Piggyback Condenser (Optional)
The system shall be supplied with a piggyback con-
denser (PB). The condenser shall be constructed of
steel with frame coated using the autophoretic
®
pro-
cess, and panels powder coated to protect against
corrosion. The coil shall be copper tube with alumi-
num fins. The heavy duty fan shall be the centrifugal
type, double width, double inlet. The 1750 RPM
(1450 RPM @ 50 Hz) fan motor shall be mounted on
an adjustable base, and equipped with an adjustable
motor pulley. A Liebert Lee-Temp head pressure con-
trol system shall be integral with the unit. The sys-
tem shall be designed for -30°F (-34.4°C) ambient.
The air cooled condenser shall have a _____ Volt,
3 phase, _____ Hz power supply.
Centrifugal Fan Condenser (Optional)
The system shall be supplied with a centrifugal fan
condenser (LCC). The condenser shall be constructed
of galvanized steel with a copper tube, aluminum fin
coil. The heavy duty fan shall be the centrifugal type,
double width, double inlet. The 1750 RPM (1450
RPM @ 50 Hz) fan motor shall be mounted on an
adjustable base, and equipped with an adjustable
motor pulley. A Liebert Lee- Temp head pressure
control system shall be field piped to the unit. Elec-
trical controls shall be in a rain-tight enclosure.
The system shall be designed for _____ °F (°C) ambi-
ent. The air cooled condenser shall have a _____ Volt,
3 phase, _____ Hz power supply.
 


The water/glycol system shall be equipped with a coax-
ial condenser having a total pressure drop of _____ ft.
of water (kPa) and a flow rate of _____ GPM (l/s) with
_____ °F (°C) entering water/glycol temperature.
2-Way Water Regulating Valve with Bypass
(Standard)
The condenser circuit shall be pre-piped with a head-
pressure actuated 2-way regulating valve with
bypass.
3-Way Water Regulating Valve (Optional)
The condenser circuit shall be pre-piped with a head
pressure actuated 3-way regulating valve.
Design Pressure
The condenser water/glycol circuit shall be designed
for a pressure of [(150 PSI (1034 kPa)) (350 PSI
(2413 kPa))].
Crankcase Heater (Optional)
A crankcase heater is provided to prevent the migra-
tion of refrigerant to the compressor during off
cycles.
Hot Gas Reheat (Optional)
The complete hot gas reheat system shall include a
copper tube, aluminum fin coil, three-way solenoid
valve, and refrigerant check valve. The capacity of
the coil shall be _____ BTU/HR (kW).

Propeller Fan Drycooler (Standard)
The Liebert manufactured drycooler shall be the low
profile, slow speed, direct drive propeller fan type.
The drycooler shall be constructed of aluminum and
contain a copper tube aluminum fin coil with an inte-
gral electric control panel. The drycooler shall be
designed for _____ °F (°C) ambient.
Centrifugal Fan Drycooler (Optional)
The system shall be supplied with a centrifugal fan
drycooler (LCD). The drycooler shall be constructed of
galvanized steel with a copper tube, aluminum fin coil.
The heavy duty fan shall be the centrifugal type, dou-
ble width, double inlet. The 1750 RPM (1450 RPM @
50 Hz) fan motor shall be mounted on an adjustable
base, and equipped with an adjustable motor pulley. A
3-way control valve and thermostat shall maintain the
desired fluid temperature. Electrical controls shall be
in a rain-tight enclosure. The system shall be designed
for _____ °F (°C) ambient. The drycooler shall have a
_____ Volt, 3 phase, _____ Hz power supply.
Single Glycol Pump Package (Standard)
This system shall be provided with a centrifugal
pump mounted in a weatherproof and vented enclo-
sure. The pump shall be rated for _____ GPM (l/s) at
_____ ft. of head (kPa), and operate on _____ Volt,
3 phase, _____ Hz.
Dual Glycol Pump Package (Optional)
The dual pump package shall include pumps, enclo-
sure, and field mounted flow switch. The pumps
shall be wired to the drycooler control box which
includes a lead/lag switch for the pumps. The
standby pump shall automatically start upon failure
of the lead pump. Each pump shall be rated _____ for
GPM (l/s) at _____ feet of head (kPa).
 
GLYCOOL Coil
The GLYCOOL coil shall be constructed of copper
tubes and aluminum fins and be located upstream of
the evaporator coil. The GLYCOOL coil shall be
designed for closed-loop applications using properly
treated glycol solutions. The coil shall be rated at
_____ BTU/HR (kW) sensible cooling capacity with a
45°F (7.2°C) entering glycol solution temperature.
The GLYCOOL coil shall require _____ GPM (l/s) and
the total unit pressure drop shall not exceed _____
feet of water (kPa) when in the free cooling mode.