Instruction manual
ControlWave Micro Instruction Manual (CI-ControlWave Micro)
4. Open HyperTerminal on the PC and set the PC communication
port settings as follows:
Bits per second: 19200
Data bits: 8
Parity: None
Stop bit: 1
Parity Check: None/Off
Carrier Detect: None/Off
Flow Control: Xon/Xoff
5. Cycle power to the ControlWave Micro/ControlWave EFM. The
FreeWave configuration menu opens in HyperTerminal.
6. In the configuration menu, set the radio as a multipoint slave. Go
to the edit book and type in the serial number of the master radio
to which you want to communicate. Make sure the baud rate
matches that of the master radio. Once you implement the
settings, press the [Esc] key to exit the configuration menu.
7. Set ECOM Module configuration jumper JP2 into a storage
position.
8. Using HyperTerminal at the master radio, inter configuration
mode and set the radio as a multipoint master. Using the edit
book (in configuration mode) make sure that no serial number is
set. Verify that the baud rate matches that of the slave radio.
(Looking into
W
ire Terminal Side
of
Cable Connectors)
3 = TXD
6 = DSR
7 = RTS
8 = CTS
4 = DTR
2 = RXD
1 = DCD
5 = GND
To P2 Pin-4
To P2 Pin-2
To P2 Pin-7
To P2 Pin-3
To P2 Pin-6
To P2 Pin-5
To P2 Pin-1
PC
9-Pin Female
“D” Connector
P1
C
W u
/C
W EFM
9-Pin Female
“D” Connector
P2
3 = TXD
6 = DSR
7 = RTS
8 = CTS
4 = DTR
2 = RXD
1 = DCD
5 = GND
or
vice
versa
Figure D-3. Internal Radio/Modem Configuration P/N 392843-01-3 Full-duplex Null Modem
Cable Diagram
D-4 Radio Installation Revised May-2011