Technical data

Guide Specifications for Liebert Mini-Mate2—1- and 1.5-Ton Systems
Liebert
®
Mini-Mate2
42
3.0 EXECUTION
3.1 Installation of Air Conditioning Unit
3.1.1 General
Install air conditioning unit in accordance with manufacturer's installation instructions. Install unit
plumb and level, firmly anchored in location indicated, and maintain manufacturer's recommended
clearances.
3.1.2 Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be factory-
mounted. Furnish copy of manufacturer’s electrical connection diagram submittal to electrical
contractor. Install and wire per local and national codes.
3.1.3 Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory-mounted.
Furnish copy of manufacturer’s piping connection diagram submittal to piping contractor.
3.1.4 Supply and Drain Water Piping
Connect water supply and drains to air conditioning unit. Unit drain shall be trapped internally and
shall not be trapped externally.
3.1.5 Field-Supplied Pan
A field-supplied pan with drain shall be installed beneath ducted cooling units.
3.2 Field Quality Control
Startup air conditioning unit in accordance with manufacturer's start up instructions. Test controls
and demonstrate compliance with requirements.