Instruction manual

ControlWave Micro Instruction Manual (CI-ControlWave Micro)
If In Slot #3 - Comm. Port Assignments = 4, 5, 6 & 7
If in Slot #4 - Comm. Port Assi
g
nments = 8, 9, 10 & 11
Comm. Port 7/11
Comm. Port 6/10
Comm. Port
Status LEDs
Comm. Port 5/9
Comm. Port 4/8
RS-232
Comm. Port 5/9
RS-485
Comm. Port 6/10
Radio
Comm. Port 7/11
Modem
Comm. Port 4/8
Transmit LEDs
Receive LEDs
P1
2
J5
J4
O
N
12
3
4
5678
J8
CR1
CR2
CR3
CR4
DCD
DTR
Comm. Port 7/11 LEDs
SW1 - On Reverse Side for
RS-485 Network
Configuration
1
JP3
1
JP6
1
1
1
1
JP2
JP1
JP5
JP4
JP6 - Modem (Factory Default = 2-to-3)
1-to2 Installed = CTS from Modem
2-to-3 Installed = CTS from RTS (Loopback)
JP2
1-to2 Installed = Enable Radio Config. Mode
2-to-3 Installed = Enable Modem Config. Mode
JP1
Installed = MDS Radio (no longer offered)
Removed = FreeWave Radio
JP4
Removed = Modem Power Removed
when DTR goes Inactive
Installed = Power Always ON
JP5 - Radio (Factory Default = 2-to-3)
1-to-2 Installed = CTS from Radio
2-to-3 Installed = CTS from RTS (Loopback)
Installed = LEDs Enabled
Removed = LEDs Disabled
Figure D-1. Expansion Comm. Module Component Identification Diagram
D.1.2 Configuring the FreeWave Radio (FGR09CSU)
To configure a Model FGR09SCU radio (installed on an ECOM
Module), perform the following steps:
1. If required, remove the ECOM Module from the controller.
2. Place the radio into configuration mode by setting ECOM
Module jumper JP2 onto pins 1 and 2. This enables
configuration of the radio through Comm. Port 4 for radio on
Comm. Port 6 (ECOM1) or through COMM. Port 8 for radio on
Comm. Port 10 (ECOM2).
3. Connect a full duplex ControlWave null modem cable (see
Figure D-3) between a PC and Comm. Port 4 (ECOM1) to
D-2 Radio Installation Revised May-2011