user manual




The chilled water cooling coil is designed for closed-
loop applications using properly maintained water. It
is constructed of copper tubes and aluminum fins. A-
frame coils are used on downflow units and V-frame
coils are used on upflow units. To ensure quality, the
coil is manufactured to the highest standards in the
industry.

The flow of chilled water through the cooling coil is
controlled by an electronic modulating motor. The
microprocessor control will activate the motor when
a need for cooling or dehumidification exists. The
motor will position the valve to precisely match the
needs of the conditioned space.

All chilled water piping within the Challenger 3000
is fully insulated to assure full system capacity and
prevent condensation.

The fully insulated control valve gives the condi-
tioned space the precise cooling needed by electronic
equipment. Its unique design requires no overtravel
linkages and never requires adjustment.


The flow switch will activate the alarm system and/
or shut down the system should the chilled water
supply be interrupted. The switch is factory wired
and mounted in the chilled water valve compart-
ment.

For special applications, a high pressure, modulating
3-way or 2-way valve can be provided. The valve is
designed for 400 psig (2758 kPa) water pressure.
 
















