Instruction manual

ControlWave Micro Instruction Manual (CI-ControlWave Micro)
Revised May-2011 Radio Installation D-7
6. Snap the cover panel onto the ECOM Module PCB and insert
the ECOM Module into the appropriate backplane slot, i.e., Slot
3 or 4.
7. Apply power and test the unit.
D2.1.2 Configuring the MultiTech Modem (MT9234SMI)
To configure a model MT9234SMI Modem (installed on an ECOM
Module), perform the following steps:
1. If required, remove the ECOM Module from the controller (see
Figure D1).
2. Place the modem into configuration mode by setting ECOM
Module jumper JP2 onto pins 2 and 3. This enables
configuration of the modem through Comm. Port 4 for modem
on ECOM1 or through COMM. Port 8 for modem on ECOM2.
3. Connect a full duplex ControlWave null modem cable (see
Figure D3) between a PC and Comm. Port 4 (ECOM1) to
configure modem on ECOM1 or Comm. Port 8 (ECOM2) to
configure modem on ECOM2.
4. Open HyperTerminal on the PC and set the PC communication
port settings as follows:
Bits per second: 9600
Data bits: 8
Parity: None
Stop bit: 1
Flow Control: None
Send Factory Default AT&F0.
Disable Flow Control AT&K0.
Set baud rate using AT Command for example:
AT$SB9600,
(Modify for whatever baud rate you require.)
Write to memory AT&W.
5. Set ECOM Module configuration jumper JP2 into a storage
position.