Instruction manual
CI-ControlWaveLP  Installation / 2-27 
2.5.2.1 Using LocalView to Upgrade ControlWaveLP Firmware 
NOTE 
Your ControlWaveLP must be set to Recovery Mode ENABLE (ON) prior to 
performing the FLASH upgrade, then set to Recovery Mode DISABLE (OFF) after 
the upgrade. On the ControlWaveLP this is accomplished via CPU Switch SW2-C. 
Also set CPU Switch SW4-3 (OFF) to ignore soft switch configuration and use 
factory defaults; set SW4-3 (ON) after the upgrade. 
A null modem cable (see Figure 2-5) must be connected to COM1 of the ControlWaveLP 
and to any RS-232 port on the associated PC. The PC’s RS-232 port used for this purpose 
must be set to run at 115.2 Kbaud. ControlWaveLP CPU Switch SW2, positions C and D 
must be set ON (see Table 2-3). 
Start LocalView, Choose FLASH, Enter A Name, Click on [Create] 
Start LocalView by clicking on: Start Æ Programs Æ OpenBSI Tools Æ LocalView. The 
New View Mode dialog box will appear (see Figure 2-25). 
"Mode" 
  Choose 'Flash' for the mode. 
"Name" 
  Enter a name for the View Mode File in the "Name" field. 
Figure 2-25 - Local View - New View Mode Menu 
"Location" 
  If you want to store the View Mode File in a directory other than that shown in the 
"Location" field, enter the new location there, or use the [Browse] push button to find 
the directory. 
When the "Mode", "Name", and "Location" have been specified, click on the [Create] push 
button to activate the Communication Setup Wizard (see Figure 2-26). 
Step 1 - Communication Setup 
Complete the fields in the Communication Setup Wizard as described, below. 
"What port would you like to use?" 
  Specify the PC port you would like to use; this would be the port on the PC which will be 
connected to the serial cable, e.g. COM1:, COM2:, etc. 