Instruction manual

ControlWave Micro Instruction Manual (CI-ControlWave Micro)
Revised May-2011 Service & Troubleshooting 5-17
Port Module Default Configuation
ECOM Type 2 RS-485: 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol.
COM7 ECOM Type 1 Not applicable
ECOM Type 2 RS-485: 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol.
COM8 ECOM Types 1 or
2
RS-232: 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol.
COM9 ECOM Type 1 RS-485: 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol.
ECOM Type 2 RS-232: 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol.
COM10 ECOM Type 1 Radio port
ECOM Type 2 RS-485: 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol.
COM11 ECOM Type 1 Modem port
ECOM Type 2 RS-485: 9600 baud, 8 bits, no parity, 1 stop bit, BSAP or
ControlWave Designer protocol.
You can connect an optional Ethernet port (situated on the CPU
module) directly or via a network to a PC equipped with an Ethernet
port (see Section 2.4.5).
Before starting the WINDIAG program, place any critical processes the
Micro is handling under manual control. You cannot run WINDIAG
while the Micro is running applications. Set the CPU modules switches
SW2-3 and SW2-8 to OFF, and perform the following steps:
1. Start the NetView program in OpenBSI with your current
network NETDEF file. A menu displays (similar to the one in
Figure 5-11):
Figure 5-11. NetView