Cut Sheet

VersaMax I/O Industrial I/O
3.24
GE Intelligent Platforms Control Systems Solutions
www.ge-ip.com
Discrete Output Modules
Discrete output modules send control signals to devices such as contactors, indicator lamps, and
interposing relays that can also have two states. Modules require a carrier base (IC200CHSxxx).
IC200MDL750 IC200MDL930 IC200MDL940
Product Name
VersaMax Discrete Output Module,
24 VDC Positive Logic, 0.5A per point,
32 points
VersaMax Discrete Output Module,
Relay 2.0 A per point Isolated
Form A, 8 points
VersaMax Discrete Output Module,
Relay 2.0 A per point Isolated
Form A, 16 points
Lifecycle Status Active Active Active
Output Voltage
10.2-30 VDC, 12/24 VDC nominal 0-125 VDC, 5/24/125 VDC nominal;
0-265 VAC (47-63 Hz),
120/240 VAC nominal
0-125 VDC, 5/24/125 VDC nominal;
0-265 VAC (47-63 Hz),
120/240 VAC nominal
Number of Points 32 8 16
Channel to Channel Isolation No Yes Yes
Load Current per Point
0.5 A per point 2.0 A for 5-265 VAC, 2.0 A for 5-30 VDC,
0.2 A for 31-125 VDC
2.0 A for 5-265 VAC, 2.0 A for 5-30 VDC,
0.2 A for 31-125 VDC
Input and Output Response
Time- On/Off (ms)
0.2/1.0 10.0/10.0 10.0/10.0
Protection
No internal fuses No internal fuses or snubbers No internal fuses or snubbers
Points per Common 2 groups of 16 Isolated points Isolated points
External Power Supply
10.2-30 VDC, 12/24 VDC nominal 0-125 VDC, 5/24/125 VDC nominal; 0-265
VAC (47-63 Hz), 120/240 VAC nominal
0-125 VDC, 5/24/125 VDC nominal; 0-265
VAC (47-63 Hz), 120/240 VAC nominal
Load Current
0.5 A at 30 VDC maximum (resistive); 2.0 A
inrush maximum for 100 ms
10 mA per point minimum; 2.0 A for 5-265
VAC maximum (resistive); 2.0 A for 5-30 VDC
maximum (resistive); 0.2 A for 31-125 VDC
maximum (resistive)
10 mA per point minimum; 2.0 A for 5-265
VAC maximum (resistive); 2.0 A for 5-30 VDC
maximum (resistive); 0.2 A for 31-125 VDC
maximum (resistive)
5V Backplane Current
Consumption (mA)
90 maximum 245 maximum 490 maximum
LED Indicators
One LED per point shows individual
point ON/OFF state (logic side).
FLD PWR LED indicates field power is
present. OK LED indicates backplane
power is present.
One LED per point shows individual
point ON/OFF state (logic side).
FLD PWR LED indicates field power is
present. OK LED indicates backplane
power is present.
One LED per point shows individual
point ON/OFF state (logic side).
FLD PWR LED indicates field power is
present. OK LED indicates backplane
power is present.
Dimensions (W x H x D)
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors