Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable Rosemount 3095 MultiVariable™ Mass Flow Transmitter with HART® or FOUNDATION™ Fieldbus Protocol Rosemount 3095MF Series Flowmeter Transmitter P r oduc tDi s c ont i nue d Start Step 1: Mount the Transmitter Step 2: Transmitter Installation Step 3: Software Installation Step 4: Connect the Wiring and Power Up (HART or Fieldbus) Step 5: Configure the Transmitter (HART or Fieldbus) Step 6: Trim the Transmitter Produc
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable © 2009 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. Rosemount Inc. Emerson Process Management GmbH & Co.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable TRANSMITTER EXPLODED VIEW Certification Label Housing Terminal Block (HART) O-ring Electronics Board Cover Nameplate Module O-ring Sensor Module Housing Locking Screw RTD Connector Process Adapter O-ring Drain/Vent Valve Coplanar Flange Flange Adapter O-ring Optional Flange Adapters LCD Display Assembly Bolts LCD Display Cover Terminal Block (Fieldbus) 3
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 1: MOUNT THE TRANSMITTER Liquid Flow Applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward. Flow Gas Flow Applications 1. Place taps in the top or side of the line. 2. Mount beside or above the taps. Flow Flow Steam Flow Applications 1. Place taps to the side of the line. 2.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 2: TRANSMITTER INSTALLATION Consider Housing Rotation To improve field access or to better view the optional LCD display: 1. Loosen the housing rotation set screw. 2. Rotate the housing clockwise to the desired position – up to 180° from its original position. Over rotating will damage the transmitter. 3. If the desired position is attained, tighten the housing rotation set screw. 4.
Quick Installation Guide Rosemount 3095 MultiVariable 00825-0100-4716, Rev DA October 2009 STEP 2 CONTINUED... 3. Set the Failure Mode Alarm (HART devices), which is located on the front of the electronics board inside the electronics housing cover. The Alarm Jumper position determines if the output is driven high or low when a failure is detected. The transmitter operates normally if the jumpers are not installed and the Alarm default fail is HI. Figure 2.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 2 CONTINUED... • Installing a Shielded 3095 RTD Cable (See Figure 4) Note: Shielded cable is intended for use in a conduit. a.Fully engage the black cable connector to the 3095 RTD Connector. b.Tighten the cable adapter until metal contacts metal. Figure 4. Shielded RTD Cable Cable Adapter 1/2–14 NPT Black Cable Connector • Installing a ATEX/IECEx Flameproof 3095 RTD Cable (See Figure 5) a.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 2 CONTINUED... Bolting Considerations If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 2 CONTINUED... Figure 7. Torque values for the flange and flange adapter bolts Bolt Material Head Markings Initial Torque Final Torque Carbon Steel (CS) 300 in.-lbs. 650 in.-lbs. 150 in.-lbs. 300 in.-lbs.
Quick Installation Guide Rosemount 3095 MultiVariable 00825-0100-4716, Rev DA October 2009 STEP 3: SOFTWARE INSTALLATION The 3095 Engineering Assistant (EA) for HART and 3095 Engineering Assistant (EA) for FOUNDATION Fieldbus software programs can be installed on the same computer. The applications cannot be open simultaneously. 3095 Engineering Assistant (EA) for HART Software Installation 1. Install the Program a.Place the CD-ROM in the drive and run setup.exe from Windows NT, 2000, or XP. b.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 3 CONTINUED... Installing the HART Modem After installing the 3095 Engineering Assistant, the HART modem configuration window automatically appears when the 3095 Engineering Assistant is opened. If this window is canceled, the HART modem may be installed manually with the following procedure. 1. Close AMS. From the Start Menu select Programs > 3095 Engineering Assistant > AMS Network. 2.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 4: CONNECT WIRING AND POWER UP (HART) Use the following steps to wire the transmitter: 1. Remove the housing cover on the side marked FIELD TERMINALS. 2. Connect the signal leads to the terminals. NOTE Do not connect the powered signal wiring to the test terminals. Power could damage the test diode in the test connection. Shielded twisted pair cable should be used for best results.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 4: CONNECT WIRING AND POWER UP (FIELDBUS) Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field Terminals.” Terminals are not polarity sensitive. 2. Connect the signal leads to the terminals labeled “Fieldbus Wiring”. 3. Plug and seal unused conduit connections. 4. Install wiring with a drip loop.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 5: CONFIGURE THE TRANSMITTER (HART) Setting the Loop to Manual Set the process application loop to manual when preparing to send or request data that would disrupt the loop or change the output of the transmitter. A prompt will appear reminding the user to set the loop to manual when necessary. Acknowledging this prompter does not set the loop to manual.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 ✓ ✓ ✓ ✓ Rosemount 3095 MultiVariable Function/Variable Fast Key Sequence DP Sens Trim DP Snsr Range DP URV DP units Date Descriptor Diff pres damp Diff pres Diff pres Fld dev rev Flo rate Flow Rate Special Units Flow Units GP Damping GP Sens Trim GP Units Gage (GP) Hardware rev LCD Settings Loop test Message Num req preams Num resp preams PV is Poll addr Process temp unit Process temp RS type RTD Config Range values Reset SP Snsr Range SP
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 5: CONFIGURE THE TRANSMITTER (FIELDBUS) Each FOUNDATION fieldbus host or configuration tool has a different way of displaying and performing configurations. Some use Device Descriptions (DD) or DD methods for configuration and to display data consistently across platforms. There is no requirement that a host or configuration tool support these features.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable STEP 6: TRIM THE TRANSMITTER NOTE Transmitters are shipped from Emerson Process Management fully calibrated and configured for the application when C2 Option is ordered. Without C2 Option, configuration will be by the factory default (span = upper range limit for FOUNDATION fieldbus transmitters).
Quick Installation Guide Rosemount 3095 MultiVariable 00825-0100-4716, Rev DA October 2009 PRODUCT CERTIFICATIONS Rosemount 3095 with HART Approved Manufacturing Locations Rosemount Inc. — Chanhassen, Minnesota USA Emerson Process Management GmbH & Co. — Wessling, Germany Emerson Process Management Asia Pacific Private Limited — Singapore Beijing Rosemount Far East Instrument Co.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable Canadian Standards Association (CSA) C Explosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F, and G. CSA enclosure Type 4X suitable for indoor and outdoor hazardous locations. Provides nonincendive RTD connection for Class I, Division 2, Groups A, B, C, and D.Factory Sealed. Install in accordance with Rosemount Drawing 03095-1024.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable G H P ATEX Type n Certificate Number: BAS98ATEX3360X Ex nL IIC T5 (Tamb = –45 °C to 40 °C) Ex nL IIC T4 (Tamb = –45 °C to 70 °C) Ui = 55V The apparatus is designed for connection to a remote temperature sensor such as a resistance temperature detection (RTD) Special Conditions for Safe Use The 3095, when fitted with the transient terminal block (order code B), are not capable of withstanding the 500 volts insulat
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable Table 7. RTD Terminals Entity Parameters Uo = 30Vdc Io = 19 mAdc Po = 140 mW The capacitance and either the Inductance or the Inductance to Resistance Ratio (L/R) of the load connected to the 4-pin connector must not exceed the following values: Group Capacitance (F) Inductance (mH) IIC IIB IIA 0.066 0.56 1.82 96 365 696 or L/R Ratio H/Ohm 247 633 633 NOTE 1.
Quick Installation Guide Rosemount 3095 MultiVariable 00825-0100-4716, Rev DA October 2009 China (NEPSI) Certifications 2 China Intrinsic Safety Ex ia IIC T4 Special conditions for safe use (x): 1. 3095 Series transmitter with temperature sensor have not been certified. 2. The temperature of process medium should be less than 121 °C. 3. The ambient temperature range is (-40~+60) °C. 4. Safety parameters 4.1 Input parameters 4.1.1 Transmitter with output code “V” Ui = 30V__ Ii = 300 mA __Pi = 1.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 11.When installation, use and maintenance transmitter, observe the following standards GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres” GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)” GB3836.
Quick Installation Guide Rosemount 3095 MultiVariable 00825-0100-4716, Rev DA October 2009 Combinations of Certifications Stainless steel certification tag is provided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinstalled using any other approval types. Permanently mark the approval label to distinguish it from unused approval types.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable Rosemount 3095 Fieldbus Hazardous Locations Certifications North American Certifications FM Approvals A J V Explosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F, and G. Enclosure type NEMA 4X. Factory Sealed. Provides nonincendive RTD connections for Class I, Division 2, Groups A, B, C, and D.
Quick Installation Guide Rosemount 3095 MultiVariable 00825-0100-4716, Rev DA October 2009 Table 9. Temperature Sensor Connection Parameters Uo = 30V Io = 19 mA Po = 140 mW Table 10. Connection Parameters for Temperature Sensor Terminals Co = 0.066 F Gas Group IIC Co = 0.560 F Gas Group IIB Co = 1.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 P Rosemount 3095 MultiVariable ATEX Dust Certificate Number: KEMA02ATEX2321 II 1 D T90°C (-50°C Tamb 80°C) Vmax = 55 Vdc Imax = 23 mA IP66 1180 IECEx Certifications (Fieldbus) 4/Y IECEx Intrinsic Safety Certificate Number: IECEx BAS05.0023X Ex ia IIC T4 (-45°C Ta 70°C) Ex ia IIC T5 (-45°C Ta 40°C) Table 11. Input Parameters Fieldbus I.S. Ui = 30Vdc Ii = 300 mAdc Pi = 1.3 W Ci = 3.3 nF Li = 0 FISCO Ui = 17.
Quick Installation Guide Rosemount 3095 MultiVariable 7 8 00825-0100-4716, Rev DA October 2009 IECEx Flameproof Certificate Number: IECEx KEM 06.0018 Zone 0/1 Ex d IIC T6 (-20°C Ta 65°C) Zone 0/1 Ex d IIC T5 (-20°C Ta 80°C) Vmax = 55 Vdc Imax = 23 mAdc IECEx Dust Certificate Number: IECEx KEM 06.0018 Ex tD A22 T90°C IP66 Combinations of Certifications Stainless steel certification tag is provided when optional approval is specified.
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 29
Quick Installation Guide Rosemount 3095 MultiVariable 30 00825-0100-4716, Rev DA October 2009
Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiVariable 31
Quick Installation Guide Rosemount 3095 MultiVariable 32 00825-0100-4716, Rev DA October 2009