Product data

June 2012
CWGFC
12 www.EmersonProcess.com/Remote
Clearance At least 2.5-inch space underneath for cabling
Weight Minimum 4.53 kg (10 lbs.)
Battery + MVT
Assembly
8.39 kg (18.5 lbs.)
Maximum with
Radio
9.07 kg (20 lbs.)
Mounting
This product can be pipe-mounted, wall-mounted or direct-mounted (in the last case,
Emerson recommends PGI Direct Mount manifold products); a kit for affixing to a 2 inches
(5.08 cm) pipe or mast is available.
Solar Panel Mounting
All solar panels are delivered with all hardware necessary for 2 inches (5.08 cm) pipe or
mast-mounting.
Environmental
Wide operating power input
voltage
5.0 to 18.0 Vdc
12 Vdc nominal is required if an internal radio is used
Operating Temperature Range -40 to 158ºF (-40 to 70ºC)
Operating Temperature Range of
Lead Acid Cell Batteries
-4 to 140ºF (-20 to 60ºC)
Operating Humidity 10 to 95% RH non-condensing
Vibration Rating
Maintains proper operation while subjected to a 2.0 g acceleration over 10-150 Hz and
1.0 g acceleration over 150-2000 Hz (ISA Process Mount)
Electrostatic Discharge Meets IEC EN 61000-4-2, EN 61326
RFI Immunity
In conformity with ENV 50140 Radio-frequency electromagnetic field amplitude
modulated EMC
Nema Rating Nema 3R (Nema 4x except with a battery vent)
Approvals
Product Markings for Hazardous
Locations
UL Class I, Division 2, Groups A, B, C, and D; Type 4 Enclosure
Approval Standards UL Class I, Division 2, Groups A, B, C, and D; Type 4 Enclosure
Canada ICES-003 Issue 3 Class A Digital Apparatus emissions requirements
Australia AS/NZS3548:1995/CISPR Class A ITE emissions requirements
EMC EN 55022:1998 Class A ITE emissions requirements (EU)
EN 61000-4-2 (Electrostatic Discharge)
EN 61326 (Immunity and Class A Emissions)
ENV 50140