Technical data

Chilled Water Systems—Capacities and Dimensions
Liebert
®
Mini-Mate2
22
Figure 19 General arrangement—Self-contained chilled water units
Figure 20 General arrangement—Hot water reheat coil, chilled water units
Table 8 Capacity correction factors (based on 10°F (5.6°C) water rise)
EWT
72°F (22.2°C) 50% RH 75°F (23.9°C) 45% RH
TCC SCC TCC SCC
42°F (5.6°C) 1.30 1.14 1.25 1.11
43°F (6.1°C) 1.19 1.10 1.17 1.07
44°F (6.7°C) 1.09 1.05 1.08 1.04
45°F (7.2°C) 1.00 1.00 1.00 1.00
46°F (7.8°C) 0.94 0.95 0.95 0.96
47°F (8.3°C) 0.88 0.89 0.90 0.90
48°F (8.9°C) 0.82 0.82 0.85 0.85
49°F (9.4°C) 0.75 0.75 0.80 0.81
*
*
DPN000167
Rev. 1
Shutoff
Valves**
Hose
Bibs **
* Field piping refers to the use of hard
piping using sweat adapter kit or
precharged line set.
** Components are not supplied by
Emerson, but are recommended for
proper circuit operation and
maintenance.
FIELD PIPING
FACTORY PIPING
Chilled Water
Control Valve
Chilled
Water
Supply
Chilled
Water
Return
Bleed Valve
Chilled Water
Valve
* Components are not supplied by
Emerson, but are recommended for proper
circuit operation and maintenance.
Bleed Valve
Hot Water
Reheat Coil
Hot Water Reheat
Control Valve
Y-Strainer
Water
Supply
Water
Return
Shutoff
Valve *
Hose Bibs *
HOT WATER REHEAT COIL ONLY
AVAILABLE ON CHILLED WATER UNITS
FACTORY PIPING
FIELD PIPING
DPN000169
Rev. 2