2.5.2 RS-485 Ports
Type 1 ECOMs include one RS-485 port. Type 2 ECOMs include two
RS-485 ports. For information on connecting to these ports, including
cabling information, see Section 2.4.4.
2.5.3 Radio Modem Port (Type 1 ECOM only)
Type 1 ECOMs support an optional piggy-back mounted spread
spectrum radio modem. You can order this factory pre-installed or you
can install it yourself.
The Radio Modem Port is COM6 (if the ECOM is in slot #3) or COM10
(if the ECOM is in slot #4). This option uses the FreeWave
®
Spread
Spectrum Wireless Data Transceiver, operating in the 902 to 982 MHz
range (20-mile range)
If you order it in kit form, you install this radio modem in the Type 1
ECOM. Figure 2-26 shows both radios mounted in the ECOM. After
you install the radio modem in the module and place the module in the
base housing, you configure the ports using the Flash Configuration
utility in NetVew or LocalView.
Installation
Following is the general installation process. For more detailed
directions, refer to Appendix D: Radio/Modem Installation Guide in
this manual. See also Figure 2-23.
1. Attach the radio modem to the Type 1 ECOM.
Note: Depending on the ordering options, the radio modem may
already be attached to the Type 1 ECOM. Alternatively, you
may have to attach it yourself.
2. Attach the RF cable to the radio modem and the ECOM port.
a. Remove the nut and washer from the internal coaxial RF cable
supplied with the ECOM.
b. Remove the plug from the front of the ECOM cover and insert
the internal coaxial RF cable’s SMA connector (straight end
with flat area on top) through the rear of the ECOM cover.
c. Install the washer and nut to secure the internal coaxial RF
cable to the front of the ECOM cover.
d. Install the other end of the internal coaxial RF cable to the
radio’s RF antenna connector.
e. Install the ECOM into slot 3 or 4 of the base housing.
f. Install the user supplied coaxial RF cable between the ECOM
cover’s SMA connector (installed in step a) and the remote
antenna.