Instruction manual
Section 3 - Grounding & Isolation  Page 3-3  S1400CW 
ground has been established, it should be tested on a regular basis to preserve system 
integrity. 
Figure 3-2 - Basic Ground Bed Soil Test Setup 
Figure 3-3 - Basic Ground Bed Soil Test Setup with Additional Ground Rods  
Figure 3-2 shows the test setup for ‘Good Soil’ conditions. If the Megger* reads less than 5 
ohms, the ground is good. The lower the resistance, the better the earth ground. If the 