2-34 / Installation  CI-ControlWaveLP 
Figure 2-34 - HyperTerminal FLASH Download (Download in Process) 
Table 2-15 - PORT 80 - Running Status Codes 
Status LEDs 
1 2 3 4 5 6 
Definition  Notes 
0 0 0 0 0 0  No application   
0 0 0 0 0 1  Application Loaded   
0 1 0 1 0 0  Currently Loading the Boot Project   
1 1 0 1 0 0  System Initialization in Progress   
0 0 0 1 0 1  Application Loaded -with BPT  Break Point(s) Set 
0 0 0 0 1 1  Application Running  Display Blank 
0 0 0 1 1 1  Running with BPT  Break Point in Debug 
0 1 1 0 0 0  Recovery Mode *  SW2-C = ON 
1 0 0 1 0 0  Battery Fail   
0 0 1 0 0 0  System Firmware XSUM error   
1 0 0 0 0 0  Diagnostic Mode  SW4-8 = OFF 
1 1 0 0 0 0  Running Diagnostic   
1 0 1 0 0 0  Error initializing application device   
0 1 1 0 0 0  NPX Error  Unit stopped 
1 1 0 1 1 1  Waiting for Power-down  After NMI 
0 0 0 1 0 0  Factory defaults applied  Flashed at startup 
0 0 0 0 1 0  Waiting for Alt. WD Timer  Control Point error 
0 1 1 1 1 1  Waiting for updump   
1 1 1 0 0 0  FLASH programming error   
1 1 1 1 1 1  Unit crashed   
  * Not an actual Running Status Code - SW2-C should be OFF 
2.5.2.3 Remote Upgrade of ControlWaveLP Firmware 
It is possible to download system firmware into an unattended remote ControlWaveLP. 
This function can only be accomplished if CPU Board Switch SW4-6 (associated with the 
unit in question) is set in the ON position (factory default). The procedure for performing a 