Instruction manual
S1400CW  Page 3-4  Section 3 - Grounding & Isolation 
Megger reads more than 10 ohms, the ground is considered ‘poor.’ If a poor ground is 
indicated, one or more additional ground rods connected 10 feet from the main ground rod 
should be driven into the soil and interconnected via bare AWG 0000 copper wire and 1” x 
¼-20 cable clamps as illustrated in Figure 3-3). * Note: Megger is a Trademark of the 
Biddle Instrument Co. (now owned by AVO International). Other devices that 
may be used to test ground resistance are “Viboground”; Associated Research, 
Inc., “Groundmeter”; Industrial Instruments, Inc., and “Ground-ohmer”; Herman 
H. Sticht Co., Inc. 
If the Megger still reads more than 10 ohms, mix a generous amount of cooking salt, ice 
cream salt or rock salt with water and then pour about 2.5 to 5 gallons of this solution 
around each rod (including the test rods). Wait 15 minutes and re-test the soil. If the test 
fails, the soil is poor and a ‘Poor Soil Ground Bed’ will have to be constructed. 
Figure 3-4 shows a typical Poor Soil Ground Bed Electrode. A Poor Soil Ground Bed will 
typically consists of four or more 10-foot long electrodes stacked vertically and separated by 
earth. Figure 3-5 shows the construction of a Poor Soil Ground Bed. For some poor soil 
sites, the ground bed will be constructed of many layers of ‘Capacitive Couplings’ as 
illustrated. In extremely poor soil sites one or more 3’ by 3’ copper plates (12 gauge or 1/16” 
thick) will have to be buried in place of the electrodes. 
Figure 3-4 - Ground Electrode Construction for Poor Soil Conditions 
3.3.1.3 Dry, Sandy or Rocky Soil 
Very dry soil will not provide enough free ions for good conductance and a single ground rod 
will not be effective. A buried counterpoise or copper screen is recommended for these 
situations. It will be necessary to keep the soil moist through regular applications of water. 
Sandy soil, either wet or dry, may have had its soluble salts leached out by rain water, 
thereby reducing conductivity of the ground. High currents from lightning strikes could also 
melt sand and cause glass to form around the ground rod, rendering it ineffective. A buried 
counterpoise or copper screen is preferred for these installations along with regular 
applications of salt water. 
Rocky soil can pose many grounding problems. A counterpoise or copper plate will probably 
be required. Constructing a trench at the grounding site and mixing the fill with a 
hygroscopic salt such as calcium chloride may help for a time. Soaking the trench with 
water on a regular basis will maintain conductivity. 
Units with phone modems require the use of a lightning arrester. The lightning arrester 
must be situated at the point where the communication line enters the building. 










