Installation Manual

Features
Three-stage■hybrid■protection
Differential■protection
Common■mode■protection
Plug-in■module
Automatic■recovery
Fast■response■time
Continuous■current■up■to■5■Amps
UL■497B■listed
Requires■Edco■PCB1B-WKEY■base
PC642PTU■(Pass■Thru■Unit)■
available■for■troubleshooting
5■year■warranty
Edco PHC Series
Two-Pair■Signaling■Circuit■Protector■(Modular)
The■ Edco■ PHC■ Series■ is■ designed■ to■ protect■ two■ pairs■ of■ wires■ specifically■ for■
alarm■and■security■systems■where■operating■currents■can■be■as■high■as■5■Amps.■
Electrically,■the■Edco■PHC■Series■is■a■rugged■series■hybrid■implementing■a■staged■
complement■of■MOVs,■copper■wound■inductors■and■Silicon■Avalanche■Diodes.■This■
design■reduces■series■resistance■to■0.2■ohms■per■pair.■These■products■are■intended■
to■mate■with■an■Edco■PCB1B-WKEY■gold-plated■female■terminal■connector.
The■Edco■PHC■modules■plug■into■a■base■assembly■(Edco■PCB1B-WKEY).■The■base■
assembly■can■ be■mounted■to■any■flat■surface■and■should■ be■ located■as■close■as■
practical■ to■ the■ protected■equipment.■Terminal■1■ and/or■ terminal■10■should■ be■
connected■to■Building-Approved■Ground■with■12■or■10■gauge■solid■wire.
Caution
Do not place this product in service on any signal line capable of supplying more than 5 Amps continuously.
Attention
Ne pas placer ce produit dans le service sur une ligne de signal capable de fournir en permanence plus de
5 ampères.
General Technical Specifications
Operating■Voltage 12,■18,■24,■30,■36,■52,■70,■120■VDC
Clamping■Voltage 15,■20,■30,■36,■43,■60,■100,■150■VDC
Operating■Current 5■A
Peak■Surge■Current 10■kA■(8■x■20■μs)
Frequency■Range 0■to■10■MHz
Insertion■Loss <■0.1■dB■at■10■MHz
SPD■Technology MOV,■SAD,■w/■Series■Inductor
Connection■Type Terminal■block■w/■compression■lugs
Terminals■accept■up■to■10■AWG
Operating■Temperature -40°C■to■+85°C
Dimensions■(in■/■mm) 3.7˝■H■x■1.75˝■W■x■2.375˝■L
[94■x■44.45■x■60.33■mm]
(PHC■+■PCB1B-WKEY■Base)
Weight■(oz■/■kg) 8■oz■[0.23■kg]
Certifications UL■497B
EDCO PCB1B-WKEY BASE SOLD SEPARATELY