User Guide

6-2
ValveLinkt Software
Network Scan Button—Opens the Network Alert Scan window and allows you to
scan selected tags. Using the Setup button you can select which tags to scan and
which alerts to scan for. Network Scan is only available on ValveLink software setup
to communicate through HART multiplexers.
Instrument Mode Button—For DVC5000, DVC6000, DVC2000, and DVC6200
instruments, allows changing the instrument mode between In Service and Out of
Service. For DVC5000f, DVC6000f, and DVC6200f instruments, allows changing the
Analog Output block, Resource block, and Transducer block target mode to another of the
permitted modes. A mode of Out of Service may be required to change a setup parameter,
or to run a calibration procedure or diagnostic test.
Control Mode Button—For DVC5000, DVC6000, DVC2000, and DVC6200
instruments only. Changes the instrument control mode between Analog and Digital.
Control mode defines where the instrument reads its set point. Choose Analog if the
instrument is to receive its set point over the 420 mA loop. Choose Digital if the instrument
is to receive its set point digitally via the HART communications link.
Setup Wizard Button—Starts the Setup Wizard to permit automatic setup and
travel calibration of the instrument using specified actuator information.
Detailed Setup Button—Opens the Detailed Setup window for the open tag.
Provides options for defining an instrument’s operating parameters. You can retrieve
information from the ValveLink software database or from the instrument. You can
also modify this data and save changes in the database or download them to the instrument.