• If a neutral wire (not the same as Earth Ground) is supplied from the building distribution panel, it should never
be bonded with PE wire in the enclosure.
• You should consider future troubleshooting and repair when installing all wiring. All wiring should be either color
coded and/or tagged with industrial wire tabs.
• As a general rule, the minimum cable bend radius is ten times the cable outer diameter.
• All wiring and cables, stationary and moving, must be protected from abrasion.
• Ground wires should not be shared or "daisy-chained" with other equipment.
• Ensure that full metal to metal surface contact is made between the enclosure ground lug and the metal
enclosure, not simply through the mounting bolt and threads.
• All inductive coils must be suppressed with appropriate devices, such as diodes or resistor/capacitor (RC)
networks, except as described in this manual.
• If using a non-shielded Ethernet cable, install a clamp on ferrite, Control Techniques part number 157016-07,
Steward 28A0593-0A2 or equivalent.