Instruction manual

Instruction Manual Supplement
D103560X012
DVC6200p Digital Valve Controller
November 2014
19
Note
Auto-calibration and tuning are part of the Device Setup procedure. However, if the DVC6200p is not physically connected to an
actuator/valve assembly you will not be able to perform the auto-calibration/tuning procedures. If Device Setup is being done prior
to mounting the device complete Device Setup up to auto-calibration and select Cancel, as shown in figure 21. Once the
DVC6200p is mounted to the actuator/valve assembly, calibration and tuning can be performed using the One-Step Local Quick
Setup to Calibrate and Tune procedure below.
Figure 21. Select Calibration Type > Cancel
Performing OneStep Local Quick Setup to Calibrate and Tune the
DVC6200p Digital Valve Controller
Note
This calibration method can be used when there is no Class2 master (ex. SIMATIC PDM) or other configuration software available.
WARNING
Changes to the instrument setup may cause changes in the output pressure or valve travel. Depending on the application,
these changes may upset process control, which may result in personal injury or property damage.
WARNING
During calibration the valve will move full stroke. To avoid personal injury and property damage caused by the release of
process fluid or pressure, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the
process fluid.