User guide

Specifications
47 Liebert
®
GXT4
Table 17 Battery run times
Number of External
Battery Cabinets
Load Percent
of Capacity
120VAC RT Models
208VAC
RT Model
500VA 700VA 1000VA 1500VA 2000VA 3000VA 3000VA
Internal Battery
10% 128 105 90 123 92 82 92
20% 82 61 37 52 38 38 39
30% 41 37 30 34 23 23 23
40% 38 32 23 23 16 16 16
50% 34 27 17 18 12 12 11
60% 31 22 14 14 9 9 9
70% 27 18 11 11 7 7 7
80% 23 15 9 9 5 5 5
90% 20 13 8 7 4 4 4
100% 17 11 7 6 3 3 3
Internal Battery
+ 1 External
Battery Cabinet
10% 448 426 332 335 303 224 303
20% 329 302 165 162 140 137 139
30% 223 163 137 129 96 95 95
40% 166 144 108 96 66 66 65
50% 153 125 92 72 49 49 48
60% 139 106 74 54 38 41 41
70% 125 94 61 46 33 34 34
80% 108 78 49 38 28 27 27
90% 100 69 40 34 23 23 25
100% 92 60 38 31 20 21 21
Internal Battery
+ 2 External
Battery Cabinets
10% 480 480 456 451 431 427 431
20% 454 433 331 318 207 202 205
30% 429 327 222 187 150 149 149
40% 333 265 166 151 124 124 123
50% 309 201 152 131 97 98 97
60% 225 164 137 107 75 76 75
70% 201 153 122 91 61 62 62
80% 166 142 105 74 50 50 50
90% 159 131 95 64 41 45 46
100% 151 120 79 53 38 41 41
Internal Battery
+ 3 External
Battery Cabinets
10% 480 480 480 480 455 452 455
20% 480 461 441 426 326 323 325
30% 458 438 336 312 197 196 195
40% 442 344 305 198 155 155 154
50% 426 322 209 160 136 136 135
60% 338 300 167 145 111 112 112
70% 322 213 157 130 96 98 98
80% 305 189 146 111 78 79 79
90% 225 163 135 99 68 70 70
100% 209 155 124 83 56 60 60