Specifications

1592032000 iProCHILL_4DIN GB r.1.0 20.01.2012 iProCHILL 4 DIN series 30/48
FA30 SET 4th STEP This allows you to set the condensation temperature /
pressure value in heat pump mode that corresponds to the operation of
the relay output in ON configured as the 4th condensation fan speed
step.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Tenths
whole
Tenths
whole
FA31 With Par. FA01 = 2 / 3 becomes the differential on the step itself of circuit
3 in heat pump mode (see fans regulation graph).
0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Tenths
whole
Tenths
whole
FA32 With Par. FA01 = 2 / 3 becomes the differential on the step itself of circuit
10.16 cm heat pump mode (see fans regulation graph).
0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Tenths
whole
Tenths
whole
Operation in defrost (dF33 = 2)
FA33 Minimum fan speed in defrost mode. This allows you to set a
minimum value for proportional regulation of the fans in defrost
mode. It is expressed as a percentage of the maximum voltage
allowed.
0 FA40 %
FA34 Maximum fan speed in defrost mode. This allows you to set a
maximum value for proportional regulation of the fans in defrost
mode. It is expressed as a percentage of the maximum voltage
allowed.
FA40 100 %
FA35 Proportional regulation
Set maximum fan speed temperature/pressure in defrost mode. This
allows you to set the condensation temperature / pressure value in
defrost mode that corresponds to the minimum fan speed.
Step regulation
SET 1st STEP This allows you to set the condensation temperature /
pressure value in defrost mode that corresponds to operation in ON
of the relay output, configured as the 1st condensation fan speed
step.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Tenths
whole
Tenths
whole
FA36 Proportional regulation
Set minimum fan speed temperature/pressure in defrost mode. This
allows you to set the condensation temperature / pressure value in
defrost mode that corresponds to the maximum fan speed.
Step regulation
SET 2nd STEP This allows you to set the condensation temperature /
pressure value in defrost mode that corresponds to operation in ON
of the relay output, configured as the 2nd condensation fan speed
step.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Tenths
whole
Tenths
whole
FA37 Proportional regulation
Proportional band regulation of fans in defrost. This allows you to set a
temperature / pressure differential that corresponds to a variation from
minimum to maximum fan speed.
Step regulation
With Par. FA01=2/3 becomes the differential on the step itself of circuit 1
in defrost mode (see fans regulation graph).
0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Tenths
whole
Tenths
whole
FA38 Proportional regulation
Differential CUT- OFF in defrost. This allows you to set a temperature /
pressure differential in defrost mode to shut off the fan.
Step regulation
With Par. FA01=2/3 becomes the differential on the step itself of circuit 2
in defrost mode (see fans regulation graph).
0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Tenths
whole
Tenths
whole
FA39 Over ride CUT- OFF in defrost. This allows you to set a temperature /
pressure differential in defrost where the fan maintains minimum speed.
0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Tenths
whole
Tenths
whole
FA40 Night function speed in defrost mode. This allows you to set a
maximum value for proportional regulation of the fans in defrost
mode. It is expressed as a percentage of the maximum voltage
allowed.
FA33 FA34 %
FA41 SET 3rd STEP This allows you to set the condensation temperature /
pressure value in defrost mode that corresponds to relay output operation
in ON configured as the 3rd condensation fan speed step.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Tenths
whole
Tenths
whole
FA42 SET 4th STEP This allows you to set the condensation temperature /
pressure value in defrost mode that corresponds to relay output operation
in ON configured as the 4th condensation fan speed step.
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Tenths
whole
Tenths
whole
FA43 With Par. FA01=2/3 becomes the differential on the step itself of circuit
7.62 cm defrost mode (see fans regulation graph).
0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Tenths
whole
Tenths
whole
FA44 With Par. FA01=2/3 becomes the differential on the step itself of circuit
10.16 cm defrost mode (see fans regulation graph).
0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Tenths
whole
Tenths
whole