM (l/m) 2.3 (8.7) 2.6 (9.9) 2.6 (9.9) 4.6 (17.4)
Pressure Drop - ft. water (kPa) 5.2 (15.5) 9.9 (29.6) 6.6 (19.7) 29.0 (86.7)
Free-Cooling Coil - Copper Tube/Aluminum Fin
Face Area ft.
2
(m
2
) 2.44 (0.23) 2.44 (0.23)
Coil Rows 2 2
Max Face Velocity-fpm (m/s) 232 (1.2) 291 (1.5)
Internal Fluid Volume - gal (l) 1.7 (6.4) 1.7 (6.4)
Free-Cooling Coil supply and return connections,
in. (mm) OD
5/8 (15.9) 5/8 (15.9)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45% RH, is the standard rating condition for
ASHRAE 127-2007. All capacities are nominal values; actual performance will be ±5%.
* Hot Gas Reheat operates only during dehumidification. Capacity shown is offset by cooling capacity; cannot be used for space heating and is for reference only.