Product data

June 2012
CWGFC
4 www.EmersonProcess.com/Remote
Overview of the Standard
Application Program:
Uses pre-configured web-style menu pages for user
readings, configuration, and maintenance. PC menu pages
can be modified and new pages configured to work with a
modified application load.
The program uses TechView Calibration Utility for the
calibration of all transducers, including the integral
MVT and external transmitters (e.g. 3808 MVT).
The PC menu pages, calibration utility, and program
load are all included on the BSI Config CD.
Standard configuration is a one-to-two run station
meter type.
The user interface to the Standard Application Program is via a
series of straight-forward web-style menu pages.
Flow calculations include the following:
AGA3-1992 with selectable AGA8 Gross or AGA8
Detail
AGA3-1985/NX-19
AGA7/NX-19
AGA7 with selectable AGA8 Gross or AGA8 Detail
Auto Adjust AGA7/NX-19
Auto Adjust AGA7 with selectable AGA8 Gross or
AGA8 Detail
AGA9
Allows you to select the integral sensor assembly or an
external transmitter for a single run configuration or as
run 1 in a multiple run configuration. External
transmitters can be interfaced via RS-485 or analog
inputs.
Includes run switching
Includes an auto-selector, PID flow/pressure control
algorithm per run or per station
Resides on a BSAP SCADA network
Supports a sampler and an odorizer
Hourly Historical Data Log
The Hourly Data Log holds one record for every
contract hour. Hourly logs hold 840 entries or 35 days;
this ensures that the previous period of hourly data is
always resident in ControlWave GFC FLASH memory.
The following items are stored in the Hourly Data Log:
Corrected Volume
Uncorrected Volume
Accumulated Energy
Average Static Pressure
Average Temperature
Average Differential Pressure
Average Specific Gravity
Average Heating Value
Flow Time
Uncorrected Count
Each log entry also contains the date and time.
ControlWave GFC has an Hourly Historical Log for each
run.
Daily Historical Data Log
The Daily Data Log holds one record for every contract
day. The contract hour may be changed by the user.
The daily log holds 62 entries; this ensures that the
previous calendar month of daily data is always resident
in ControlWave GFC FLASH memory. The following
items are stored in the Daily Data Log:
Corrected Volume
Uncorrected Volume
Accumulated Energy
Average Static Pressure
Average Temperature
Average Differential Pressure
Average Specific Gravity
Average Heating Value
Flow Time
Uncorrected Count
Each log entry also contains the date and time.
ControlWave GFC has a Daily Historical Log for each
run.
Periodic Historical Data Log
The periodic data log holds one record for every log
interval. Log interval is 15 minutes. The Periodic
Historical Data Log holds 1440 records, or four days of
15 minute data. The following items are stored in the
Periodic Historical Data Log:
Flowing Differential Pressure
Flowing Static Pressure
Flowing Temperature
Frequency
Each log entry also contains the date and time.
ControlWave GFC has a Periodic Historical Data Log for
each run.