Installation manual

18
Safety Information Product Overview Installation Diagnostics
Options and
Accessories
Specification
Line Fusing and Wire Size
You must incorporate over current protection for the incoming AC power with the rating shown here. The drive alone
does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National
Electrical Code and any additional local codes.
Use copper conductors only. Conductors must be rated 75°C or higher, preferably 90°C.
Suitable for use on a circuit capable of delivering not more than 10,000 rms symmetrical Amperes. When one of the
above current protection devices are used.
Drive Model
Recommended
Minimum AC/PE
Line Wire Gauge
Fuse Miniature Circuit Breaker
Fuse Class & Action Bussman
Ferraz-
Shawmut
Allen Bradley Square D
EP202
16 AWG
ISO 1,5
RK1 Time-Delay LPN-RK-6SP A2D6R
1489-A1D060
6 A, 1 pole
60124
6 A. 1 pole
RK1 Quick-Acting KTN-R-6 A2K6R
CC Time-Delay LP-CC-6 ATDR6
1489-A2 D060
6 A, 2 pole
60158
6 A, 2 pole
CC Quick-Acting KTK-R-6 ATMR6
EP204
16 AWG
ISO 1,5
RK1 Time-Delay LPN-RK-10SP A2D10R
1489-A1D100
10 A, 1 pole
60127
10 A, 1 pole
RK1 Quick-Acting KTN-R-10 A2K10R
CC Time-Delay LP-CC-10 ATDR10
1489-A2D100
10 A, 2 pole
60161
10 A, 2 pole
CC Quick-Acting KTK-R-10 ATMR10
EP206
14 AWG
ISO 2,5
RK1 Time-Delay LPN-RK-15SP A2D15R
1489-A1D150
15 A, 1 pole
60129
15 A, 1 pole
RK1 Quick-Acting KTN-R-15 A2K15R
CC Time-Delay LP-CC-15 ATDR15
1489-A2D150
15 A, 2 pole
60163
15 A, 2 pole
CC Quick-Acting KTK-R-15 ATMR15
EP209
12 AWG
ISO 4
RK1 Time-Delay LPN-RK-20SP A2D20R
1489-A1D200
20 A, 1 pole
60130
20 A, 1 pole
RK1 Quick-Acting KTN-R-20 A2K20R
CC Time-Delay LP-CC-20 ATDR20
1489-A2D200
20 A, 2 pole
60164
20 A, 2 pole
CC Quick-Acting KTK-R-20 ATMR20
EP216
12 AWG
ISO 4
RK1 Time-Delay LPN-RK-20SP A2D20R
1489-A1D200
20 A, 1 pole
60130
20 A, 1 pole
RK1 Quick-Acting KTN-R-20 A2K20R
CC Time-Delay LP-CC-20 ATDR20
1489-A2D200
20 A, 2 pole
60164
20 A, 2 pole
CC Quick-Acting KTK-R-20 ATMR20
1489-A3D200
20 A, 3 pole
60196
20 A, 3 pole
The Protective Earth (PE) wire connection is mandatory for human safety and proper operation. This
connection must not be fused or interrupted by any means. Failure to follow proper PE wiring can cause death
or serious injury.