Port PCB Default Configuration
ECOM Type 1 Not applicable
COM6
ECOM Type 2 RS-485; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
ECOM Type 1 Not applicable COM7
ECOM Type 2 RS-485; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
COM8 ECOM Type 1 or Type
2
RS-232; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
ECOM Type 1 RS-485; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
COM9
ECOM Type 2 RS-232; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
ECOM Type 1 Radio port COM10
ECOM Type 2 RS-485; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
ECOM Type 1 Modem port COM11
ECOM Type 2 RS-485; 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol
Note: You can re-enable the factory comm settings at any time by
setting switch 3 on the CPU module’s SW3 to “OFF.”
Ethernet
Using an optional Ethernet port (located on the CPU module), you can
connect either directly or through a network to a PC equipped with an
Ethernet port.
4.3.2 Collecting Data from the ControlWave Micro
OpenBSI utilities such as DataView, Data Array Save/Restore and
Harvester allow you to collect real time data (values of variables, array
values, alarm messages) and historical data (audit records, archive files)
from the ControlWave. See the OpenBSI Utilities Manual (D5081) for
details. SCADA software such as OpenEnterprise can then present this
data to an operator in the form of graphical displays and reports.
4.4 Creating and Downloading an Application (ControlWave Project)
Your ControlWave Micro executes an application called a ControlWave
project. You create the project using PC-based ControlWave Designer
software. Instructions for creating a ControlWave project are beyond the
scope of this manual. Please refer to the following sources for
information:
Getting Started with ControlWave Designer (D5085)
ControlWave Micro Quick Setup Guide (D5124)
ControlWave Designer Programmer’s Handbook (D5125)