Instruction Manual
Basis Weight Actuator
16
Figure 12. Limit Switch Connection Schematic, 4 Limit Switches (Optional)
E0017 / IL
INSTALLED AT
FACTORY IN
DIN RAIL
(O.D. = 10.7mm)
over-tightened, the switch action may
not allow the switch to close after it has
been tripped.
5. Use the handwheel to position the actuator to 90
degrees rotation (fully open).
6. Repeat steps 3 and 4 for the limit switch for 90 de-
grees rotation (LS1).
7. Replace the travel indicator cover and screws.
Stroking Speed
Stroking speed adjustments for the manual (MAN) and
automatic (COMP) modes are on the faceplate of the
IC500 card (key 3, figure 4). If it appears that motor
torque is too low, decrease stroking speed.
Note
In this manual, the default half-step in-
crement is referred to as a step.
The two trim potentiometers (screwdriver adjustments)
on the front panel of the IC2000 are for setting each of
the selectable preset speeds. The slowest speed is
approx. 600 steps/second in Manual mode and
approx. 5 steps/second in Computer mode; this speed
is governed by trim potentiometer resistance. The
Fastest speed is about 20 seconds for full stroke in