TABLE OF CONTENTS 1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1.1 Designed to Match Computer and Electronic Equipment Needs—From Installation to Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2.0 STANDARD FEATURES—1.5- TO 3-TON SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 2.
FIGURES Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Figure 21 Figure 22 Wall-box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Flexible configurations—All systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLES Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Table 12 Table 13 Table 14 Table 15 Table 16 Table 17 Table 18 Table 19 Table 20 Table 21 Table 22 Table 23 Table 24 Table 25 Table 26 60Hz capacities & typical specifications, air-cooled applications. . . . . . . . . . . . . . . . . . . . . . . . . . . 8 50Hz capacities & typical specifications, air-cooled applications. . . . . . . . . . . . . . . . . . . . . . . . . . .
iv
Introduction 1.0 INTRODUCTION 1.1 Designed to Match Computer and Electronic Equipment Needs—From Installation to Operation Installed on the floor or on the wall, Liebert DataMate Precision Cooling systems control the cooling, humidity and air distribution required by sensitive electronic equipment. A range of sizes and configurations is available to meet varying sites’ needs. The Liebert DataMate is also easy to use.
Standard Features—1.5- to 3-Ton Systems 2.0 STANDARD FEATURES—1.5- TO 3-TON SYSTEMS 2.1 Evaporator Section—Split-Systems The Liebert DataMate is available as a split system air, water/glycol-cooled unit or self-contained chilled water unit. Split-System Evaporator Section includes the evaporator coil, 2-speed centrifugal blower assembly, filter-drier, galvanized steel drain pan, R-407C refrigerant charge, cleanable filters and microprocessor control with wall-mounted display panel.
Standard Features—1.5- to 3-Ton Systems 2.5 System Controls System controls include a microprocessor control board mounted in the evaporator/chilled water unit and a wall-mounted interface with a two-line, 16-character liquid crystal display. An eight-key, membrane keypad for setpoint/program control, unit On/Off, fan speed and alarm silence is below the LCD screen.
Optional Factory-Installed Features—Evaporator/Chilled Water & Condensing Units 3.0 OPTIONAL FACTORY-INSTALLED FEATURES—EVAPORATOR/CHILLED WATER & CONDENSING UNITS 3.1 Electric Reheat Electric low watt tubular reheat element with non-corrosive metal sheath provides one stage of nonionizing reheat to maintain room dry bulb temperature. 3.2 Humidifier/Electric Reheat Package The humidifier and electric reheat are available as a package for complete humidity control.
Ship-Loose Accessories—Field-Installed 4.0 SHIP-LOOSE ACCESSORIES—FIELD-INSTALLED The Condensate Pump is field-mounted internal to the unit and wired to the unit power block or is field-mounted external to the unit with power from unit or external power supply. Pump is complete with integral float switch, discharge check valve, pump, motor assembly and reservoir. A secondary float can be field-wired to shut down the unit upon high condensate level.
Ship-Loose Accessories—Field-Installed 4.1 Remote Monitoring, Autochangeover and Leak Detection Equipment The Liebert RCM4™ is a four-point, normally open, dry contact monitoring panel. One Form-C, dry contact common alarm relay output (rated at 24 VAC, 3 Amp) is provided. Four red LEDs illuminate on the respective alarm and the alarm buzzer is silenced by a front panel switch. The RCM4 requires a 24VAC or 24VDC power source. Power supply is not included.
Flexible Configurations 5.0 FLEXIBLE CONFIGURATIONS Figure 2 Flexible configurations—All systems Air-Cooled Systems L ie be rt ¨ ¨ Liebert OUTDOOR, AIR-COOLED CONDENSING UNIT Suitable for installation on a roof or at ground level. INDOOR AIR-COOLED CONDENSING UNIT For applications where roof or ground level locations are impractical. Water/Glycol-Cooled Systems L ie be ¨ Liebert WATER/GLYCOL-COOLED CLOSE-COUPLED A single power and water supply connection puts the unit in operation.
Air-Cooled Systems—Capacities and Dimensions 6.0 Table 1 AIR-COOLED SYSTEMS—CAPACITIES AND DIMENSIONS 60Hz capacities & typical specifications, air-cooled applications Evaporator Model DME020E PFH - Outdoor DME027E DME037E Condensing Unit Type DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM 80°F DB, 62.8°F WB Total 5.40 (18,500) 7.10 (24,200) (26.7°C DB, 17.1°C Sensible 5.40 (18,500) 7.10 (24,200) WB) 38 %RH 75°F DB, 61°F WB Total 5.05 (17,200) 6.60 (22,500) (23.9°C DB, 16.
Air-Cooled Systems—Capacities and Dimensions Table 2 50Hz capacities & typical specifications, air-cooled applications DME020E Evaporator Model DME027E DME037E PFH - Outdoor PFH - Outdoor MCD - Indoor PFH - Outdoor MCD - Indoor Condensing Unit Type DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM Total 5.15 (17,500) 80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38 %RH Sensible 5.05 (17,200) 6.50 (22,200) 6.40 (21,800) 9.90 (33,800) 9.45 (32,300) 6.50 (22,200) 6.40 (21,800) 8.
Air-Cooled Systems—Capacities and Dimensions Figure 3 General arrangement, air-cooled split systems 10
Air-Cooled Systems—Capacities and Dimensions Figure 4 Dimensions, evaporator unit See Table 3 for Dimension A Table 3 Evaporator section dimensions—air-cooled applications Model Weight lb (kg) Width - A in. (mm) Depth in. (mm) Height in.
Air-Cooled Systems—Capacities and Dimensions Figure 5 Cabinet and floor planning dimensions—Outdoor air-cooled condensing units Removable (right) panel for access to refrigeration component Fan Rotation CCW (left side) A Right Air Discharge Left Air Intake B Shaded area indicates a minimum clearance of 18" (457mm) for proper airflow Shaded area indicates a recommended clearance of 24" (610mm) for component access and removal C Shaded area indicates a minimum clearance of 18" (457mm) for proper air
Air-Cooled Systems—Capacities and Dimensions Figure 6 Dimensions, indoor air-cooled condensing units Table 6 Model MC*23A MC*24A MC*35A MC*36A Remote centrifugal fan, air-cooled condensing, weight and dimensions Weight lb (kg) Dimensions, in (mm) A B C D 1-7/16 (37) 11-7/16 (290) 1/2 (13) 20-7/16 (519) 230 (104) 240 (109) 13
Water/GlycolSystems—Capacities and Dimensions 7.0 Table 7 WATER/GLYCOLSYSTEMS—CAPACITIES AND DIMENSIONS 60Hz capacities & typical specifications, water-cooled and glycol-cooled applications DME020E DME027E DME037E WaterGlycolWaterGlycolWaterGlycolCooled Cooled Cooled Cooled Cooled Cooled Condensing Unit Type DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM Total 5.90 (20,100) 5.15 (17,600) 7.95 (27,200) 6.75 (23,000) 11.4 (38,900) 9.65 (32,900) 80°F DB, 62.8°F WB (26.7°C DB, 17.
Water/GlycolSystems—Capacities and Dimensions Table 8 50Hz capacities & typical specifications, water-cooled and glycol-cooled applications DME027E Evaporator Model Water-Cooled Condensing Unit Type DME037E Glycol-Cooled Water-Cooled Glycol-Cooled 11.3 (38,700) 9.30 (31,800) DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM 80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38 %RH 75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45 %RH 72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50 %RH Total 7.
Water/GlycolSystems—Capacities and Dimensions Figure 7 General arrangement, water/glycol, split systems Figure 8 General arrangement, water/glycol systems, close-coupled condensing unit 16
Water/GlycolSystems—Capacities and Dimensions Figure 9 Dimensions, evaporator unit See Table 9 for Dimension A Table 9 Evaporator section dimensions—water/ glycol-cooled applications Depth Height Model Weight lb (kg) Width - A in. (mm) in. (mm) in.
Water/GlycolSystems—Capacities and Dimensions Figure 10 Dimensions, close-coupled water/glycol condensing unit Table 11 Net weight, water/glycol condensing units Model Tons Weight DMC022WG 1-1/2 170lb (77kg) DMC029WG 2 170lb (77kg) DMC040WG 3 170lb (77kg) For refrigerant and water/glycol piping connection sizes, see Tables 7 and 8 18
Water/GlycolSystems—Capacities and Dimensions Figure 11 Cabinet dimensions and piping data, water/glycol indoor remote condensing modules Table 12 Net weight, indoor water/glycol-cooled condensing unit Model # 60Hz 50Hz Weight lb (kg) MC*26W MC*25W 175 (79) MC*38W MC*37W 220 (100) 19
Chilled Water Systems 8.0 CHILLED WATER SYSTEMS Table 13 Chilled water data, 50/60Hz DME044C 208/230-1-60 CW Model, 60 Hz 200/220-1-50 Net Capacity Data - kW (Btuh) based on 45°F (7.2°C) EWT & 10°F (5.6°C) temperature rise 80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38 %RH Total 10.5 (36,000) 9.1 (31,100) Sensible 9.65 (32,900) 8.3 (28,200) Flow Rate, GPM (l/m) 7.3 (27.7) 6.3 (23.9) Pressure Drop, ft. water (kPa) 12.0 (35.9) 9.3 (27.8) Total 8.45 (28,900) 7.6 (25,900) Sensible 7.
Chilled Water Systems Table 14 Chilled water capacity correction factors based on 10°F (5.6°C) water rise 72°F (22.2°C) 50% 75°F (23.9°C) 45%RH EWT TCC SCC TCC SCC 42°F (5.6°C) 1.27 1.14 1.23 1.11 43°F (6.1°C) 1.17 1.09 1.15 1.07 44°F (6.7°C) 1.08 1.04 1.07 1.04 45°F (7.2°C) 1.00 1.00 1.00 1.00 46°F (7.8°C) 0.93 0.96 0.94 0.96 47°F (8.3°C) 0.86 0.92 0.88 0.93 48°F (8.9°C) 0.79 0.88 0.82 0.89 49°F (9.4°C) 0.74 0.83 0.77 0.
Chilled Water Systems Figure 13 Dimensions—Chilled water unit Table 15 Model DME044C Net weights and dimensions, chilled water units Dimensions W x D x H, in (mm) Weight lb (kg) Water Connection Sizes 64-1/8 x 11-7/8 x 32 (1628 x 302 x 813) 364 (165) 7/8" (22.
Electrical Data—All Units 9.0 ELECTRICAL DATA—ALL UNITS Table 16 Electrical data, split system evaporator or chilled water unit, 60/50Hz 208/230V-1ph-60Hz Base Evaporator/ Chilled Water DME020E DME027E 200/220V-1-50 DME037E DME044C DME020E DME027E DME037E DME044C Cooling Only FLA 1.4 1.5 2.2 1.4 1.5 2.2 WSA 1.8 1.9 2.8 — — — OPD 15 15 15 — — — With Reheat FLA 11.8 22.3 23.0 11.8 22.3 23.0 WSA 14.8 27.9 28.
Electrical Data—All Units Table 18 60Hz electrical data, outdoor air-cooled condensing unit 1.5 Nom. Capacity, Tons 2 3 3 3 3 PFH037A-PL7 PFH037A-YL7 PFH037A-AL7 PFH037A-BL7 Standard 95°F (35°C) Propeller Fan Condensing Unit Model PFH020A-PL7 PFH027A-PL7 Volt-Ph-Hz 208/230-1-60 208/230-1-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 FLA 12.1 13.5 19.3 12.8 6.4 5.9 WSA 14.8 16.5 23.8 15.7 7.8 7.
Electrical Data—All Units Table 20 Electrical data, indoor air & water/glycol remote condensing units, 50 & 60Hz 60 Hz Model 208/230-1ph-60Hz 277-1ph-60Hz MC*24A 50 Hz 208/230-3ph-60Hz 460-3ph-60Hz 220-1ph-50Hz 380/415-3ph-50Hz MC*24A MC*24A MC*23A MC*23A MC*24A FLA 13.7 11.9 N/A N/A 13.2 5.7 WSA 16.6 14.3 N/A N/A 16.1 6.8 OPD 25 20 N/A N/A N/A N/A MC*36A MC*36A MC*36A MC*36A MC*35A MC*35A FLA 19.4 16.6 15.1 7.1 20.1 7.8 WSA 23.3 20.2 18.0 8.5 24.4 9.
Refrigerant Piping 10.0 REFRIGERANT PIPING Table 21 Refrigerant charge 60 Hz 50 Hz DME020E DME020E 4 (0.11) DME027E DME027E 5 (0.14) DME037E DME037E 6.5 (0.18) MC*24AL_H7 MC*23AL_H7 134 (3.80) MC*36AL_H7 MC*35AL_H7 213 (6.04) MC*26W__H7 MC*25W__H7 41 (1.16) MC*38W__H7 MC*37W__H7 54 (1.54) DMC022WG N/A 47 (1.33 DMC029WG N/A 59 (1.67 DMC040WG N/A 61 (1.72) PFH020A-_L7 PFH019A-_L7 134 (3.80) PFH027A-_L7 PFH026A-_L7 134 (3.80) PFH027A-_H7 PFH026A-_H7 213 (6.
Refrigerant Piping Table 25 Line charges - refrigerant per 100 ft. (30m) of Type L copper tube R-407C, lb/100 ft. (kg/30m) Line Size, O.D., in. Liquid Line Suction Line 3/8 3.7 (1.7) — 1/2 6.9 (3.1) — 5/8 11.0 (5.0 0.4 (0.2) 3/4 15.7 (7.1) 0.6 (0.3) 7/8 23.0 (10.4) 1.0 (0.4) 1-1/8 — 1.7 (0.7) 1-3/8 — 2.7 (1.1) Figure 15 Refrigerant piping diagram Pitch down 1/2" (13mm) per 10 ft.
Glycol Loop Piping 11.0 GLYCOL LOOP PIPING Contact Emerson Application Engineering for assistance in choosing correct drycooler models. Refer to Figure 16. Figure 16 Heat rejection loop, multiple drycoolers and multiple indoor units Expansion Tank ______ Gal. (L) HP GPM (l/s) ft. ____(kW) ____ Per Pump @ ____(kPa) FS PUMP PACKAGE Drycooler No.
Model Number Nomenclature—All Systems 12.
Model Number Nomenclature—All Systems Figure 20 Model number nomenclature, close-coupled water/glycol condensing units—60Hz only Liebert DataMate Evaporator Section Nominal Capacity (kBtuH) WG = Water/Glycol P = 208/230/1/60 DMC 040 WG P 07 07 = R-407C Refrigerant Figure 21 Model number nomenclature—Indoor remote water/glycol-cooled condensing units Nominal Capacity 25 = 2-ton, 50Hz 26 = 2-ton, 60Hz 37 = 3-ton, 50Hz 38 = 3-ton, 60Hz MC = Liebert Mini-Mate2 Style Indoor Condensing Units D = Disconne
Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW) GUIDE SPECIFICATIONS—FOR LIEBERT DATAMATE 1.5- TO 3-TON (5 TO 10.5KW) 1.0 GENERAL 1.1 Summary These specifications describe requirements for an environmental control system. The system shall be designed to maintain temperature and relative humidity conditions within the room. The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation requirements of the site.
Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW) 2.1.3 Microprocessor Control System The control system shall be microprocessor-based, factory-wired into the system and tested prior to shipment. The wall-mounted control enclosure shall include a 2-line by 16-character LCD providing continuous display of operating status and alarm condition. An 8-key membrane keypad for setpoint/ program control, fan speed selection and unit On/Off shall be located below the display.
Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW) 2.1.4 Alarms 2.1.4.1 Unit Alarms The control system shall monitor unit operation and activate an audible and visual alarm in the event of the following factory preset alarm conditions. • • • • • • • • High Temperature (max 90°F, 32.2°C) Low Temperature (min 35°F, 1.7°C) High Humidity (max 85% RH) Low Humidity (min 15% RH) High Water Alarm - Lockout Unit Operation High Head Pressure Loss of Power Compressor Short Cycle 2.1.4.
Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW) 2.2 Direct Expansion System Components 2.2.1 Direct Expansion Coil The evaporator section shall include an evaporator coil, thermostatic expansion valve and filter-drier. The evaporator coil shall have ___ ft.2 (m2) face area, ___ rows deep. It shall be constructed of copper tubes and aluminum fins and have a maximum face velocity of ___ FPM (m/s) at _____ CFM (CMH).
Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW) 2.3 Indoor Remote Water/Glycol-Cooled Condensing Unit The water/glycol condensing unit shall include a scroll compressor, high-pressure switch, coaxial condenser, water-regulating valve, hot gas bypass system and liquid line solenoid valve. A hot gas bypass circuit shall be provided to reduce compressor cycling and improve operation under low-load conditions.
Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW) 2.5.6 Liebert Local Monitoring Systems, Autochangeover and Leak Detection Provide indicated quantities of the following: • ______ Leak Detection System(s) Model __________________________________ • ______ Remote Monitor(s) Model ________________________________________ • ______ Auto Changeover Control(s) Model ________________________________ 2.5.
Ensuring The High Availability Of Mission-Critical Data And Applications. Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity.