Partial Stroke Test using 475/375 Field Communicator
The Partial Stroke Test procedure contained in this Instruction Manual Supplement is to be considered as a guideline
only and should be modified to address site‐specific requirements. Use this procedure in conjunction with the
appropriate Safety Manual for FIELDVUE DVC6000 SIS Digital Valve Controllers for Safety Instrumented System (SIS)
Solutions (0‐20 mA or 0‐24 VDC
[D103035X012] or 4‐20 mA [D103294X012]) and the Fisher FIELDVUE DVC6000 SIS
Series Digital Valve Controllers for Safety Instrumented System (SIS) Solutions Instruction Manual (D103230X012). In
addition, exercise good engineering practices and abide by specific plant safety guidelines for safe operation.
Note
This procedure requires the use of the 475 or the 375 Field Communicator, device description (DD) rev. 1.
This procedure should be done with the digital valve controller's Instrument Mode set to “In Service”. There is nothing in the scope
of this procedure that requires the digital valve controller's Instrument Mode be set to “Out of Service”.
Partial Stroke Test Procedure
The Partial Stroke Test allows a DVC6000 SIS digital valve controller to move a valve from its current position to a
specified travel target, and then return it to its original position, while the instrument is in service and operational. In
an SIS application, it is important to be able to exercise and test the shut down valve to verify that it will operate when
commanded. This feature allows you to partially stroke the valve while continually monitoring the shut down signal. If
a demand arises, the test is aborted and the valve moves to its commanded position. The purpose of this test is to
ensure that the valve assembly moves upon demand.
1. Physically inspect the valve and positioner assembly in the field for any loose screws, loose mounting bracket, loose
feedback linkage, loose or broken tubing/conduit or the other mechanically loose conditions. Check air filter
regulators to ensure they are operating properly. Inspect gauges and verify that they are reading correctly.