user manual




This reheat uses stainless steel elements and also
includes the necessary sensors and controls to pro-
vide variable heat output to help maintain tighter
control of room conditions, especially in lightly
loaded applications. (Contact factory for available
voltages.) Direct expansion units only.

Four optional filters are available in lieu of standard
package. A 4" (102mm) 20%, 30%, 40%-45% or
60%-65% filter may be specified. (Efficiency based on
ASHRAE 52.1). 2" (51mm) 20% pre-filters may also
be specified.

These 16 ga. panels include heavy duty gaskets to
provide satisfactory system operation when located
outside the conditioned space in less-than desirable
environments.

These blower/motor packages are available on upflow
models where external static pressures are up to
2.0 inches (500 Pa) on 60 Hz units, and up to
1.5 inches (370 Pa) on 50 Hz units. These blowers are
rigidly mounted for ducting directly to the blower
housing.
(Consult the factory for specific applications.)

These motors replace the standard efficiency motors
to provide increased energy savings during operation
(consult factory for specific efficiencies).

Standard height of 18" (457mm) with top duct con-
nection or 2-way, 3-way or 4-way grille discharge
styles available.

The smoke detector senses the return air, shuts
down the unit upon detection, and sends visual and
audible alarm. Dry contacts are available for a
remote customer alarm. This smoke detector is not
intended to function as or replace any room smoke
detection system that may be required by local or
national codes.
Supervised smoke detectors are also available as an
option. Consult factory.

The firestat senses return air temperature of the sys-
tem. Upon sensing high temperatures, the environ-
mental control system is shut down. Required by
codes in certain areas.

Controlled by a 2-way solenoid valve from the micro-
processor control panel, these economical reheats
have the capacity to maintain dry bulb conditions
when the system is calling for dehumidification. The
system is completely pre-piped and includes a control
valve and Y-strainer. The reheat coil is constructed
of copper tubes and aluminum fins.
NOTE
Some options or combinations of options
may result in reduced air flow. Consult
factory for recommendations.


DISCONTINUED
PRODUC T