ControlWave Micro Instruction Manual (CI-ControlWave Micro)
2. Select Start >Programs > OpenBSI Tools >Common Tools >
Diagnostics. The Main Diagnostics menu (Figure 5-12)
displays.
Figure 5-12. WINDIAG Main Diagnostics Menu
3. Select the module to be tested. Enter any prompted parameters
(slot #, etc.). WINDIAG performs the diagnostics and displays
pass/fail results.
4. After performing all diagnostic testing, exit WINDIAG and then
exit the NetView if you don’t have any other Micro units to test.
When you close NetView, the system asks whether you want to
close OpenBSI. Select Yes.
5. Set switch SW2-8 on the CPU module to ON (open). The Micro
should resume normal operation.
5.4.1 Available Diagnostics
Using WINDIAG, you can test all Micro modules with the exception of
the PSSM. WINDIAG’s Main Diagnostics Menu (see Figure 5-12)
provides the following diagnostic selections:
Option Tests
CPU & Peripherals Checks the CPU module (except for RAM &
PROM).
Analog Output Checks AOs on AI/O, AO, or Mixed I/O modules.
High Speed Counter Checks HSCs on HSC or Mixed I/O modules.
Prom/Ram Checks the CPU’s RAM and PROM hardware.
Analog Input Checks AIs on AI/O, AI, or Mixed I/O modules.
Communications Checks Communication ports 1 through 9 (but
5-18 Service & Troubleshooting Revised May-2011