Data Sheet

D4 Valve
D103039X012
Product Bulletin
51.2:D4
November 2013
5
Table 1. Hazardous Area Classifications - CSA (Canada and United States)
CERTIFICATION BODY
CERTIFICATION
OBTAINED
ENTITY RATING TEMPERATURE CODE ENCLOSURE RATING
CSA Class I, Division 1, GP C, D T6 ---
T6 (Tamb 70_C)
CSA Type 4X Enclosure
Table 2. EMC Summary Results - Immunity
PORT PHENOMENON BASIC STANDARD TEST LEVEL
PERFORMANCE
CRITERIA
(1)
Enclosure
Electrostatic discharge (ESD) IEC 61000-4-2
4kV Contact
8kV Air
A
Radiated EM field IEC 61000-4-3
80 to 1000 MHz @ 10V/m 1kHz AM at 80%
1400 to 2000 MHz @ 3V/m 1kHz AM at 80%
2000 to 2700 MHz @ 1V/m 1kHz AM at 80%
A
(2)
/B
Rated p ower frequency
magnetic field
IEC 61000-4-8 30 A/m @ 50 and 60 Hz A
I/O signal/ control
Burst IEC 61000-4-4 1kV A
Surge IEC 61000-4-5 1kV cable shield, and line to ground A
Conducted RF IEC 61000-4-6 3V 150 kHz to 80 MHz at 3 Vrms A
Performance criteria is +/- 5% stem position
1. A= No degradation during testing. B = Temporary degradation during testing, but is self recovering.
2. Criteria A with conduit on DC and I/O cables, Criteria B without conduit
Ordering Information
When ordering, specify:
Application Information
1. Type of application
a. Throttling or on-off
b. Reducing or relief (back pressure)
2. Controlled fluid
a. Type (include chemical analysis, if available)
b. Temperature (normal and maximum
anticipated)
c. Specific gravity
3. Range of flowing inlet pressures
4. Pressure drops
a. Range of flowing pressure drops
b. Maximum drop at shutoff
5. Flow rates
a. Minimum controlled flow
b. Normal flow
c. Maximum flow
6. Input s ignal range to actuator
Control Valve Assembly Information
Refer to the Specifications and review the information
under each specification.