Specifications

iPro DAC Manual Input and Output Setup • 11
used to power the devices controlled by the analog
outputs (e.g., damper actuator) may be used to supply
power to terminals 28 and 29.
Figure 4-12 - Analog Output Wiring
CAUTION! The devices controlled by these
analog outputs must be powered separately
with another transformer (do not use the same
secondary of the controller’s power) in order to prevent
the outputs from malfunctioning or being damaged.
Terminal Number on
Connector
Name
21 Analog Output 1
22 Analog Output 2
23 Analog Output 3
24 Analog Output 4
25 Analog Out Common
26 Analog Output 5
27 Analog Output 6
28 24VAC or 24VDC(-)
29 24VAC or 24VDC(+)
30 Analog Out Common
Table 4-8 -Digital Relay Output Connector Terminal Numbers