Instruction Manual

Instruction Manual
D103409X012
Detailed Setup
December 2013
48
Table 4‐1. Default Detailed Setup Parameters (continued)
Setup Parameter Default Setting
(1)
Travel History Alerts
Cycle Counter Alert Enable No
Cycle Counter Alert Deadband 1%
Cycle Counter Alert Point 1000000
Travel Accumulator Alert Enable No
Travel Accumulator Deadband 1%
Travel Accumulator Alert Point 1000000
Deviation & Other Alerts
Travel Deviation Alert Enable Yes
Travel Deviation Alert Point 5%
Travel Deviation Time 9.99 sec
Pressure Deviation Alert Enable Yes
Pressure Deviation Alert Point 5 psi
(3)
Pressure Deviation Alert Time 9.99 sec
Drive Signal Alert Enable Yes
Supply Pressure Alert Enable Yes
Supply Pressure Alert Point 19 psi
(3)
Travel Alerts
Travel Alert Lo Enable No
Lo Point -25%
Travel Alert Hi Enable No
Hi Point 125%
Travel Alert Lo Lo Enable No
Lo Lo Point -25%
Travel Alert Hi Hi Enable No
Hi Hi Point 125%
Deadband 5%
Electronics Alerts
Shutdown Activated Yes
Non‐Critical NVM Alert Enable No
Informational Status
Instrument Time Invalid Enable Yes
Calibration in Progress Enable No
Autocalibration in Progress Enable No
Diagnostics in Progress Enable No
Diagnostics Data Available Enable Yes
Integrator Saturated Hi Enable Yes
Integrator Saturated Lo Enable Yes
Pressure Control Active Enable Yes
Multi‐Drop Alert Enable No
Alert Record
Valve Alerts Enable Yes
Failure Alerts Enable Yes
Miscelleneous Alerts Enable No
Alert Record has Entries Enable Yes
Alert Record Full Enable Yes
1. The settings listed are for standard factory configuration. DVC6200 instruments can also be ordered with custom configuration
settings. For the default custom settings, refer to the order requisition.
2. If the instrument is shipped mounted on an actuator, these values depend upon the actuator on which the instrument is mounted.
3. U.S. Factory defaults only.