Instruction manual
2-14 / Installation  CI-ControlWaveLP 
Figure 2-7 - Point-to-Point 10Base-T Ethernet Cable 
The maximum length of one segment (CPU to Hub) is 100 meters (328 feet). The use of 
Category 5 shielded cable is recommended. 
Figure 2-8 - Standard 10Base-T Ethernet Cable (CPU Module to Hub) 
Table 2-7 - Ethernet 10/100Base-T CPU Module Pin Assignments 
Pin #  Description  Pin #  Description 
1  Transmit Data+ (Output)  5  Not Connected 
2  Transmit Data- (Output)  6  Receive Data- (Input) 
3  Receive Data+ (Input)  7  Not Connected 
4 Not Connected  8 Not Connected 
Note: TX & RX are swapped at Hub’s. 