Instruction manual
1-20 /Introduction    ControlWaveLP 
FMI/OB Bd. Connectors TB5 - TB8 PC/104 I/O & P3 - P6 I/O Expansion Interface 
FMI/OB Cable Connectors P3, P4, P5 and P6 are provided to interface a PC/104 Expansion 
Board to Expansion I/O Terminal Blocks TB5 through TB8 respectively. Ribbon Cable(s) 
will be used to interconnect a PC\104 Expansion Board to P3, P4, P5 & P6. 
FMI/OB Bd. PC/104 Bus Connectors P7 & P10 (CPU/FMI/OB Interface)
Connections to the ISA bus are available on the PC/104 bus via the CPU/FMI/OB Interface 
Connectors P7 and P10 (J10 of CPU mates with P7 of FMI/OB and J11 of CPU mates with 
P10 of FMI/OB) (see Table 4-10). With the exception of FMI/OB Board signal P10-1 (PFIN*) 
and CPU Board signal J11-1 (PWR_FAIL) all signals are identical. ISA bus signals are 
provided by the RadiSys R400EX system controller on the CPU Board. 
During non-ISA bus cycles, the R400 places the ISA bus into a quiet mode to reduce overall 
power consumption. The external interface to PC/104 cards is level shifted to a 5V bus 
through a set of buffers and transceivers and is capable of driving up to 8 PC/104 cards. 
FMI/OB Bd. Power Supply/Sequencer Bd. (PSSB) Interface Connector P9
Connector P9 is a 20-pin DIP Header that interfaces Power, Ground and power supply 
status signals to Connector J1 on the PSSB Board (see Table 4-11). 
1.3.3.3 FMI/OB Board Jumpers 
The FMI/OB Board contains 52 Configuration Jumpers (situated on the top side of the 
PCB) (see Table 1-10). 
It should be noted that although JP1 appears to be a Jumper Block, it is actually used for 
measuring voltages as follows: 
  +5V - measure between JP1-1(+) and JP1-2(-) 
  +1V - measure between JP1-3(+) and JP1-2(-) 
Table 1-10 - FMI/OB Board Jumper Assignment 
Jumper  Function  Notes 
W1  Config. DI1  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W2  Config. DI2  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W3  Config. DI3  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W4  Config. DI4  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W5  Config. DI5  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W6  Config. DI6  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W7  Config. DI7  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W8  Config. DI8  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W9  Config. DI9  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W10  Config. DI10  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W11  Config. DI11  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W12  Config. DI12  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W13  Config. DI13  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W14  Config. DI14  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W15  Config. DI15  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W16  Config. DI16  see Figure 2-6 (2-3 = Isolated DI)(1-2 & 3-4 = Dry Contact DI) 
W17  DI LEDs  Installed = DI LEDs Enabled 
W18  DO LEDs  Installed = DO LEDs Enabled 
W20A  Config. AI1  see Figure 2-11 