Liebert® APM™ User Manual–15-90kVA, 120, 208, 480 and 600V, 50/60Hz
TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 1.1 Battery Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 3.4.1 3.4.2 3.4.3 3.4.4 3.4.5 Input Dry Contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liebert BDC Interface . . . . . . . . . . . . . . . . . . . . .
7.0 INSTALLATION DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62 8.0 LIEBERT INTELLISLOT® INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 8.1 Liebert IntelliSlot Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 8.2 Liebert IntelliSlot Web Card—SNMP/HTTP Network Interface Card . . . . . . . . . . . . . . . . . 78 8.2.
10.3 UPS Battery Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 10.4 Switching the UPS from Normal Operation to Maintenance Bypass . . . . . . . . . . . . . . . . . 103 10.5 Switching the UPS from Maintenance Bypass to Normal Operation . . . . . . . . . . . . . . . . . 104 10.6 De-Energize Liebert APM with Maintenance Bypass Cabinet . . . . . . . . . . . . . . . . . . . . . . 105 10.
FIGURES Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Figure 21 Figure 22 Figure 23 Figure 24 Figure 25 Figure 26 Figure 27 Figure 28 Figure 29 Figure 30 Figure 31 Figure 32 Figure 33 Figure 34 Figure 35 Figure 36 Figure 37 Figure 38 Figure 39 Figure 40 Figure 41 Figure 42 Figure 43 Figure 44 Figure 45 Figure 46 Figure 47 Figure 48 Cabinet arrangement . . . . . .
Figure 49 Figure 50 Figure 51 Figure 52 Figure 53 Figure 54 Figure 55 Figure 56 Figure 57 Figure 58 Figure 59 Figure 60 Figure 61 Figure 62 Figure 63 Figure 64 Figure 65 Figure 66 Figure 67 Figure 68 Figure 69 Figure 70 Figure 71 Figure 72 Figure 73 Figure 74 Figure 75 Figure 76 Figure 77 Figure 78 Figure 79 Figure 80 Figure 81 Figure 82 Figure 83 Figure 84 Figure 85 Figure 86 Figure 87 Figure 88 UPS dimensions continued, center of gravity—side, top and bottom views . . . . . . . . . . . . . . . . .
TABLES Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Table 12 Table 13 Table 14 Table 15 Table 16 Table 17 Table 18 Table 19 Table 20 Table 21 Table 22 Table 23 Table 24 Table 25 Table 26 Table 27 Table 28 Table 29 Table 30 Table 31 Table 32 Table 33 Table 34 Table 35 Table 36 Table 37 Table 38 Table 39 Table 40 Table 41 Table 42 Table 43 Table 44 Table 45 Table 46 Table 47 Table 48 Table 49 Battery voltage, nominal and float . . . . . . . . . . . . . . . . . . .
Table 50 Table 51 Table 52 Table 53 Table 54 Table 55 Table 56 Table 57 Inverter output to critical load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component service life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery voltage record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation of the Liebert APM, Liebert Bypass Distribution Cabinet™ and batteries (where applicable). Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel.
Ground Leakage Currents ! CAUTION Risk of electric shock from high leakage current. Can cause injury, property damage and death. EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY. Earth leakage current exceeds 3.5 mA and is less than 1000 mA. Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous RCCB or RCD devices.
Battery Cabinet Precautions The following warning applies to all battery cabinets supplied with UPS systems. Additional warnings and cautions applicable to battery cabinets may be found in 5.0 - Battery Installation. ! WARNING Risk of improper handling. Can cause injury, property damage and death. Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet (after initial installation). • Battery cabinets contain non-spillable batteries. • Keep units upright.
GLOSSARY OF SYMBOLS Risk of electrical shock ! Indicates caution followed by important instructions AC input AC output i - Requests the user to consult the manual + Indicates the unit contains a valve-regulated lead acid battery PbH2SO4 R Recycle DC voltage AC voltage Equipment grounding conductor Bonded to ground Liebert® APM™ 4
Introduction 1.0 INTRODUCTION The Liebert APM UPS is a transformer-free, hardware-scalable, online uninterruptible power system with 208/120V input and 208/120V output capability. The Liebert APM can operate with either a 50 or 60Hz input and provide a matching output frequency conversion. The rack-mounted 15kVA/kW modules allow scaling the UPS’s capacity in 15kVA increments from 15kVA to a maximum of 90kVA in a single frame.
Introduction ! WARNING Risk of electrical shock and high short circuit current. Can cause equipment damage, personal injury and death. The following precautions must be observed when working on batteries: • Remove watches, rings and other metal objects. • Use tools with insulated handles. • Wear rubber gloves and boots. • Do not lay tools or metal parts on top of batteries. • Disconnect charging source prior to connecting or disconnecting battery terminals. • Determine whether the battery is grounded.
Introduction Matching Battery Cabinets—Optional Although the individual battery cells are sealed (valve-regulated) and require only minimal maintenance, the Battery Cabinets should be given a periodic inspection and electrical check. Checks should be performed at least annually to ensure years of trouble-free service. Voltage Records: With the Battery Cabinet DC circuit breaker closed and the connected UPS operating, measure and record battery float voltage.
Installation 2.0 INSTALLATION This section describes the Liebert APM’s environmental requirements and mechanical considerations that must be taken into account when planning the positioning and cabling of the UPS equipment. Because each site is unique, this section presents a guide to general procedures and practices that should be observed by the installing engineer, rather than step-by-step installation instructions. ! WARNING Risk of electric shock. Can cause injury, property damage and death.
Installation 2.1 Initial Inspections 1. While the Liebert APM and ancillary cabinets are still on the truck, inspect the equipment and shipping container for any signs of damage or mishandling. Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with the shipping agency immediately and contact Liebert Services at 1-800-LIEBERT to inform them of the damage claim and the condition of the equipment. 2.
Installation 2.3.2 Environmental Considerations Before installing the Liebert APM, verify that the UPS room satisfies the environmental conditions stipulated in 11.2 - UPS Environmental, paying particular attention to the ambient temperature and air exchange system. The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).
Installation 2.5 Mechanical Considerations The Liebert APM is constructed with a steel frame and removable panels. Top and side panels are secured to the chassis by screws. The doors may be opened for access to power connections bars, auxiliary terminals blocks and power switches. The UPS comes with an Operator Control Panel that provides basic operational status and alarm information. The cabinet houses both the power components and the internal batteries. Cooling is provided by internal fans.
Installation 2.5.4 Special Considerations for Parallel Systems 1. Consider the grounding configuration of the UPS system before finalizing module placement. For optimal ground performance, the Liebert APM modules should be close together. See 3.2.6 Cabling Guidelines. 2. For optimal load-sharing performance, the UPS bypass input cables and output cables should be approximately the same length, ±10 percent. 3.
Installation 2.6.1 Optional Cabinets If the Liebert APM installation includes a Liebert BDC, the UPS must be positioned to allow the Liebert BDC to be bolted to right side of the Liebert APM (see Figure 1). The Liebert BDC must be cabled and bolted to the Liebert APM before the UPS and bypass cabinet are moved into their final position. Connect the input wiring to the Liebert BDC ONLY after the units are connected and positioned.
Installation 2.8 Liebert FlexPower™ Assembly Figure 2 Liebert FlexPower assembly indicators and controls Fault LED Run LED DIP Switches Battery Start Button Ready Switch The Battery start button allows starting of UPS on battery; refer to 10.3 - UPS Battery Start. The Run LED is illuminated Green when the Liebert FlexPower assembly is operating normally. The Fault LED will illuminate red when the Liebert FlexPower assembly has a problem.
Electrical Connections—UPS 3.0 ELECTRICAL CONNECTIONS—UPS The UPS requires both power and control cabling once it has been mechanically installed. All control cables must run separate from power cables in metal conduits or metal ducts that are electrically bonded to the metalwork of the cabinets to which they are connected. ! WARNING Risk of electric shock. Can cause property damage, injury and death.
Electrical Connections—UPS 3.2.1 Rectifier and Bypass Input Supply of the UPS Overcurrents Install suitable protective devices in the distribution unit of the incoming mains supply, considering the power cable current-carrying capacity and overload capacity of the system. Generally, the magnetic circuit breaker with IEC60947-2 tripping curve C (normal) at the 125% of the nominal current listed in Table 41 is recommended.
Electrical Connections—UPS 3.2.4 UPS Input Configuration By default, the Liebert APM ships with internal links installed between the bypass input and main (rectifier) input (single input configuration see Figure 84). Figure 4 shows the Liebert APM in a split bypass (single source dual-input) configuration. In this configuration, the static bypass and the maintenance bypass lines are supplied by the same source using separate feeds.
Electrical Connections—UPS 3.2.5 UPS Input Configuration with Transformers Figure 5 shows the Liebert APM in a split bypass (single-source, dual-input) configuration using two transformers. One transformer is inside the Bypass Distribution Cabinet and the other inside the UPS. In this configuration, the static bypass and the maintenance bypass lines are supplied by the same source using separate feeds. Both feeds must be protected externally with properly sized protective devices.
* Utility 19 Rect. Input Ø to GRD * Customer must supply shunt trip to rectifier input breaker with 120V coil ØA ØB ØC RIB Utility ØA ØB ØC BIB Input Neutral W07 W08 W09 To Bypass Input Kirk Key K1 Ground To Unit Frame W85 W86 W84 W83 W87 See Note 1 PE N A B C Rect. Input 1 UPS AC Output Bypass Input Liebert APM UPS N A B C 2 4 3 1 3 3 4 W88 W89 NOTES 1. Customer-furnished electrode conductor to be installed in accordance with national and local electrical codes. 2.
Electrical Connections—UPS 3.2.6 Cabling Guidelines The following are guidelines only and are superseded by local regulations and codes of practice where applicable. Use wiring rated at 75°C or greater. 1. Take special care when determining the size of the neutral cable, as current circulating on the neutral cable may be greater than nominal current in the case of non-linear loads. Refer to the values in 11.4 - UPS Electrical Characteristics. 2.
Electrical Connections—UPS Figure 7 Input busbars—Liebert APM 45kVA frame 1.75" (44mm) 1.52" (39mm) (Typ.) (Typ.) 1.75" (44mm) 1.65" (42mm) ø .50" (13mm) ø .55" (14mm) 1.65" (42mm) 2 places 4 places .8" (20mm) 3.54" (90mm) (Typ.) .7" (18mm) .8" (20mm) 1.6" (41mm) DETAIL D Top View DC Busbars DETAIL C Top View Ground ø .50" (13mm) Typ. Main Input Busbars Same for Bypass and Output Busbars See Detail D TOP VIEW 1.75" (44mm) Typ. BOTTOM VIEW 31.5" (800mm) 37.
Electrical Connections—UPS Figure 8 Input busbars—Liebert APM 90kVA frame NOTES 1. Dimensions are in inches [mm]. 2. Control wiring and power wiring must be run in separate conduits. 3. Emerson recommends using only copper cables. 4. All wiring must be in accordance with national and local electrical codes. Liebert® APM™ 22 UAM02021 Rev.
Electrical Connections—UPS Figure 9 Liebert BDC TOP VIEW BOTTOM VIEW 1. All dimensions are in inches (mm). 2. Control wiring and power wiring must be run in separate conduits. 3. Only copper cables are recommended. 4. All wiring is to be in accordance with national and local electrical codes. 5. If bypass distribution cabinet is attached to the UPS, Emerson will supply the interconnection cables. 6. See UAM06020B, Pg. 2 of 2. 37.5" (953mm) 23.6" (600mm) LDB 78.
Electrical Connections—UPS Figure 10 Busbars—Liebert BDC UPS Bus Ø .44" (11mm) Typical Neutral Bus 5" x 8.9" (127 x 227mm) Ø .44" (11mm) Typical System Input Bus See Detail B 1.38" (35mm) 1.38" (35mm) Ø .56" 1.38" (35mm) (14mm) 1.38" (35mm) Typical DETAIL A 2.44" (62mm) 1.75" (44.5mm) Typical All Busbars Ground Bus 5" x 4" (127 x 102mm) 2.44" (62mm) Ø .56" (14mm) Typical Input/Outout Bus Typical 1.5" x 8.9" (38 x 227mm) Input Breaker Ø .44" (11mm) Typical Input Ground Bus Ø .
Electrical Connections—UPS Figure 11 Busbars—External 600mm battery cabinet 3.66" (93mm) 3.66" (93mm) 1.75" (45mm) 1.75" (45mm) .56" Dia.(14.3mm) TERMINAL SPECIFICATIONS Unit Rating: 15-90kVA Bolt Shaft Size: M10 Torque: 240 lb-In (27Nm) .44" Dia. (11.1mm) 1.75" (45mm) 1.75" (45mm) 1.65" (42mm) Top View Bottom View 1.75" (45mm) 3.66" (93mm) 23.6" (600mm) 1.65" (42mm) 4.96" (126mm) DETAIL A Alber Battery Monitoring 37.5" (953mm) DC Connection Busbars Ground Bus 78.
Electrical Connections—UPS Figure 12 Busbars—External 900mm battery cabinet 3.31" (84mm) 3.31" (84mm) 1.65" (42mm) 1.65" (42mm) .56" Dia. (14.3mm) 1.75" (45mm) 1.75" (45mm) 1.75" (45mm) TOP VIEW Alber Battery Monitoring .44" Dia. (11.1mm) BOTTOM VIEW 35.4" (900mm) DETAIL A 37.5" (953mm) DC Connection Busbars Ground Bus 78.7" (2000mm) See Detail A Front View Left Side View Door Removed Panel Removed NOTES 1. Dimensions are in inches [mm]. 2.
Electrical Connections—UPS Figure 13 Accessory fuses BDSi Fuse Block (optional) Backfeed Breaker Fuse Block Figure 14 Dual input backfeed breaker wiring when bypass distribution cabinet not used 1. Auxiliary contacts not needed for backfeed breaker operation. 2. A 120V shunt trip coil is required for proper operation.
Electrical Connections—UPS 3.2.9 Safety Ground The safety ground busbar is below the neutral input and output busbars as shown in Figure 15 below. The safety ground cable must be connected to the ground busbar and bonded to each cabinet in the system. This ground busbar is then connected to the ground electrode conductor (GEC). All cabinets and cable conduit should be grounded in accordance with local regulations. ! WARNING Risk of electrical shock and arc flash.
Electrical Connections—UPS Figure 15 Ground and neutral busbar connections—45kVA frame busbars 1.75" (44mm) 1.52" (39mm) (Typ.) (Typ.) 1.75" (44mm) 1.65" (42mm) ø .50" (13mm) ø .55" (14mm) 4 places .8" (20mm) 1.65" (42mm) 2 places 3.54" (90mm) (Typ.) .7" (18mm) .8" (20mm) 1.6" (41mm) DETAIL D Top View DC Busbars DETAIL C Top View Ground ø .50" (13mm) Typ. Main Input Busbars Same for Bypass and Output Busbars See Detail D TOP VIEW 1.75" (44mm) Typ. BOTTOM VIEW 31.5" (800mm) 37.
Electrical Connections—UPS Figure 16 Ground and neutral busbar connections—90kVA frame busbars NOTES 1. Dimensions are in inches [mm]. 2. Control wiring and power wiring must be run in separate conduits. 3. Emerson recommends using only copper cables. 4. All wiring must be in accordance with national and local electrical codes. Liebert® APM™ 30 UAM02021 Rev.
Electrical Connections—UPS 3.2.10 Protective Devices For safety, it is necessary to install circuit breakers in the input AC supply external to the UPS system. Given that every installation has its own characteristics, this section provides guidelines for qualified installation engineers with knowledge of operating practices, regulatory standards and the equipment to be installed.
Electrical Connections—UPS Common Input Connections 5. For common bypass and main inputs, connect the AC input supply cables to the UPS input terminals (A2-B2-C2-N1) and tighten the connections to 240lb-in. (27N-m) (M10 Bolt). Ensure correct phase rotation. NOTE For common bypass and main inputs, the AC input cables must be connected to the bypass terminal (A2-B2-C2-N1) but not the main input terminal (A2-B2-C2). Split Bypass Connections 6.
Electrical Connections—UPS Figure 17 Static bypass assembly connections to display cabinet and options Monitor Operator Control Panel J4 Battery Cabinet J8 J5 Bypass Distribution Cabinet J12 Bypass Backfeed Protection J11 Mains Backfeed Protection J10 Temp Sensor (optional) and BCB Control Board J4 Ground Fault (optional) Sensor & BCB Control Board On Generator (optional) J9 Static Bypass Assembly Figure 18 Auxiliary terminal block detail (static switch assembly front panel) Input /output dr
Electrical Connections—UPS 3.4 Dry Contacts The UPS provides input dry contacts and output dry contacts on the Auxiliary Terminal Block (ATB). 3.4.1 Input Dry Contacts External input dry contacts are connected via the ATB. Dry contacts are available for environment detection, battery ground fault detection, etc. The UPS accepts external signal from zero-voltage (dry) contacts connected through external dry contact terminals produced, and these terminals are on the static bypass assembly.
Electrical Connections—UPS 3.4.2 Output Dry Contacts The Auxiliary Terminal Block has three output dry contact relays (see Figure 20 and Table 5). Figure 20 Output dry contacts and EPO wiring MFP_O MFP_S INV_O MFP_C J10 INV_S BFP_O BFP_C INV_C J12 BFP_S J11 NOTE: The black square () on each connector indicates Pin 1. Refer to Figure 18 for the location of connectors J10, J11 and J12. Table 5 Output dry contact relays Position Name J11.2 BFP_O Bypass feedback protection relay.
Electrical Connections—UPS 3.4.4 Battery Cabinet Interface Connectors The battery cabinet interface is on the Auxiliary Terminal Block at J8 and J4. Refer to Figure 18 for the location of connectors J4 and J8 and to Figure 19 for circuit details. Table 7 Battery cabinet interface Position Name Description J4.1 BAT_IN Internal Battery Temperature Detection J4.2 +12V J4.3 BAT_OUT J4.4 GND J8.1 DRIVER BCB Driver Signal J8.2 BCB_IN BCB Contact State J8.3 GND J8.
Electrical Connections—UPS Table 8 EPO input contact relays Position Name Description J6.1 EPO_NC EPO Activated when opened to J6.2 J6.2 +12V EPO Activated when opened to J6.1 J6.3 +12V EPO Activated when shorted to J6.4 J6.4 EPO_NO EPO Activated when shorted to J6.3 NOTE The Emergency Stop action within the UPS shuts down the rectifier, inverter and static bypass. It does not internally disconnect the input power supply.
Parallel System and LBS System Installation 4.0 PARALLEL SYSTEM AND LBS SYSTEM INSTALLATION This chapter gives details on the installation of a parallel system and an LBS system. 4.1 General A parallel Liebert APM system can consist of two Liebert APM cabinets connected in parallel without a main system static bypass. Instead, the bypass static switches of each UPS share the load when the system transfers to the utility bypass supply.
Parallel System and LBS System Installation Figure 23 UPS system with external maintenance switch MBB Buyout Liebert APM Paralleling Switchboard * System AC Input 4 Wire +GND UIB See Note 7 UIB Opt.
Parallel System and LBS System Installation 4.2.4 Power Cable The power cable wiring is similar to that of the UPS module. Refer to 3.1 - Power Cabling. The bypass and rectifier input supplies must use the same neutral line input terminal. If the input has a current leakage protective device, the current leakage protective device must be fitted upstream of the neutral line input terminal.
Parallel System and LBS System Installation Figure 25 Output breaker control wiring Buyout Liebert APM Paralleling Switchboard MBB System AC Input 4-Wire + GND MIB MOB1 UIB UHRF3S67X2 (J5) AC Output 4-Wire + GND See Note 2 Liebert APM #1 TB2 1 1 See Note 3 2 J5 3 2 4 X2 J5 3 MOB2 UIB Liebert APM #2 1 Notes 1. See drawings UAM01080A, UAM01080B, UAM01080C, UAM01080E and UAM01080F. 2. MBB auxiliary switch connections are on the normally closed and common positions. 3.
Parallel System and LBS System Installation 4.2.8 Key Interlock System Figure 27 Key interlock system control wiring AC Input ØA ØB ØC Buyout Liebert APM Paralleling Switchboard MBB AC Output ØA ØB ØC Neu See Note 2 UHRF3S67X2 (J5, J12) Kirk Key K1 MIB MOB1 Liebert APM #1 *See Note 4 J5 3 4 X2 J12 1 2 3 4 X2 J5 TB3 1 2 See Note 3 TB2 1 2 3 Kirk Key K2 2 Fuses 2A SKRU MOB2 Liebert APM Bypass Module Only One Shown Notes 1.
Parallel System and LBS System Installation Figure 28 Locations of ports J1, J2 and J3 on bypass module Input/output dry contact and EPO/BCB/MBC interface J1 ~ J3 port can’t connect to phone! J4 J1 J1 J10 MFP_C MFP_S J12 INTELLISLOT2 INTELLISLOT3 MFP_O BFP_S BFP_O INV_S INV_O INPUT_1 BFP_C DRIVER J11 INV_C ENV_DET GND OUT GND INPUT_2 ONLINE +12V GND Q3BP BAT_READY +12V EPO-NO EPO-NC LBS J9 BCB_IN J6 J8 BAT_GND +12V PARA GND BAT-OUT Q2BP J3 J3 BAT-IN J5 +12V PA
Parallel System and LBS System Installation 4.3 LBS System 4.3.1 Cabinet Installation A dual bus system consists of two independent UPS systems, each containing one or more parallel UPS modules, as shown in Figure 30. The dual bus system has high reliability and is suitable for loads with multiple input terminals. For a single-input load, an optional static transfer switch can be fitted to achieve the transfer between the two outputs of the dual bus system.
Parallel System and LBS System Installation Figure 31 Connection of typical dual bus system of two parallel systems UPS 1 UPS 2 UPS 3 Bypass Module Bypass Module UPS 4 Bypass Module Bypass Module J1 J1 J1 J1 J2 J2 J2 J2 J3 J3 J3 J3 LBS Cable LBS Cable Figure 32 Connection of typical dual bus system of two single UPS’s without redundant LBS cable UPS 1 UPS 2 Bypass Module Bypass Module J1 J1 J2 J2 J3 J3 LBS Cable Figure 33 Connection of typical dual bus system of two single
Battery Installation 5.0 BATTERY INSTALLATION 5.1 Introduction Emerson recommends that the batteries in external cabinets be the same type and made by the same manufacturer as the internal batteries in the Liebert APM. If multiple sets of batteries connected in parallel are used to provide the required battery backup run times, fit each set with an isolating device to permit working on one of the battery sets while leaving the others in service and providing backup protection. 5.
Battery Installation 5.3 UPS Batteries—Liebert APM 45kVA Frame Only The Liebert APM’s internal batteries are fully charged before the unit is shipped. During storage and transportation, some charge is lost. All batteries should be recharged before use. The battery charger works only when the Liebert APM is connected to input power and turned On.
Battery Installation Figure 35 Internal battery control wiring Battery Breaker Liebert APM DC Bus W61 W62 Neg. Midpoint Liebert APM Internal Battery Neutral (Neg. Midpoint) W63 Aux.
Battery Installation 5.4 External Battery Cabinet Installation 5.4.1 Matching Battery Cabinets A matching battery cabinet is available. Refer to Figure 37. The same model battery cabinet may be installed in parallel in multiple cabinet strings for additional capacity. Battery run time depends on the cabinet model, the number of cabinets and the load on the UPS. Handling—The battery cabinet has casters to facilitate movement over short distances.
Battery Installation 5.4.2 Connecting the Batteries If the Liebert APM battery cabinets are installed on a raised floor, the battery power cables and circuit breaker control cables may be routed to the UPS cabinet through the bottom of the cabinet. If the Liebert APM battery cabinets are installed adjacent to one another on a solid floor, these cables may be passed between the cabinets through slots in the lower sides of the cabinets.
Battery Installation Figure 38 Battery trays for 600mm battery cabinet HX300 HX330 HX205 HX150 51 Liebert® APM™
Battery Installation 603797 Page 1, Rev.
Battery Installation 5.4.3 Installation Considerations Position—Liebert battery cabinets come in versions specific to the left side of the UPS. If the system includes a matching Liebert BDC, the cabinet should be mounted to the right of the UPS (nearest the busbars) and the battery cabinet(s) should be installed to the left of the UPS.
Battery Installation Table 9 Control wiring for Liebert APM to battery cabinet From To Liebert APM UPS Bypass Module (X2 J4 & J8) Battery Cabinet Terminal Strip (TB1) J4-2 TB1-12 J4-3 TB1-11 J4-4 TB1-10 J8-1 TB1-6 J8-2 TB1-7 J8-3 TB1-8 J8-4 TB1-9 Figure 40 Battery cabinet connection to Liebert APM Neg. Mid Pt. Positive W22 Neutral W23 Negative GRD Fault CT AC 120V from UPS BDSi Fuse Block MX Ground W24 Blue (Not Used) Aux.
Battery Installation 5.5 Non-Standard Batteries When batteries other than a matching battery cabinet are used, a remote battery disconnect switch with overcurrent protection is required per the National Electrical Code. Contact your local Emerson sales representative about this option. Refer to Figures 87 and 88 for details. Install battery racks, cabinets and batteries in accordance with the manufacturer's instructions.
Battery Installation Figure 42 Control wiring diagram for battery ground fault detection option W600 Red UHRF3S67X2 (J9) Blk UHR93S6A1ZA6 Output EMI Board Liebert APM Bypass Module Output A Output B Output C Output N X2_J4 UHRF3S67X2 UHW241M5 Auxiliary Power Board Blk Red Brn Blk Red X2_J9 W603 W601 Liebert APM Bypass Module Red Brn Blk J1 Red J4 J5 W602 CT Blk J7 12V Battery Breaker GND J9 Blk Brn Blk Brn Positive Liebert APM DC Bus Neutral Liebert APM Internal Battery Liebert®
Liebert BDC™ 6.0 LIEBERT BDC™ The Liebert BDC is designed to operate in UPS normal mode, static bypass mode and maintenance mode. The Liebert BDC offers either 45kVA or 90kVA capacity to match the associated Liebert APM frame offerings. Each of the Liebert BDC capacities offer optional input 208V, 480V and 600V internal transformers as well as multiple output distribution selections.
Liebert BDC™ 6.3 Maintenance Mode When the Liebert BDC is in Maintenance mode (MBB closed; BIB/MIB open), it provides an alternate path for power to the connected equipment should the UPS need to be taken out of service for limited maintenance or repair. In this mode of operation, no power is supplied to the UPS and the load is NOT protected by the UPS. 6.4 Locating the Cabinet This Liebert BDC may be mounted to the left of the UPS or installed as a stand-alone unit.
Liebert BDC™ 6.5.3 Input/Output Wiring Follow the steps below to connect the input wiring: NOTE Input wiring must be installed using conduit if cabinet is not mounted to the immediate right of the UPS. 1. Locate the input wiring access (top or bottom access), remove the conduit landing plate and punch the appropriate size hole for the size conduit being used. Pull the three/four input wires through it, allowing some slack for installation.
Liebert BDC™ Figure 45 BDC connection to Liebert APM Output Neutral W91 MBB Utility W04 W05 W06 ØA ØB ØC AC Output MIB Kirk Key K1 W88 W89 W90 Kirk Key K2 AC Input 4 BIB W07 W08 W09 Output Ground 3 W85 W86 W87 A B C N PE 2 4 3 1 (2) Fuses Ground 2A to Unit Frame 3 3 432 SKRU 4 1 2 3 4 5 6 7 8 9 10 11 12 K0 Input Neutral Main Ground Busbar To TB1 See Note 1 Push Button AC 120V Ground to Unit Frame Inner Door SKRU - Solenoid Key Release Unit KO - Key Operator UAM04012 Field-Suppl
Liebert BDC™ 6.6 Bolting Cabinets Together NOTE UPS wiring must be completed before the cabinets are bolted together. 1. Line up cabinets so that mounting holes are aligned. Figure 46 Bolting Liebert APM to a Liebert BDC A Washer Split, M10 Hex Head Bolt, M10 2 3 Washer Flat, M10 1 Hardware for bolting units is in a bag attached to the Liebert BDC. See form included with UPS. Place cabinets so mounting holes are aligned.
Installation Drawings 7.0 INSTALLATION DRAWINGS The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert APM UPS System cabinets (UPS, Liebert BDC and battery). Figure 47 UPS dimensions- front view 55.4" (1408mm) 23.8" (604mm) 1. All dimensions are in inches (mm). 2. 24" (610) minimum clearance above unit; 36" (914) front access required for service. 3. Keep cabinet within 15 degrees of vertical. 4.
Installation Drawings Figure 49 UPS dimensions continued, center of gravity—side, top and bottom views 23.4" (595mm) See Detail A 3" (77mm) 9.2" (235mm) Power Cable Entry 21.26 x 7.87" (540 x 200mm) 28.3" (719mm) Bracket Centers Vent Screen 34.3" (871mm) Power Cable Entry 21.26 x 7.87" (540 x 200mm) 28.3" (719mm) TOP VIEW 0.8" (21mm) BOTTOM VIEW 39-1/2" (1000mm) Mechanical Stop Caster 8.9" (226mm) 1.4" (36mm) Detail A 31.
Installation Drawings Figure 50 Liebert APM with top fan kit Caster Mechanical Stop DETAIL A Top Fan Flange to Flange 13.2" (335mm) 3" (77mm) 20.7" (526mm) 9.2" (235mm) 12.1" (308mm) FRONT See Detail A Power Cable Entry 21.26" x 7.87 (540mm x 200) 28.3" (718mm) Bracket Centers Vent Screen 34.3" (871mm) Power Cable Entry 21.26" x 7.87" (540x 200mm) 8.9" (226mm) 28.3" (719mm) TOP VIEW 23.4" (595mm) 0.8" (21mm) BOTTOM VIEW 1.4" (36mm) 31.5" (800mm) w/o Side Panels 39.
Installation Drawings Table 11 Center of gravity and weights for Liebert APM 90 kVA frame Center of Gravity KVA Rating Dimension X in. (mm) Weight, lb (kg) Dimension Y in. (mm) Dimension Z in. (mm) Unit Shipping No Internal Options 15 16.65 (423) 37.64 (956) 18.78 (477) 796 (362) 896 (407) 30 16.18 (411) 38.66 (982) 18.54 (471) 872 (396) 972 (442) 45 15.79 (401) 39.88 (1013) 18.35 (466) 948 (431) 1048 (476) 60 15.47 (393) 41.30 (1049) 18.
Installation Drawings Table 12 Center of gravity and weights for Liebert APM 90 kVA frame with top fan option Center of Gravity KVA Rating Dimension X in. (mm) Weight, lb (kg) Dimension Y in. (mm) Dimension Z in. (mm) Unit Shipping Top Fan Option Only 15 17.99 (457) 37.83 (961) 18.70 (475) 827 (376) 927 (421) 30 16.34 (415) 38.90 (988) 18.43 (468) 903 (410) 1003 (456) 45 15.94 (405) 40.08 (1018) 18.23 (463) 979 (445) 1097 (498) 60 15.63 (397) 41.54 (1055) 18.
Installation Drawings Table 13 Center of gravity and weights for Liebert APM 45 kVA frame Center of Gravity kVA Rating Dimension X in. (mm) Weight, lb (kg) Dimension Y in. (mm) Dimension Z in. (mm) Unit Shipping 12HX100 Batteries 15 14.29 (363) 31.50 (800) 21.30 (541) 1922 (874) 2022 (919) 30 13.94 (354) 33.46 (850) 21.59 (548.4) 1998 (908) 2098 (954) 45 13.62 (346) 35.04 (890) 21.73 (552) 2074 (943) 2174 (988) 12HX150 Batteries 15 14.25 (362) 30.91 (785) 21.
Installation Drawings Figure 51 UPS main components—typical unit UAM02000 Rev. 2 Liebert APM 45kVA Frame Liebert APM 90kVA Frame Liebert® APM™ 68 UAM02000 Rev.
Installation Drawings Figure 52 UPS cable connections—45kVA and 90kVA frames 45kVA frame 90kVA frame 69 Liebert® APM™
Installation Drawings Figure 53 Battery cabinet connection to UPS Refer to Table 15 for interconnect wiring NOTES 1. Dimensions are in inches [mm]. 2. Control wiring and power wiring must be run in separate conduits. 3. Emerson recommends using only copper cables. 4. All wiring must be in accordance with national and local electrical codes. Liebert® APM™ 70 UAM02021 Rev.
Installation Drawings Figure 54 Battery cabinet connection to UPS (continued) 600mm Battery Cabinet 900mm Battery Cabinet Table 15 Run Interconnect wiring for Liebert APM to battery cabinet From To Conductors A UPS Battery Busbar External Battery Cabinet Busbar Positive, DC Neutral, Negative B Battery Cabinet Terminal Block TB1 UPS Static Bypass Assembly J4 and J8 Battery Breaker Shunt and Aux Contacts See Figure 40 for additional details.
Installation Drawings Figure 55 Battery cabinet outline drawing, weights and center of gravity, 600mm cabinet 3.75" (95mm) Outside Panel Cable Entry Area 8.2" x 8.7" (210 x 220mm) 2 Places FRONT Cable Entry Area 14.6" x 7.6" (370 x 190mm) 2.5" (65mm) Outside Panel 7.9" (200mm) Outside Frame 13" (300mm) Outside Frame 34.3" (872mm) 23.7" (602mm) Cable Entry Area 7.9" x 23.6" (200 x 600mm) TOP VIEW Maximum Door Swing - 120° 1. All dimensions are in inches (mm). 2.
Installation Drawings Figure 56 Battery cabinet outline drawing, weights and center of gravity 900mm cabinet 4" (101mm) Outside Panel Cable Entry Area 14.6" x 7.6" (370 x 190mm) 17.1" (434mm) Outside Panel FRONT Cable Entry Area 8.2" x 8.7" (210 x 220mm) 2 Places 18.2" (464mm) 20" (507mm) Y X Z Battery Type 12HX400-FR 17.3 (440) 35 (890) 20 (510) 12HX505-FR 17.3 (440) 33 (840) 20.9 (530) 12HX540-FR 17.3 (440) 33 (840) 20.9 (530) 12.6" (320mm) Outside Frame 14.1" (359mm) Bracket Centers 34.
Installation Drawings Figure 57 Outline drawing, Liebert BDC for Liebert APM, 15-45kVA 11.5" (292mm) Outside Panel Cable Entry Area 6.2" x 13.2" (57 x 335mm) X 39.5" (1000mm) Z Cable Entry Area 11.4" x 13.2" (290 x 335mm) Cable Entry Area 11.4" x 13.2" (290 x 335mm) 6.5" (164mm) Outside Panel 23.6" (600mm) Cable Entry Area 6.2" x 13.2" (57 x 335mm) 34.6" (870mm) 28.3" (719mm) Bracket Centers 6.5" (164mm) Outside Panel 78.7" (200mm) 23.7" (602mm) 5.
Installation Drawings Figure 59 Liebert BDC connection to UPS 37.5" (953mm) Links for Main to Bypass (Single Input Only) 2.2" (56mm) Typ. 6 Places Main Input Busbars Bypass Busbars 1.97" (50mm) Typ. 3 Places See Detail B Ground See Detail C Output Busbars RIGHT SIDE DC Busbars See Detail D 2.36" (60mm) Typ. 2 Places DETAIL B (Panel Removed) UAM02021 Rev. 3 23.6" (600mm) Input Breaker LDB Input Ground Bus System Input Busbar Located at Rear, Typ. 78.
Installation Drawings Table 17 Run Interconnect wiring for Liebert APM to Liebert BDC From To Conductors A Utility AC source BDC System Input Bus Phase A, B, C B Utility AC Source BDC System Input Bus Neutral C BDC Bypass Isolation Breaker UPS Main Input Phase A, B, C D BDC Bypass Isolation Breaker UPS Main Input Neutral E UPS Output MBC Maintenance Isolation Breaker Phase A, B, C F UPS Output MBC Maintenance Isolation Breaker Neutral G BDC Panelboard Load AC Connection Phas
77 4.3" (110mm) 5.5" (140mm) 5.5" (140mm) 6.5" (165mm) 11.0" (280mm) 9.8" (250mm) 5.5" (140mm) 5.5" (140mm) 11.0" (280mm) 9.8" (250mm) 6.5" (165mm) 5.5" (140mm) 5.5" (140mm) 5.5" (140mm) BYPASS DISTRIBUTION CABINET 4.3" (110mm) 6.9" (175mm) 3.7" (94mm) Front Cabinet Base Bracket (See Detail B) 39.2" (997mm) 3.5" (89mm) .75 (19mm) Minimum FLOOR Detail A FLOOR UAM08020 Rev.
Liebert IntelliSlot® Installation 8.0 LIEBERT INTELLISLOT® INSTALLATION 8.1 Liebert IntelliSlot Communication The Liebert APM has three Liebert IntelliSlot ports to allow installation of optional communication cards. Liebert IntelliSlot cards communicate via Liebert’s proprietary Velocity protocol to cards that translate the information into such protocols as SNMP and Modbus. Other cards provide dry contact signals for external signaling of operating status.
Liebert IntelliSlot® Installation 8.2.1 Liebert IntelliSlot® Unity Cards—IS-UNITY-LIFE, IS-UNITY-S, IS-UNITY-DP • IS-UNITY-LIFE (Included): Offers a web interface to manage and configure the Emerson Life.net and Emerson proprietary protocols for use with the Emerson Life Station™, Liebert Nform® and Emerson® Trellis™. • IS-UNITY-DP: Offers a web interface to monitor and configure the Life.
Liebert IntelliSlot® Installation 8.4 Liebert IntelliSlot® Relay Card The Liebert IntelliSlot Relay card (IS-RELAY) provides voltage-free contact closures for remote monitoring of alarm conditions. Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals, the easy-to-install card integrates with AS/400 computers (additional cable required) and other relay contact monitoring systems. The relay card is rated for 24 VAC/DC at 1A.
Liebert IntelliSlot® Installation 8.4.2 Liebert IntelliSlot® Relay Card Jumper Setup The Liebert IntelliSlot Relay Card has five jumpers, P3 through P7, as shown in Figure 64. Each jumper connects two pins. Figure 64 Jumper location and numbering Front of Card Jumper P6 Jumper P5 Jumper P4 Jumper P3 Jumper P7 By default all five jumpers have shunts installed. The two pins are shunted together to provide the functions shown in Table 21, allowing relay commons to be tied together.
Liebert IntelliSlot® Installation 8.5 Liebert IntelliSlot™ MultiPort Card The Liebert IntelliSlot MultiPort card provides four sets of voltage-free contact closures for remote monitoring of alarm conditions UPS operation On Battery and battery low condition. A typical application is to allow a maximum of four computer systems to simultaneously monitor the status (e.g., utility power failure-low battery) of a single UPS.
Liebert IntelliSlot® Installation Figure 66 Alber BDSi controller and input connection Rear Panel 120VAC 50/60Hz ! INPUT XXXXXXXXXXXXXAXA XXXXXXXXXXXA OUTPUT POWER X XXXXXXA Input 83 Liebert® APM™
Liebert IntelliSlot® Installation 8.7 Battery Temperature Compensation For a UPS with external batteries, an optional battery temperature interface optimizes the external battery management by connecting up to four external temperature sensors from the battery cabinets to a control unit inside the UPS.
Operator Control and Display Panel 9.0 OPERATOR CONTROL AND DISPLAY PANEL 9.1 Operator Control Panel The control panel and LCD on the front of the Liebert APM lets the operator: • • • • Turn the UPS On or Off. Transfer into the various operating modes. Silence alarms. Check the status of the UPS and its batteries, including all measured parameters, events and alarms. The main areas of the control panel are shown below in Figure 68 and explained in Table 22.
Operator Control and Display Panel 9.2 Mimic Display Indicators Figure 69 Mimic display indicators location E ME R S O N TM 3 Network Power Mimic indicators 1. Rectifier indicator 2. Battery indicator 3. Bypass indicator 4. Inverter indicator 5. Load indicator 6. Status indicator 4 5 2 STATUS 6 1 Mimic indicators show the operational status of the Liebert APM by their color—green, amber or red—and whether they are ON (solid), flashing or OFF.
Operator Control and Display Panel 9.3 Control Buttons The Control Buttons on the front panel may be used to shut down the UPS completely, turn the inverter on or off, restart the UPS after a fault and silence the alarm, as shown in Figure 70. The function of each button is described in Table 24. NOTE To activate a button properly, press and hold until you hear a short beep—about two seconds.
Operator Control and Display Panel 9.5 LCD Overview The LCD on the front panel has five main sections, as shown in Figure 72. Press the F1 key below the LCD to scroll through these sections. • • • • UPS system information - view UPS name and model, date and time, overall status. LCD Menu - choose a category of data items to appear below the menus (see Table 26). Data and settings - view data items for the selected menu (see Table 26).
Operator Control and Display Panel 9.6 Navigation Keys The navigation keys on the front panel—F1 through F4 and Help—are used to access the LCD to view the current status and other information about the Liebert APM. Navigation key icons on the LCD appear above each key to indicate its operation (see Table 25). The keys are “soft keys” that can change functions according to the icon. • Use F1 to move to the home portion of the LCD.
Operator Control and Display Panel Figure 73 Menu tree Mains (input) Bypass Output Load System L-N voltage (V) L-N current (A) Frequency (Hz) L-L voltage (V) Power factor L-N voltage (V) Frequency (Hz) L-L voltage (V) L-N voltage (V) L-N current (A) Frequency (Hz) L-L voltage (V) Power factor Sout (kVA) Pout (kW) Qout (kVAR) Load level % Crest factor Sout (kVA) Pout (kW) Qout (kVAR) 9.
Operator Control and Display Panel Figure 74 Language selection screen Single POLSKI APM 090 kVA 02:17:47 ENGLISH DEUTSCH FRANCAIS ITALIANO ESPANOL NEDERLANDS SVENSKA PORTUGUES Language F1 9.9 F2 F3 F4 HELP Current Date and Time To change the system date and time: 1. From the main menu, press the F4 (shift) key to move the cursor to the Settings menu at the bottom of the screen. 2. Press HELP to select the Settings menu. 3.
Operator Control and Display Panel 9.10 UPS History Log The Liebert APM displays status changes as they occur and stores that data in the history log, as shown in Figure 76. • History Log: When a record moves to the history log, the time the status changed is recorded. The history log can hold up to 512 records. History log records may be viewed by accessing the Records menu. Figure 76 History log records Single APM 090 kVA 1 Ma in s v o lt .
Operator Control and Display Panel Figure 77 Opening display Single APM 090kVA 0 2 :1 7 : 4 7 EMERSON™ Network Power Press any key back to main menu F1 F2 F3 HELP F4 9.11.2 Default Screen After the UPS has powered up and completed a self-test, the output screen appears, as shown in Figure 78. This window is the default screen. Figure 78 Default screen Single APM 090 kVA 02:17:47 L1-N/L2 L2- N/L3 L-N voltage (V) 118.4 119.2 0.0 L-N current (A) 0.0 Frequency (Hz) 59.97 59.97 L-L voltage (V) 205.
Operator Control and Display Panel 9.11.4 Screen Saver Window If there has been no interaction with the Liebert APM’s LCD for 2 minutes, the screen saver window appears. It remains on the LCD for 2 minutes, then the screen will go dark. The LCD will become active again when any key is pressed. Figure 79 Screen saver window Single APM 090kVA 0 2 :1 7 : 4 7 EMERSON™ Network Power Press any key back to main menu F1 F1 9.
Operator Control and Display Panel 9.12.3 System Self-Test When a system self-test is completed, a pop-up window reports the results of the test, as shown at right. • Press the Help (Enter) key and the pop-up window closes. System Self-Test finished. Please check the current warnings 9.12.4 Battery Capacity Test Confirmation When a battery capacity test is started from the Command menu, the battery will be discharged to low-battery warning level.
Operator Control and Display Panel Table 26 UPS menus and data window items Menu Type Mains (input) Bypass Output Load System Battery Item Type Explanation L-N voltage (V) Phase voltage L-N current (A) Phase current Frequency (Hz) Input frequency L-L voltage (V) Line-line voltage Power factor Power factor L-N voltage (V) Phase voltage Frequency (Hz) Bypass frequency L-L voltage (A) Line-line voltage L-N voltage (V) Phase voltage L-N current (A) Phase current Frequency (Hz) O
Operator Control and Display Panel Table 26 UPS menus and data window items (continued) Menu Type Settings Command (start / stop battery & system tests) Run Time Version Item Type Explanation Display contrast Adjust the LCD display contrast Date format set Choose the format for date display: YYYY MM DD, DD MM YYYY and MM DD YYYY Date & time Set the date and time Comm1 baud rate Communication baud rate setting for Liebert IntelliSlot 1 Comm2 baud rate Communication baud rate setting for Li
Operation 10.0 OPERATION 10.1 Liebert APM Operating Modes The UPS is designed to operate as an on-line, double-conversion, reverse-transfer system in the following modes: • • • • • • • • • • • Normal Mode Battery Mode Auto-Restart Mode ECO Mode Bypass Mode Battery Start Mode Maintenance Mode (Manual Bypass) Sleep Mode Paralleling Mode Output Voltage Adjustment Generator Mode NOTE 1. The user controls and indicators mentioned in these procedures are identified in 9.0 Operator Control and Display Panel. 2.
Operation ECO Mode (Single-Module UPS System Only) When ECO mode is selected, the Liebert APM switches inverter power from the UPS input to the bypass input to save energy by improving UPS efficiency. In this mode, the bypass is the preferred source. If the bypass voltage or frequency becomes outside preset limits, the UPS load is transferred back to the inverter. Battery Start Mode The battery start option permits starting the Liebert APM with power supplied only by the batteries (at charged condition).
Operation Generator Mode The Liebert APM UPS can be set up for operation in Generator Mode by an Emerson Network Power Liebert Services engineer. The setup requires connecting J9 Pin 1 to Pin 4 or connecting J9 Pin 2 to Pin 4. The software must be configured to reflect the connection points as attached. 10.2 UPS Startup The Liebert APM must be fully installed and commissioned before startup, and external power isolators must be closed. Once those general conditions are met, the UPS may be started.
Operation Table 28 Mimic indicators after initialization LED Status Rectifier Indicator Green Battery Indicator Red Bypass Indicator Green Inverter Indicator Off Load Indicator Green Status Indicator Amber 7. Ensure that the Liebert FlexPower assembly ready switches are latched (in Down position). 8. Close the external output circuit breaker. 9. Press the INVERTER ON button for 2 seconds. The inverter indicator flashes while the inverter is starting.
Operation 10.2.3 Switching Between UPS Operation Modes To switch from Normal Mode to Static Bypass Mode—Press the INVERTER OFF button to switch to Bypass Mode (see Figure 70). NOTE In Static Bypass Mode, the load is being powered by the utility and is not protected from fluctuations in input power: spikes, sags and failure. To Switch From Bypass Mode To Normal mode—When the UPS is in Bypass Mode, press the INVERTER ON button. After the inverter enters normal operation, the UPS transfers to Normal Mode.
Operation 10.4 Switching the UPS from Normal Operation to Maintenance Bypass Follow the procedure below to transfer the load from the UPS inverter output to the Maintenance Bypass system. ! CAUTION This procedure must be performed by properly trained and qualified personnel who are knowledgeable about the operation of this system. Failure to follow these instructions will result in loss of power and possible damage to critical equipment.
Operation 10.5 Switching the UPS from Maintenance Bypass to Normal Operation Follow the procedure below to transfer the load from the Maintenance Bypass system to the UPS inverter output. These conditions must be met for this operation to proceed: • the UPS must be operating normally • the BIB breaker must be closed • the UPS system must be in the Maintenance Bypass mode of operation. ! CAUTION Risk of electrical shock and arc flash. Can cause property damage, injury and death.
Operation 10.6 De-Energize Liebert APM with Maintenance Bypass Cabinet ! CAUTION This procedure will remove power from the critical bus. To de-energize the system: 1. On the UPS control panel, press and hold the INVERTER OFF button for 2 seconds. 2. Open all battery circuit breakers(s) including internal battery breaker (if applicable). ! CAUTION Performing the next step will shut down the critical load. 3. If the MBC is an Emerson cabinet, open the Maintenance Isolation Circuit Breaker (MIB).
Operation 10.7 De-Energize Liebert APM Without Maintenance Bypass Cabinet ! CAUTION This procedure will remove power from the critical bus. To de-energize the APM: 1. On the UPS control panel, press and hold the INVERTER OFF button for 2 seconds. 2. Open all battery circuit breakers(s) including internal battery breaker (if applicable). ! CAUTION Performing the next step will shut down the critical load. 3. 4. 5. 6. Open the UPS output circuit breaker(s).
Operation Figure 82 Liebert APM six-breaker buyout paralleling configuration MBB Buyout Liebert APM Paralleling Switchboard * System AC Input 4 Wire +GND UIB See Note 7 UIB Opt.
Operation 10.8.1 Procedure to Take UPS1 Offline While Leaving UPS2 Online The procedure below is used to switch the system from parallel to single UPS operation. NOTICE 1. 2. 3. 4. 5. 6. 7. Risk of improper switching. Can cause damage to connected load. Verify that removal of UPS1 from the system bus will NOT overload UPS2 and cause the load to drop. Turn OFF the inverter on UPS1 (see Figure 82). Verify that UPS1 is now in Static Bypass Mode. Open Battery Breaker(s) for UPS1.
Operation 10.9 APM Procedure from Parallel Inverter Operation to Wrap-Around Bypass Note: MBB is OPEN. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. Turn OFF the Inverter on UPS1 (see Figure 82). Turn OFF the Inverter on UPS2. Verify that each UPS is now in Static Bypass Mode. Open Battery Breaker(s) for UPS1. Open Battery Breaker(s) for UPS2. Verify that the Battery Status Light on UPS1 and UPS2 turns Red. Close MBB - Bypass Breaker for System. Open UIB1. Open MOB1.
Operation 10.13 Emergency Shutdown With EPO This circuit has been designed to switch off the UPS in emergency conditions (i.e., fire, flood, etc.). The system will turn off the rectifier, inverter and stop powering the load immediately (including the inverter and bypass), and the battery stops charging or discharging. If the input utility is present, the UPS’s controls will remain active; however, the output will be turned off. To remove all power from the UPS, the external feeder breaker should be opened.
Operation 10.17 Replacing Dust Filters Installing the two dust filter sizes in a Liebert APM requires only a Phillips screwdriver. Each filter is held in place by a bracket on either side of each filter. Each UPS is shipped from the factory with two sets of washable and reusable dust filters. Refer to 12.3.2 - Air Filters for details about filter maintenance. To replace each filter: 1. Open the UPS front door and locate the filters on the back side of the front door (see Figure 83). 2.
Operation 10.18 Operation ! WARNING Risk of electrical shock and arc flash. Can cause property damage, injury and death. The Liebert APM contains high voltages internally. Components that can only be accessed by opening the protective cover with tools cannot be serviced or replaced by the user. Only properly trained and qualified service personnel are authorized to remove the protective covers. The Liebert APM operates in the modes shown in Table 31.
Operation Figure 85 Single module block diagram—Dual input configuration with three-breaker Liebert BDC Bypass Distribution Cabinet MBB * Bypass AC Input BIB 4-Wire + GND MIB AC Output Optional 208V 54-Pole 4-Wire + GND See Note 6 Static Bypass * Rectifier AC Input 4-Wire + GND UPS Cabinet See Note 7 Battery NOTES BIB - Bypass Isolation Breaker 1. Install in accordance with national and local electrical codes. MBB - Maintenance Bypass Breaker 2. Input and bypass must share the same single source.
Operation Figure 86 Block diagram—Single input configuration with four-breaker internal bypass UPS Cabinet System * AC Input 4-Wire + GND MBB RIB BIB MIB Output Busbar AC Output 208V 4-Wire + GND Static Bypass Battery 1. Install in accordance with national and local electrical codes. 2. A neutral is required from the system AC source. Emerson recommends a full-capacity neutral conductor and grounding conductors. 3. System AC input and output cables must be run in separate conduits. 4.
Specifications and Technical Data 11.0 SPECIFICATIONS AND TECHNICAL DATA 11.1 Conformity and Standards The Liebert APM has been designed to conform to the following standards: Safety UL 1778, CSA 22.2 107.3, 4th Edition Surge ANSI 62.
Specifications and Technical Data Table 34 45kVA Liebert BDC mechanical characteristics 15-45 Rated Power, kVA 23-5/8 x 39-1/2 x 78-3/4 (600 x 1000 x 2000) Dimensions, W x D x H, in (mm) Weight, lb (kg) No Distribution 525 (239) 225A Panelboard 625 (284) No Distribution & 480V Transformer 1070 (486) No Distribution & 600V Transformer 1085 (493) 225A Panelboard & 480V Transformer 1170 (532) 225A Panelboard & 600V Transformer 1085 (493) Color Black Protection Degree IEC (60529) Table 35 I
Specifications and Technical Data Table 37 900mm battery cabinet mechanical characteristics 15 - 90 Rated Power, kVA Dimensions, W x D x H, in (mm) 35-1/2 x 39-1/2 x 78-3/4 (900 x 1000 x 2000) Weight, lb (kg) with HX400 batteries 2693 (1224) with HX505 batteries 3245 (1475) with HX540 batteries 3345 (1520) Color Black Protection Degree IEC (60529) 11.
Specifications and Technical Data 11.4 UPS Electrical Characteristics Refer to additional circuit breaker notes in 3.2.8 - Accessory Fuses and Backfeed Breaker Wiring. NOTE The breakers and cables used must be in accordance with NEC ANSI/NFPA 70. A disconnect breaker must be provided for AC input, DC input and AC output. Recommended cable sizes are suitable for operation at a maximum temperature of 86°F (30°C).
Specifications and Technical Data Table 44 UPS currents and terminals—Output 208V Maximum Recommended Lug (T&B) Unit Rating Nominal Output Current OCP Device Rating Wire Compression Lug Two Hole 3/8" Bolt Mechanical Lug Two Hole 3/8" Bolt 15 42 130 (1) #1 54857BE 32209 30 M10 (3/8") 150 (1) 1/0 54860BE 32209 200 M10 (3/8") 175 (1) 2/0 54862BE 32209 225 M10 (3/8") 230 (1) 4/0 54866BE 32211 208 300 M10 (3/8") 300 (2) 1/0 54860BE 32209 250 350 M10 (3/8") 350 (2) 2/0
Specifications and Technical Data Table 47 Rectifier input Parameter 15-90kVA Rated AC Input Voltage 1 208/120V or 220/127V, 60Hz, 3-Phase, 4-Wire Plus Ground Input Voltage Range, Startup/Operating Input Voltage Range, Operating Frequency Power Factor THD 96-138V or 102-146V or -20%, +15% (Full Load) 72-138V or 76-146V or -40%, +15% (<80% Load) 50 or 60Hz (40-70Hz Range) 0.99 Full Load, 0.98 Half Load 3% THDI Full Load 1. Three-phase, four-wire and shared neutral with the bypass input.
Specifications and Technical Data Table 49 Inverter output to critical load Parameter 15 - 90kVA Rated AC Voltage 1 208/120, 220/127VAC, 60Hz, 3-phase, 3- or 4-wire plus ground Frequency 2 60Hz 110% load, 60 min 125% load, 10 min 150% load, 60 sec Overload Capacity Fault Current Non-Linear Load Capability Short circuit for 200 ms 3 100% Neutral Current Capability 170% Steady State Voltage Stability ±1% (balanced load) Voltage Regulation ±1% for balanced load ±5% for 100% unbalanced load P
Specifications and Technical Data Figure 87 Battery, circuit breaker and UPS wiring with external batteries with four connecting wires + U N P S N N - Figure 88 Battery, circuit breaker and UPS wiring with external batteries with three connecting wires + + N N - - Liebert® APM™ 122
Maintenance 12.0 MAINTENANCE 12.1 Safety Precautions Observe the safety precautions in Important Safety Instructions on page 1. Only properly trained and qualified personnel should perform maintenance on the UPS system. Observe all of the warnings and cautions below before performing any maintenance on the UPS system and associated equipment. Also observe the manufacturer's safety precautions pertaining to the battery, along with the battery safety precautions in this section.
Maintenance 12.2 Limited Life Components The Liebert APM UPS has a design life well in excess of 10 years. Well-maintained units can continue to provide economic benefits for 20 years or more. Long-life components are used in the UPS wherever practical and cost-effective.
Maintenance 12.3.2 Air Filters The air filters must be inspected and serviced on a regular schedule. The period between inspections will depend upon environmental conditions. Under normal conditions, the air filters will require cleaning or replacement approximately every two months. All Liebert APM models have replaceable filter elements behind the grille in the front of the unit. This element can be changed with the UPS operating, by opening the outer door for access.
Maintenance When replacing batteries, use the same number and type of batteries. ! WARNING Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause property damage, injury and deth. Lead-acid batteries contain hazardous materials. Batteries must be handled, transported, and recycled or discarded in accordance with federal, state, and local regulations. Because lead is a toxic substance, lead-acid batteries should be recycled rather than discarded.
Maintenance ! WARNING Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment damage, personal injury and death. Do not use equalize charging with valve-regulated, lead-acid batteries, such as those used in Liebert battery cabinets. Refer to the battery manufacturer’s manual, available on the manufacturer’s Web site, for specific information about equalize charging.
Maintenance 12.4 Detecting Trouble It is important that the operator check the instrument readings if abnormal equipment performance is suspected. Any metered value that differs appreciably from normal could mean an impending malfunction, and should be investigated. Items to check on the various UPS display screens include: 1. Output voltage of all phases should be within 2% of normal voltage. Output currents on each phase should not normally differ by more than 20%.
Maintenance APPENDIX A HAZARDOUS SUBSTANCES OR ELEMENTS ANNOUNCEMENT Table 56 Hazardous substances or elements Hazardous Substances Lead (Pb) Mercury (Hg) Cadmium (Cd) Chrome (Cr6+) Polybrominated Biphenyl (PBB) Polybrominated Diphenyl Ethers (PBDE) Hex copper stud X ✔ ✔ ✔ ✔ ✔ PCBA X ✔ ✔ ✔ ✔ ✔ AC capacitor X ✔ ✔ ✔ ✔ ✔ DC capacitor X ✔ ✔ ✔ ✔ ✔ Fan X ✔ ✔ ✔ ✔ ✔ Cables X ✔ ✔ ✔ ✔ ✔ LCD X X ✔ ✔ ✔ ✔ Sensors X ✔ ✔ ✔ ✔ ✔ Large-medium power magnetic comp
Maintenance APPENDIX B UPS STATUS MESSAGES Table 57 shows all event messages as they appear in the current status area of the LCD or the history log, along with a description and recommended actions, if any. For further information on the current status area and the history log, see 9.10 - UPS History Log. Table 57 UPS status messages Event Message Description / Suggested Action (if any) Comm. Fail The CAN communication between internal monitor and rectifier/inverter/bypass fails.
Maintenance Table 57 UPS status messages (continued) Event Message Description / Suggested Action (if any) Inverter Asynchronous This alarm is triggered by an inverter software routine when the inverter and bypass waveforms are misaligned by more than 6 degrees in phase. This alarm resets automatically once the condition is no longer true. 1. First check if the alarm “Bypass unable to trace” or “Bypass abnormal” occurs. If so, solve it first. 2. Verify the waveform of the bypass voltage.
Maintenance Table 57 UPS status messages (continued) Event Message Description / Suggested Action (if any) DC Bus Abnormal Shut off inverter due to abnormal DC bus voltage. Contact Liebert Services at 800-543-2378 for assistance. System Transfer The whole paralleled UPS system transferred to bypass at the same time. This message will appear on the UPS which passive transfer to bypass. DC Bus Overvoltage Rectifier, inverter and battery converter were shutdown because DC bus voltage is too high.
Maintenance Table 57 UPS status messages (continued) Event Message Description / Suggested Action (if any) Byp. Abnormal Shutdown Both bypass and inverter voltages unavailable. Load interruption. Mains Neutral Lost AC Input mains reference neutral not detected. Battery Room Alarm Environment in battery room needs attention. Rec Flash Update Rectifier firmware is being updated. Inv Flash Update Inverter firmware is being updated. Monitor Flash Update Monitor firmware is being updated.
Technical Support / Service Web Site www.liebert.com Monitoring liebert.monitoring@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets liebert.upstech@emerson.