iProCHILL 4 DIN SERIES (v.1.
INDEX 1. IMPORTANT RECOMMENDATIONS 3 PRODUCT DISPOSAL (WEEE) 4 2. INTRODUCTION 5 3. GENERAL SPECIFICATIONS 5 PROCESSING ENVIRONMENT 5 Fields of application .................................................................................................................................................................................. 5 Hardware architecture ............................................................................................................................................
1. IMPORTANT RECOMMENDATIONS The symbol alerts the user of non-insulated “dangerous voltage” within the product area that is sufficiently high to constitute a risk of electric shock to persons. The symbol alerts the user of important operating and maintenance (assistance) instructions found in the documentation attached to the device. Dixell Srl cannot accept any liability for damages caused by modems that are not supported. Dixell Srl reserves the right to modify this manual without prior notice.
It is good practice to bear the following in mind for all Dixell products: o o o o o o Prevent the electronic circuits from getting wet as contact made with water, humidity or any other type of liquid can damage them. Comply with the temperature and humidity limits specified in the manual in order to store the product correctly. The device must not be installed in particularly hot environments as high temperatures can damage it (electronic circuits and/or plastic components forming part of the casing).
2. INTRODUCTION iPRO is the range of programmable controllers manufactured by Dixell. The range consists of programmable controllers, I/O expansions, drivers for electronic valves and graphical interfaces adapted to cover any type of application in the air-conditioning sector, cooling sector and any relative area. As the system is one of the most technologically advanced, it is flexible and can be customised for it to be adapted to the user's particular requirements. 3.
The programme and parameters are stored in a permanent flash memory. No data is lost in case of power failure. Internal web server with the Dixell website as default with the option of downloading a customised website for reading and writing variables with synoptic creation (via HTML). Ethernet port. USB port. Connection to the dedicated remote LCD display. CANBus. RS485 Master. RS485 Slave. The remote LCD display has the following features: 240x96 pixel LCD graphic display.
On if the machine is on and represents the Heat or Cool mode of operation based on the logic set in the CF31 parameter Cir1 on if in view values for circuit 1 Cir2 on if in view values for circuit 2 The icon is flashing on when counting the interval between defrosting sessions; the icon is steady on during the defrosting phase 4.
Displays Parameter Description min max um Resolution VISOGRAPH dP 1 dP 2 dP 3 dP 4 Allows you to personalise how an analog input is viewed on the first line of the 1st Visograph keyboard 0 = no display (the row remains empty) Allows you to personalise how an analog input is viewed on the second line of the 1st Visograph keyboard 0 = no display (the row remains empty) Allows you to personalise how an analog input is viewed on the third line of the 1st Visograph keyboard 0 = no display (the row rema
36. Dynamic set point probe 4÷20 mA 4.
Dp10 Bottom led display with unit on 0 = No Display 1 = Evaporator input temperature 2 = Output temperature evaporator 1 3 = Output temperature evaporator 2 4 = Evaporator common output temperature 5 = Condenser common input temperature 6 = Condenser input temperature 1 7 = Condenser input temperature 2 8 = Condenser output temperature 1 9 = Condenser output temperature 2 10 = Condenser common output temperature 11 = External air temperature 12 = Remote terminal temperature 13 = Combined defrost temperatur
4.5 DISPLAY SCREEN FOR THE DEVICE IN STD-BY Parameter dP11: Display in STD-BY 0= displays the "STD-BY" label 1= displays the values defined by par. dP9 and dP10 2= displays the "OFF" label dP11=0 dP11=1 The screen displays the values defined by par. dP9 and dP10. 1592032000 iProCHILL_4DIN GB r.1.0 20.01.
dP11=2 1592032000 iProCHILL_4DIN GB r.1.0 20.01.
4.6 BOTTOM SCREEN LED CLOCK LED When the time is displayed leds 1 / 2 flash FUNCTION MENU LEDS In functions menu leds 1 / 2 flash when the remaining time to the beginning of defrost in circuit 1 / 2 is displayed 5. DISPLAY OF CONTROLLED VALUES In normal function circuit 1 is always displayed as the default. The displayed circuit is marked by the icon Cir1 (circuit 1) or Cir2 (circuit 2). 5.
Fig.2 Cir2 icon on: the top screen displays the low pressure relative to circuit 2 (3.6 bar). Fig.2 6. OTHER SCREEN DISPLAYS 6.1 HOW TO DISPLAY THE SET POINT From the home page press the SET key, and the bottom screen will display SetC (set chiller) and by pressing a second time it will display SetH (set heat pump if configured). With the unit on only the set point relative to the state of operation will be displayed. To exit the set point Menu press the SET key. 1592032000 iProCHILL_4DIN GB r.1.0 20.
6.2 HOW TO CHANGE THE SET POINT 1) Inside the SET point menu, press the SET key for at least 3 sec; 2) To change the value act on the UP or DOWN keys To memorise the new set point press the SET key or wait for the time out to exit programming. 6.3 HOW THE VIEW THE REAL OPERATING SET POINT WITH EITHER ENERGY SAVING OR DYNAMIC SET ACTIVATED Activating set energy saving and dynamic set point is signalled by the Vseticon; it is possible to view them only if the machine is on.
KEY ACTION Press and release with default display FUNCTION It shows the set point in the chiller (SetC label) and/or in the heat pump (SetH label) With the unit in chiller or heat pump mode, if the Press and release in the SetS energy saving or dynamic set point function is menu enabled, it shows the real operating set (SetS label); the Vset icon is on.
3. Set the hour with the down and UP keys. Confirm the hour by pressing the SET key; the controller will display the following setting. 4. Repeat operations 2. 3. and 4.
Configuration Parameter Description min max um Resolution um °C °F Resolution tenth whole Unit CF 1 CF 5 Defines the type of unit to be controlled 0 = Chiller air / air 1 = Chiller air / water 2 = Chiller water / water Selection of unit working mode 1 = chiller only 2 = heat pump only 3 = chiller with heat pump Enable compressor operation 0 = chiller and heat pump 1 = chiller only 2 = heat pump only Motor-condensing unit 0 = no 1 = yes Temperature control, dynamic set point and energy saving funct
St 10 St 11 St 12 St 13 St 14 St 15 St 16 St 17 St 18 St 19 St 20 St 21 St 22 St 23 St 24 St 25 St 26 St 27 St 28 This defines the temperature control probe of the machine in heat pump mode 0= Evaporator input NTC temperature probe 1= Evaporator 1 output NTC temperature probe 2= Evaporator 2 output NTC temperature probe 3= Evaporator common output NTC temperature probe 4= temperature probe remote terminal 1 5= condenser water common input NTC temperature probe 6=circuit 1 condenser water input NTC
St 29 Activation offset with regulation of the neutral zone St 30 St 31 Activation delay with regulation of the neutral zone Deactivation offset with regulation of the neutral zone St 32 Deactivation delay with regulation of the neutral zone Displays Description min Remote terminal 1 Allows you to personalise how an analog input is viewed on the first line of the 1st Visograph keyboard 0 0 = no display (the row remains empty) Allows you to personalise how an analog input is viewed on the second line of
dP 15 Led display screen with unit in stand-by 0 = Stby above, nothing below 1 = Defined by parameters dP9 and dP10 2 = OFF above, nothing below 0 2 Machine set up Parameter SP 1 SP 2 SP 3 SP 4 SP 5 SP 6 Description min Analog inputs Working in temperature or pressure from an analog input 0 = NTC temperature/pressure function – 4-20 mA: The condensation temperature is controlled through the use of an NTC probe, while a transducer with an input of 4-20 mA must be used to control the evaporation pr
Parameters Description min Sd 1 Maximum increase in chiller mode dynamic set point -50.0 This determines the maximum variation of the working set point in chiller -58 mode Sd 2 Maximum increase in heat pump mode dynamic set point -50.0 This determines the maximum variation in the working set point in heat -58 pump mode Sd 3 Dynamic set point in chiller mode for the external air temperature setting -50.0 -58 Sd 4 Dynamic set point in heat pump mode for the external air temperature -50.
AH 11 Modulating auxiliary heating set point AH 12 Modulating auxiliary heating proportional band -50.0 -58 0.
CO 15 CO 16 CO 17 CO 18 CO 36 CO 37 Switch-on time with gas bypass valve / idle compressor start-up valve 0 (see partialisation mode) Compressor rotation - balancing - temperature control Selection criteria of compressors in the circuit 0 = Fixed sequence 1 = FIFO 0 2 = Balance 3 = Saturation 4 = Compressor weight Selection criteria of circuits 0 = Fixed sequence 1 = FIFO 0 2 = Balance 3 = Saturation 4 = Compressor weight Balance/saturation criteria 0= Hours 0 1= Peaks Resource control in proportional/
PA 1 PA 2 PA 3 PA 4 PA 5 PA 6 PA 7 PA 8 PA9 PA10 PA11 PA12 PA 13 PA 14 PA 15 PA 16 PA 17 PA 18 PA 19 PA 20 PA 21 PA 22 PA 23 PA 24 Evaporator pump/supply fan operation mode 0 = The pump and/or the supply fan are absent or not controlled. 1 = Continuous mode: the pump/supply fan is activated when the 0 machine is switched on (chiller/h.p. selection). 2 = Working on demand of the compressors: the water pump/supply fan are linked with the compressors being switched on and off.
PA 25 Determines the condenser water pump/s anti-freeze operation when the device is OFF or on Stand-by 0 = always OFF in remote OFF or Stand-by 0 1 = ON, parallel with the anti-freeze heaters 2 = on in remote OFF or Stand-by, depending on the temperature control request PA 26 Condenser anti-freeze temperature control probe alarm 0 = disabled 1 = regulation on common condenser water input probe 2 = regulation on common condenser water input probe and condenser input 1 3 = regulation on common condenser wat
Un 1 Un 2 Un 3 Un 4 Un 5 Un 6 Un 7 Un 8 Un 9 Un 10 Un 11 Un 12 Comp.
Condensing fan Parameters Description min FA1 Fan regulation 0= not present 1= always on 0 2 = ON/OFF step insertion 3= ON/OFF continuous step insertion 4= proportional speed regulator FA2 Fan operation mode 0= depending on the compressor 0 1= independent from the compressor FA3 MAX speed fan peak time after ON (TRIAC) At every start-up the fan is powered at maximum voltage for time FA03, irrespective of the 0 condensation temperature/pressure.
FA15 FA16 FA17 FA18 FA19 FA20 FA21 FA22 FA23 FA24 FA25 FA26 FA27 FA28 FA29 CUT - OFF delay time. This allows you to set a delay time for the activation of the CUT - OFF function at fan start-up. If at compressor start-up the proportional regulator requests the fans to be shut off and FA15 0, the fan will be forced at minimum speed for the set time. If FA15=0, the function is not enabled. Night function speed in chiller mode.
FA30 FA31 FA32 FA33 FA34 FA35 FA36 FA37 FA38 FA39 FA40 FA41 SET 4th STEP This allows you to set the condensation temperature / pressure value in heat pump mode that corresponds to the operation of the relay output in ON configured as the 4th condensation fan speed step. With Par. FA01 = 2 / 3 becomes the differential on the step itself of circuit 3 in heat pump mode (see fans regulation graph). With Par. FA01 = 2 / 3 becomes the differential on the step itself of circuit 10.
Anti-freeze heaters – support Parameters Description Ar 1 Set point for anti-freeze/support heaters in chiller mode. The temperature value below which the heaters start up. Ar 2 Anti-freeze/support heaters band regulation in chiller mode Ar 3 Ar 4 Set point for anti-freeze/support heaters in heat pump mode. The temperature value below which the heaters start up. Anti-freeze/support heaters band regulation in heat pump mode min -50.0 -58 0.1 1 -50.0 -58 0.
dF 8 dF 9 dF 10 Waiting time with compressor OFF after defrost (inversion of 4-way valve) Defrost interval in the same circuit Set start temperature for combined defrost cycle circuit 1 after the counting of parameter dF09 elapses Set start temperature for combined defrost cycle circuit 2 after the counting of parameter dF09 elapses 0 1 -50.0 -58 -50.
rC 1 rC 3 rC 4 rC 5 rC 6 rC 7 Recovery function 0 = disabled 1 = separate hydraulic circuits 2 = hydraulic circuits in parallel 3 = total recovery gas side Choice of priority for recovery mode (rC1 = 3) 0= priority to user side 1= priority to recovery side Forced step deactivation time Forced step deactivation time after rotation of recovery valve Minimum operation time in recovery mode Minimum delay between recovery end and next recovery Set recovery function disabling rC 8 Recovery function enabling d
FS 15 FS 16 FS 17 FS 18 FS 19 FS 20 FS 21 FS 22 FS 23 FS 24 Minimum Anti legionella set point value. This defines the minimum limit that can be used to set the Anti legionella set point. Maximum Anti legionella set point value This defines the maximum limit that can be used to set the Anti legionella set point. Anti-legionella activation time Day of activation Anti-legionella 0=disabled, 1=Sunday, 2=Monday...
FS 48 Do not turn the valves in production of domestic water only with dedicated return 0 0=function not active 1=function active FS 49 Evaporator water pump shut off during production of domestic water only in dedicated return mode 0 0=function not active 1=function active FS 50 Overlapping time between evaporator water pump and domestic water pump in dedicated return mode, during the transition to domestic water 0 only with FS49=1 FS 51 Waiting time before switching inversion valves from chiller to h.p.
FC 18 FC condenser water set point temperature to activate free cooling FC 19 FC 20 FC 21 Delay in free cooling activation The FC condenser water temperature must be below the FC18 set point for FC19 seconds before the effective activation of free cooling Switching delay for ON/OFF free cooling valves Free cooling set point FC 22 Free cooling differential FC 23 FC 24 FC 25 Delay in outfeed from free cooling Delay in activation of anti-freeze prevention in free cooling Free cooling valve set point in
US 12 Auxiliary relay differential 3 (see auxiliary relay operation and diagrams) US 14 US 15 Auxiliary relay 4 Auxiliary relay 4 operation (see auxiliary relay operation and diagrams) 0 = not enabled 1= always enabled with direct action 2= enabled with direct action only with unit ON 3= always enabled with inverse action 4= enabled with inverse action only with unit ON Analog input configuration for control of the auxiliary relay 4 Set point of auxiliary relay 4 (see auxiliary relay operation and diagra
US 31 US 32 US 33 Proportional auxiliary output 3 operation (see auxiliary output operation and diagrams) 0= not enabled 1= always enabled with direct action 2= enabled with direct action only with unit ON 3= always enabled with inverse action 4= enabled with inverse action only with unit ON Analog input configuration for control of the auxiliary output 3 Set point for auxiliary 3 (see auxiliary output operation and diagrams) US 34 Differential for auxiliary 3 (see auxiliary output operation and diagram
AL 5 AL 9 Maximum number of interventions per hour of the low pressure alarm from a digital/analog input Reset is always manual if AL05 = 0 Reset is always automatic if AL05 = 60 Reset switches from automatic to manual if AL05 falls between 1 and 59 Low temperature / pressure alarm in defrost mode 0 = not enabled 1= enabled Low temperature / pressure alarm delay in defrost mode Low temperature / pressure alarm with the unit in remote OFF or standby mode 0 = alarm detection disabled 1 = alarm detection ena
AL 29 AL 32 Compressor thermal overload alarm function 0 = blocks the individual compressor 1 = blocks the circuit Compressor thermal overload alarm with compressor OFF 0 = alarm detection disabled 1 = alarm detection enabled Compressor thermal overload alarm reset password value (see procedures) Anti-freeze alarm in chiller mode Anti-freeze minimum set point limit in chiller mode AL 33 Anti-freeze maximum set point limit in chiller mode AL 34 AL 39 Anti-freeze alarm set point in chiller.
AL 47 AL 50 Anti-freeze temperature control probe alarm in chiller mode 0= disabled 1 = regulation on evaporator input 2 = regulation on evaporator output 1 3 = regulation on evaporator output 2 4 = regulation on evaporator output 1 / 2 5 = regulation on evaporator output 1 / 2 and common output Anti-freeze temperature control probe alarm in heat pump mode 0= disabled 1 = regulation on evaporator input 2 = regulation on evaporator output 1 3 = regulation on evaporator output 2 4 = regulation on evaporator
AL 66 Alarm log reset password value (see procedures) 0 Anti-freeze alarm in free cooling AL 67 Delay of the anti-freeze alarm signal in free cooling 0 AL 68 Maximum number of interventions per hour for anti-freeze alarm in free cooling Reset is always manual if AL68 = 0 0 Reset is always automatic if AL68 = 60 Reset switches from automatic to manual if AL68 falls between 1 and 59 Auxiliary heating alarms AL 69 The behaviour of the compressors in case of auxiliary heating alarms 0 = they follow their behav
Et12 Et13 Et14 Et15 Et16 Et17 Selection of output circuit valve 2 driver 2 0 = Not present 1 = Circuit 1 2 = Circuit 2 Et31 Number of additional steps to achieve complete closure. When a closing request is received, the valve starts from the current number of steps and moves to 0, then closes for the set number of steps Number of return steps in opening mode after the valve has been closed completely.
Et52 Overheating regulation dead band in heat pump mode Et53 Et57 High overheating threshold. The alarm status is signalled after the high overheating alarm activation delay Low overheating threshold. In this case, an additional integral time is added to the normal regulation in order to speed up the return to the normal operating conditions Additional integral time to prevent low overheating in heat pump mode MOP protection activation threshold.
28. 29. 30. 31. Circuit 1 condensation probe (NTC temperature) Circuit 2 condensation probe (NTC temperature) Circuit 1 condensation probe (pressure 4÷20 mA / ratiometric 0÷ 5Volt) Circuit 2 condensation probe (pressure 4÷20 mA / ratiometric 0÷ 5Volt) Evaporation transducers 32. Circuit 1 evaporation pressure probe (pressure 4÷20 mA / ratiometric 0÷ 5Volt) 33. Circuit 2 evaporation pressure probe (pressure 4÷20 mA / ratiometric 0÷ 5Volt) Auxiliary transducers and dynamic set point 34.
49. 50. 51. 52. 53. 54. 55. 56. 57. 58. 59. 60. 61. 62. 8.3 0. 1. 2. 3. 4. 5. 6. 7.
39. 40. 41. 42. 43. Heaters (second step) for domestic water production Heaters (third step) for domestic water production Solar panel pump Solar coil activation/deactivation ON/OFF valve Domestic water pump Compressor 1 44. Direct start-up: compressor relay 1 PW start-up: coil relay 1 compressor 1 Star / triangle start-up: relay line 1 compressor 1 45. PW start-up: coil relay 2 compressor 1 Star / triangle start-up: relay line 2 compressor 1 46. Star centre relay star start up / triangle compressor 1 47.
89. IV management valve 14 90. IV management valve 15 91. IV management valve 16 8.4 CONFIGURATION OF PROPORTIONAL OUTPUTS Configurable output signal 4÷20mA - 0÷10V 0. output disabled 1. proportional output 0÷10V condensation control circuit 1 2. proportional output 0÷10V condensation control circuit 2 3. proportional output 0÷10V damper / mixing valve free cooling direct action 4. proportional output 0÷10V damper / mixing valve free cooling direct action 5. auxiliary output 1 0÷10V 6.